2
Mounting the supply
pressure regulator
To prevent excessive amounts of condensed
water from collecting, the distance between
the compressor and supply pressure regula-
tor should be kept as short as possible.
Make sure the drain plug faces downwards
in versions with a filter receptacle.
2.1 Compact supply pressure
regulator
The supply pressure regulator can either be
mounted directly in the pipeline of the air
supply or on rails or brackets using the cor-
responding mounting parts (see accessories
table in section 7).
Observe the direction of flow of the supply
air. An arrow on the nameplate indicates
the direction.
2.1.1 Direction of flow
In the compact supply pressure regulators
4708-10xx/-11xx/-14xx
and
-17xx
the
direction of flow can be changed as follows:
1. Unscrew both fixing screws and lift the
supply pressure regulator off its connect-
ing plate.
2. Remove the diverting gasket, turn it
180 degrees and reposition it as shown
in Fig. 3.
Note:
The long rubber finger of the gas-
ket must always point in the direction of
the regulator outlet.
3. Fasten the supply pressure regulator
onto the connecting plate.
4. Stick the enclosed adhesive label over
the arrow of the nameplate, ensuring the
arrow indicates that the supply air flows
in the opposite direction.
8
EB 8546 EN
Mounting the supply pressure regulator
G
4708-112.
0
6
3-....
0
6
3-....
4708-112.
G
Fig. 3 · Changing the direction of flow in compact supply pressure regulators
Connecting plate
Standard label
Diverting gasket
Connecting plate
Label with arrow
Fixing screws
Long rubber finger always pointing towards the regulator outlet
Supply
pressure
regulator