Display
Parameter designation
Range of values (default)
OT activation value rated operation
–30 °C to OT deactivation value reduced operation (–15 °C)
Only with CO1 -> F07 - 1.
OT deactivation value reduced operation
OT activation value rated operation to 50 °C (15 °C)
Only with CO1 -> F07 - 1.
OT deactivation value rated operation
0 to 50 °C (22 °C)
Only with CO1 -> F07 - 1.
Lag time of heating circulation pump
15 to 2400 sec (180 sec)
EB 5433 EN
87
Appendix