1.4
Setting the system time
The current time and date need to be set immediately after start-up and after a power failure
lasting more than 24 hours.
Set the
system time
in the settings level under the menu item “Date / time”. The
Automatic sum-
mer time
function can also be activated or deactivated in this menu item.
4
System time:
Time-dependent functions of the saved application are based on the system
time set in the PLC.
4
Automatic summer time:
The summer time is automatically set on the last Sunday in
March at 02:00 h and the winter time on the last Sunday in October at 03:00 h.
Proceed as follows:
Activate the editing mode.
Display: Entering the key code
0000
blinks
Enter the key code.
Confirm the key code entered.
Display: Settings level
The “Date / time“ menu item is highlighted.
Activate the menu item “Date / time“.
Display: System time (DD.MM.YYYY HH:MM)
Activate the editing mode for the system time.
Display: Date (
DD
) blinks.
Enter date.
Confirm date entered.
Display: Month (
MM
) blinks.
8
EB 5571 EN
Operation
Entering the key code
0000
Settings level
Date / time
RS-232/Slave
RS-485/Master
RS-232/Prog
Meter bus
Universal input type
Back
Settings level
28.11.2005 10:00
RS-232/Slave
RS-485/Master
RS-232/Prog
Meter bus
Universal input type
Back