manualshive.com logo in svg
background image

Operating Instructions

EB 9527-2 EN

Firmware: TROVIS-VIEW 4/Media 6 V3.10-3.19

Tr

anslat

ion of original instruct

ions

®

Electronics from SAMSON 

Edition February 2016

TROVIS-VIEW 4 Software for Media 6

Media 6 Differential Pressure Meter

Configuration with TROVIS-VIEW 4

Содержание Media 6

Страница 1: ...EN Firmware TROVIS VIEW 4 Media 6 V3 10 3 19 Translation of original instructions Electronics from SAMSON Edition February 2016 TROVIS VIEW 4 Software for Media 6 Media 6 Differential Pressure Meter...

Страница 2: ...if not avoided will result in death or seri ous injury WARNING Hazardous situations which if not avoided could result in death or seri ous injury NOTICE Property damage message or mal function Note A...

Страница 3: ...urement differential pressure mea surement level measurement in transportation vehicles 25 3 2 1 Flow rate measurement 26 3 2 2 Counting flow rate measurement 29 3 2 3 Differential pressure measuremen...

Страница 4: ...4 EB 9527 2 EN...

Страница 5: ...Media 6 device for example editing plant texts saving and printing configuration data Almost the entire configuration of a Media 6 device can be performed using the software The user level set to Main...

Страница 6: ...00 or higher are not compatible with earlier versions e g firmware version 2 30 2 Communication with Media 6 Differential Pressure and Flow Meter To establish communication between the software and t...

Страница 7: ...he settings needed for communication with a Media 6 device Identification General data Tank Medium Maintenance Certificates and approvals Operation 3 1 Liquid level measurement By default all settings...

Страница 8: ...ification Type Media 6 Differential Pressure Meter Type 5006 Version Firmware version Addition Identifier for different versions Serial no Serial number of the connected Media 6 device 3 1 2 General d...

Страница 9: ...A1 in Enter the value in the range between 0 and 100 A blinking bar graph on the display indicates that the adjusted value has been exceeded with a max contact or the value has fallen below the adjus...

Страница 10: ...to calculate tank characteristic A default set of data with predetermined values is available in the tank database Load these data and overwrite them with the corresponding tank geometry data and sett...

Страница 11: ...ur entries Cylinder upright Cylinder horizontal Ball Characteristic mode Define tank geometry by selecting the corresponding entry Shape of tank bottom Drop down list with five entries Flat head Toris...

Страница 12: ...t 20 mA corresponds to the tank MCN or to the gauge pipe marker SCN Select from toggle field Max tank content MCN Tank content up to overflow gauge pipe SCN Permissible filling limit in Geometric volu...

Страница 13: ...EB 9527 2 EN 13 User interface...

Страница 14: ...14 EB 9527 2 EN User interface 3 1 4 Medium Medium The data for a maximum of four media can be entered...

Страница 15: ...to Medium 4 Medium database General medium data Tank pressure Density calculations Densities Operating filling limit hazard warning Calculated values Medium database Load data You can load and modify...

Страница 16: ...emperature of the tank This value depends on the tank material operating temperature and the process medium Tank pressure Additional pressure Operating pressure Unit of Operating pressure Additional p...

Страница 17: ...nsity No No values need to be entered in Gas density in the tank and Gas density in the low pressure pipe When By preset pressure is selected Min differential pressure Max differential pressure Final...

Страница 18: ...ressure pipe are automatically converted and displayed Gas density in tank and Gas density in low pressure pipe in m Details on gas column correction Gas density in the tank depends on the nominal pre...

Страница 19: ...g the tank Calculated values Reading of the previously entered value and the automatically calculated value It cannot be edited and is only shown on the software Max tank content MCN Entered in m Tank...

Страница 20: ...20 EB 9527 2 EN User interface Save The data can be saved to a file txt e g filling level_01 txt and processed on a computer using other standard software...

Страница 21: ...es e g error status sum of error codes are shown and can be reset Other maintenance data Measuring range reading of the connected Media 6 device Reset Restart the Media 6 device This activates changed...

Страница 22: ...Information on the connected Media 6 device concerning certificates and approvals Ex certification Indicates whether the connected Media 6 device is approved for use in hazardous areas Oxygen Indicate...

Страница 23: ...ontent in Differential pressure Current differential pressure in mbar Max tank content MCN in Tank content up to overflow gauge pipe SCN in Tank content up to Operating filling limit UCW in Min differ...

Страница 24: ...Off Limit switch A2 State of limit switch A2 On Off Tap position State of equalizing valve between the and measuring lines Only vis ible if the Equalizing valve open signal Yes see section 3 1 2 on p...

Страница 25: ...lling level in tank truck can also be selected The user level is password protected samson for first installation TROVIS VIEW 4 3 20 and higher DURCHFLUSS after update TROVIS VIEW 4 before 3 20 More d...

Страница 26: ...r the data required for flow rate measurement Flow rate is visible together with its associated parameters Medium density Density Rho in kg m Enter the medium density for the operating conditions Flow...

Страница 27: ...ed or changed data to the database General medium data Medium identifier Unit Medium identifier A maximum of 8 characters can be entered to describe the medium The text appears in up per case letters...

Страница 28: ...on the display of the Media 6 device The unit selected in this case relates to the previous Pressure parameter A drop down list contains the units mbar bar kPa psi mm H2O cm H2O m H2O in H2O Calculate...

Страница 29: ...ow rate mode is visible together with its associated parameters Besides the parameters entered in Flow rate additional data in Flow rate specifications and Calculated values are required Count Select...

Страница 30: ...of counts Max 99 999 999 reading Maximum recordable number of counts At 100 flow rate and the adjusted count the min interval until counter overflow can be deduced Max recordable counts Max 99 999 999...

Страница 31: ...he required data Differential pressure is visible together with its associated parameters Differential pressure specifications Min differential pressure Max differential pressure Unit Min differential...

Страница 32: ...cifications Additional pressure Additional pressure Yes No When Yes is selected enter the operating pressure and select the corresponding unit from the drop down list mbar bar kPa psi mm H2O cm H2O m...

Страница 33: ...lder enter the required data See details in section 3 1 on page 7 In addition to the details weight details listed in General data are required General data Tank truck Permissible total weight Own wei...

Страница 34: ...an calibration Menu bar Device Calibration Zero and span calibration Run Zero and span are calibrated Note To be able to perform the calibration in the TROVIS VIEW 4 software refer to u EB 9527 3 for...

Страница 35: ...in the online mode In this case communication is established per manently between the Media 6 device and TROVIS VIEW All the configuration and operat ing data are transferred cyclically from the Medi...

Страница 36: ...otection at the selector switch on the Media 6 device front left on the housing Set slider switch 4 to OFF see write protection in u EB 9527 3 Menu bar Device Write To write data to the Media 6 device...

Страница 37: ...ent is 1 5 The SAMSON memory pen can also be used to exchange data between TROVIS VIEW 4 and the Media 6 device The memory pen serves as a data carrier and is able to load and store data from the Medi...

Страница 38: ...38 EB 9527 2 EN...

Страница 39: ...EB 9527 2 EN 39...

Страница 40: ...SAMSON AG MESS UND REGELTECHNIK Weism llerstra e 3 60314 Frankfurt am Main Germany Phone 49 69 4009 0 Fax 49 69 4009 1507 samson samson de www samson de EB 9527 2 EN 2016 08 18 English...

Отзывы: