EB 8389S EN
55
Tests
4.1
Drive signal diagram
steady-state
The 'Drive signal diagram steady-state'
(Tests) allows you to check the results of the
drive signal diagram steady-state in Statisti-
cal information (in-service monitoring) more
closely (see
u
pointing problems in supply pressure, it can
also detect defective actuator springs.
The test is started in the manual mode.
During the test the valve moves to various
fixed valve positions distributed over the
working range of the valve. The drive signal
y is measured for each valve position x and
compared with the reference graph.
The recorded data of the drive signal y are
plotted versus the valve position x in a graph
(Repetition).
Requirements
1. A single-acting actuator is mounted on
the valve.
2.
No booster is mounted on the control
valve.
3. A reference test has been performed.
See
u
Section 1.2.1.
If a reference test has not be stored in the
positioner, the data of the first test per
-
formed are used as the reference.
Fig. 9:
Diagnosis > Tests > Drive signal diagram steady-state
Содержание TROVIS SAFE 3731 Series
Страница 5: ...EB 8389S EN 5...
Страница 49: ......
Страница 73: ...EB 8389S EN 73...
Страница 83: ...EB 8389S EN 83 Binary input...
Страница 101: ...EB 8389S EN 101...
Страница 102: ...102 EB 8389S EN...