8-12
EB 6495-2 EN
Operation
Determining and changing the internal set
point is described in section 8.3.4.
Cascade control
For cascade control (
M.1-3
) the cascade
can also be opened and closed by switching
over the set point.
−
The cascade is opened if the following
applies in the slave controller [2]: SP =
SPI.
−
The cascade is closed if the following ap-
plies in the slave controller [2]: SP =
SPM.
8.3.4 Switching over and
changing internal set
points
In the operating menu, one of the set points
SP1, SP2, SP3 or SP4 can be assigned to the
internal set points SPI, depending on the
configuration.
Required configuration for determining the set
point
SP1
C.2.1.1-1/-2/-3/-4
SP2
C.2.1.1-2/-3/-4
SP3
C.2.1.1-3/-4
SP4
C.2.1.1-4
Example:
The controller [1] has two internal
set points SP1 and SP2 (configured with
1C.2.1.1-2
).
−
The set point SP1 is to be switched over
to set point SP2.
−
The set point SP1 is to be kept at 70
while the set point SP2 is to be changed
to 100.
The controller is currently in the operating
level:
Î
Enter the operating menu (see sec-
Switchover between internal set points
1x Select
Set point
menu item.
1x Activate
Set point
menu item.
Note
Содержание TROVIS 6495-2
Страница 6: ...EB 6495 2 EN...
Страница 46: ...6 6 EB 6495 2 EN...
Страница 90: ...8 26 EB 6495 2 EN...
Страница 94: ...9 4 EB 6495 2 EN...
Страница 96: ...10 2 EB 6495 2 EN...
Страница 98: ...11 2 EB 6495 2 EN...
Страница 100: ...12 2 EB 6495 2 EN...
Страница 102: ...13 2 EB 6495 2 EN...
Страница 104: ...14 2 EB 6495 2...
Страница 107: ...EB 6495 2 15 3 Certificates TR CU certificate...
Страница 108: ...15 4 EB 6495 2 Certificates...
Страница 109: ...EB 6495 2 15 5 Certificates...
Страница 110: ...15 6 EB 6495 2...
Страница 185: ......