EB 2173 EN
Operation
Fig. 3:
Adjustment diagrams
Dynamic behavior of Type 2430 K Control Thermostat
The dynamics of the regulator are mainly determined by the response of the sensor with its
characteristic time constant.
The table shows the dynamic behavior of the Type 2430 K Thermostat measured in water.
Table 2:
Dynamic behavior of Type 2430 K Thermostat
Type 2430 K
Sensor Ø
Time constant [s]
Without
With
Thermowell
Adsorption principle
9.5 mm
15 s
40 s
16 mm
30 s
80 s
Air sensor
8 s
–
1)
1)
Thermowell not possible
0
20
40
60
80
100
120
140
150
0
1
2
3
4
70...150
50...120
40...100
25...70
0...35
°C
0
20
40
60
80
100
120
140
150
0
1
2
3
4
°C
70...150
50...120
40...100
25...70
0...35
Scale marking on the thermostat head
Set point ranges
Set point ranges
DN 15 to 25
DN 32 to 50
Type 43-3