8.6.1 Sending text message in case of a fault alarm
Currently, text messages can only be sent to the German D1 network. The corresponding access
numbers into the D1 network as well as the mobile phone number of the recipient must be set in
the PA9 level:
4
D1 access number:
0171 252 10 02
(add 0 in front when dialing from a private branch exchange)
Digits 0 to 9, P = pause, - = end, max. 22 characters
The access number is assigned by Deutsche Telekom and may alter.
4
Mobile phone number:
49 xxx yyyyyyy , where xxx stands for 160, 171 or any other valid
D1 dialing code and yyyyyy represents the specific phone number of the mobile phone you
wish the alarm to be sent to.
Digits 0 to 9, P = pause, - = end, max. 14 characters
Note!
Currently, text messages can only be sent to the German D1 network.
Functions
WE
Configuration
Modbus
ON
Co9 -> Fb00 = OFF
Modem
OFF
Co9 -> Fb01 = OFF
Text message via SMS
OFF
Co9 -> Fb06 = ON
SMS dialing procedure
OFF
Co9 -> Fb07
Alarm sent per fax
OFF
Co9 -> Fb10 = OFF
Parameters
WE
Parameter level / Range of values
Access number (UGno)
–
PA9 / configurable as required*
Mobile phone number (HAndY)
–
PA9 / configurable as required**
* Digits 0 to 9, P = pause, - = end, max. 14 characters
** Digits 0 to 9, P = pause, - = end, max. 22 characters
8.6.2 Sending fax in case of a fault alarm
The device type is forwarded in addition to a detailed error description. The recipient’s fax
number must be programmed in the PA9 level. Optionally, also the sender’s station ID can be
programmed; this number will then be forwarded as well. If no station ID is specified, the string
“nicht verfügbar“ (not available) is inserted.
4
Fax number:
Digits 0 to 9, o = Pause, - = end, max. 14 characters
(place an additional 0 in front when dialing from a private branch exchange)
74
EB 5179 EN
Operational faults
Содержание TROVIS 5179
Страница 87: ...EB 5179 EN 87 Communication...
Страница 93: ...EB 5179 EN 93 System Anl 3 Option Type 5244 Type 5257 5 System Anl 4 Option Type 5244 Type 5257 5...
Страница 94: ...94 EB 5179 EN System Anl 5 Option Type 5244 Type 5257 5 System Anl 6 Option Type 5244 Type 5257 5...
Страница 95: ...EB 5179 EN 95 _ _ _ 3 1 2 System Anl 8 Option Type 5244 Type 5257 5 System Anl 7 Option Type 5244 Type 5257 5...
Страница 103: ...Fb Function WE Anl Comments Function block parameters Range of values default setting...