Mounting and start-up
5.2.2 Selecting cables and
wires
The minimum radial thickness of the conduc-
tor insulation must be suitable for the con-
ductor diameter and type of insulation. It
must be at least 0.2 mm.
The diameter of an individual wire in a
fine-stranded conductor must not be smaller
than 0.1 mm.
Protect the conductor ends against splicing,
e.g. by using wire-end ferrules.
5.2.3 Cable entry
The M16x1.5 cable gland is designed for a
clamping range of 6 to 12 mm.
The cage clamp terminals hold wire
cross-sections of 0.2 to 1.5 mm².
Î
Unscrew the cover and remove it.
Î
To unlock the cage clamp terminals:
place a slotted screwdriver on the plastic
part (Fig. 4) and lightly push it into the
terminal block.
Î
Insert or remove the wire
without force
.
Î
Guide wires for the reference variable to
the ter11 and –12 located on
the housing.
A reference variable above or below the
static destruction limit will damage the posi-
tioner.
Keep the reference variable within the static
destruction limit of ±32 V.
Mounting the cover
Î
Mount the cover, briefly turn it counter
-
clockwise to center it. Turn it clockwise to
firmly close it.