14
KA 5500-Z EN
Technical data
6 Technical data
Inputs
4x Pt 1000, PTC or Ni 1000 sensor inputs, alternatively configurable
for binary alarms
Outputs
1x three-step signal: rating max. 250 V AC, 2 A
alternatively 1x on/off signal: rating max. 250 V AC, 2 A
2x pump output: rating max. 250 V AC, 2 A
All outputs are relay outputs with varistor suppression,
2x 0 to 10 V or PWM signal, configurable, to issue a control signal or
for pump speed control
Interfaces
RS-485 device bus interface for communication with TROVIS 5578 (po
-
larity independent)
Supply voltage
85 to 250 V, 48 to 62 Hz, max. 6.6 VA
Ambient temperature
0 to 50 °C (operation), –10 to +60 °C (storage and transport)
Degree of protection
IP 40 according to EN 60529
Class of protection
II according to EN 60730
Degree of contamination
2 according to EN 61010-1
Overvoltage category
II according to EN 60730
Noise immunity
According to EN 61000-6-1
Noise emission
According to EN 61000-6-3
Weight
Approx. 0.5 kg
Conformity