The assignment of the control circuits to the mode selector switches depends on the system
code number (Anl):
System
(Anl)
Mode selector switch
Top
Middle
Bottom
1
Heating circuit 1
Heating circuit 2
Pre-control circuit
2
Heating circuit 1
DHW heating
Heating circuit 2
3
Heating circuit 1
Heating circuit 2
Heating circuit 3/Pre-control
circuit
4
Heating circuit 1
DHW heating
Pre-control circuit
5
Heating circuit 1
DHW heating
Heating circuit 2/Pre-control
circuit
6
Heating circuit 1
Heating circuit 2
Heating circuit 3
7
Heating circuit 1
DHW heating
Pre-control circuit
8
Heating circuit 1
DHW heating
Heating circuit 2/Pre-control
circuit
9
Heating circuit 1
DHW heating
Heating circuit 2
10
Heating circuit 1
DHW heating
Heating circuit 2
1.2 Operating modes
Day mode (rated operation)
Regardless of the programmed times-of-use and summer mode, the set points relevant for rated
operation are used by the controller.
Night mode (reduced operation)
Regardless of the programmed times-of-use, the set points relevant for reduced operation are
used by the controller.
Automatic mode
During the programmed times-of-use, the controller works in rated operation. Outside these
times-of-use, the controller is in reduced operation, unless control operation is deactivated de-
pending on the outdoor temperature. The controller switches automatically between both oper-
ating modes.
Manual op 0 –
Valves and pumps can be controlled manually.
8
EB 5179 EN
Operation
Содержание TROVIS 5179
Страница 87: ...EB 5179 EN 87 Communication...
Страница 93: ...EB 5179 EN 93 System Anl 3 Option Type 5244 Type 5257 5 System Anl 4 Option Type 5244 Type 5257 5...
Страница 94: ...94 EB 5179 EN System Anl 5 Option Type 5244 Type 5257 5 System Anl 6 Option Type 5244 Type 5257 5...
Страница 95: ...EB 5179 EN 95 _ _ _ 3 1 2 System Anl 8 Option Type 5244 Type 5257 5 System Anl 7 Option Type 5244 Type 5257 5...
Страница 103: ...Fb Function WE Anl Comments Function block parameters Range of values default setting...