Control levels
Note!
Any changes in the configuration level (PA and CO levels) may cause errors in the sys-
tem. Therefore, they must be only performed by the specialist!
Fig. 1 shows the level structure in the
TROVIS 5177 Ventilation Controller. It also
shows the operating steps that need to be
taken to access each individual level. The con-
troller contains two main levels: the operat-
ing level and the configuration level. Use the
changeover key (C) to switch between the lev-
els. The operating level contains the info lev-
els, in addition to this, when switched to the
manual mode, a manual level is also accessi-
ble. The configuration level contains the
parameter levels, the system code number
level and the configuration levels. The info,
parameter and configuration levels are
assigned to an index from 1 to 9 which is the
same in all three levels. In this way, specifica-
tions concerning the heating coil are always
termed InF1, PA1 und Co1 (index 1) accord-
ing to the level. All other indices are summa-
rized in the table opposite.
Usually, the ventilation controller is in the
operating level and the time appears on the
display. In Fig. 1, for example, 10:24 is
indicated on the display. Apart from the
time, symbols to represent the operating
mode and operating status as well as the sys-
tem represented symbolically appear on the
display. Refer to page 147 for a summary
of the major symbols.
A bar graph appears on bottom right-hand
corner of the display, showing roughly the
control signals Y1, Y2 and Y3. This bar
graph is shown in the operating level.
Note: Two minutes after the last entry, the
controller returns automatically from the
configuration level back to the operating
level.
Designation
of levels
Information,
parameters, functions
InF1, PA1, Co1
Heating coil
InF2, PA2, Co2
Heat recovery unit, mixed air
chamber
InF3, PA3, Co3
Cooling coil
InF4, PA4, Co4
Fans, humidifier
InF5, PA5, Co5
Functions affecting all
systems
Co6
Sensor initialization
PA7, Co7
LON communication
Co8Error initialization
PA9, Co9
Modbus communication
Anl
System code number and
control method
12
EB 5177 EN
Operation
Control levels