![Samson TROVIS SAFE 3730 Series Скачать руководство пользователя страница 32](http://html1.mh-extra.com/html/samson/trovis-safe-3730-series/trovis-safe-3730-series_operating-instructions-manual_3973652032.webp)
32
EB 8389-1S EN
Valve signature
3.
Device settings > Alarm settings > Status
classification > Supply pressure
−
Permissible limit exceeded:
, , , [ ]
−
Too high: , [ ], ,
−
Fluctuates: [ ], , ,
−
Too low: , [ ], ,
−
Not available:
, , , [ ]
4.3.1
Analysis and monitoring
The positioner generates the 'Supply pres
-
sure status' message with the defined status
classification.
−
'Too high' if the supply pressure exceeds
the 'Upper limit'.
−
'Not available' if the supply pressure falls
below 0.1 bar.
−
'Too low' if the supply pressure exceeds
the 'Lower limit'.
−
'Permissible limit exceeded' if the supply
pressure exceeds 7.0 bar.
A fluctuating supply pressure is recognized
by the positioner whenever the supply pres-
sure continuously falls below the 'Lower limit'
and rises above the 'Upper limit'. In such
cases, the positioner generates the 'Supply
pressure status' message with the defined
status classification.
Diagnostics > Monitoring > Actuator
−
Supply pressure status: , , ,
−
Supply pressure (Code 48 - d7)
−
Min. supply pressure
−
Time stamp of min. supply pressure
−
Max. supply pressure
−
Time stamp of max. supply pressure
−
Dwell time (supply pressure < 1.0 bar)
−
Dwell time (supply pressure > 7.0 bar)