background image

T 8313 EN  

5

Table 1.2: 

Explosion‑protection certificates for Type 3372

Type 3372

With integrated i/p converter

With Type 3725 Positioner (direct attachment)

 1)

Actuator area

120 cm²

120 cm²

350 cm²

Rated travel

15 mm

15 mm

15 mm

30 mm

ATEX

No.

PTB 99 ATEX 2049

PTB 11 ATEX 2020 X

Date

1999-07-06

2011-08-25

Type of protection

II 2G Ex ia IIC T6

II 2G Ex ia IIC T4

CSA Group

No.

2703735 X

Date

2014-06-03

Type of protection

Ex ia IIC T4;

 

Class I, Zone 0, AEx ia IIC T4;

 

Class I, Div. 1, Groups A, B, C & D

GOST

 

No.

RU C-DE.GB08.B.00697

Date

2014-12-15

Valid until

2019-12-14

Type of protection

1EX ia IIC T4 Gb X

1) 

Versions with Type 3730-x or Type 3731-x Positioner on request

Table 1.3: 

Further technical data for Type 3372

Type 3372

With integrated i/p converter

With Type 3725 Positioner (direct attachment)

Actuator area

120 cm²

120 cm²

350 cm²

Rated travel

15 mm

15 mm

15 mm

30 mm

Pneumatic data

Tight-closing function

Stem 

retracts

Stem 

retracts

Stem 

extends

Stem 

extends

Stem 

retracts

Stem 

retracts

Stem 

extends

Stem 

extends

Stem 

retracts

Stem 

extends

Stem 

retracts

Stem 

extends

Bench range

0.4 to 1.4

1.4 to 2.3

2.1 to 3.3 0.4 to 1.4

1.4 to 2.3

2.1 to 3.3 1.5 to 2.1 2.1 to 2.7 1.5 to 2.7 2.2 to 3.8

Supply pressure

Max. 

6 bar

Max. 4 bar

Max. 

6 bar

Max. 6 bar 

1)

Max. 6 bar

Materials

Actuator housing

Aluminum, powder paint coated

Aluminum, powder paint coated

1.0332

Diaphragm

NBR

NBR

NBR

Actuator stem

1.4305

1.4305

1.4401/1.4404

Weight (without positioner)

kg (approx.)

3.7

3.3

15

Attachment

Form B

Form B or Form C

 

(see Table 2)

Form C

Compliance

 · 

1) 

With “stem extends” fail-safe action and travel stop, the supply pressure must not exceed the upper spring range value by more than 1.5 bar.

Table 1.4: 

Technical data of Type 4744‑2 Limit Switch

Type 4744‑2 Limit Switch

Travel range

15 mm

Permissible load

AC voltage: 250 V/5 A

DC voltage: 250 V/0.4 A

Temperature range

–20 to +60 °C

Degree of protection

IP 66

Explosion protection

Flameproof enclosure II 2G Ex db IIC T6-T5

Weight, approx.

0.4 kg

Associated documentation

u

 T 8367

Содержание 3372

Страница 1: ...aphragm cases a rolling diaphragm and internal springs The Type 3372 Electropneumatic Actua tor is controlled by a 4 to 20 mA signal For throttling service an i p converter is integrated into the actu...

Страница 2: ...ator stem 8 8 Plug connector 14 Zero adjuster 8 2 Rod type yoke 8 9 Cover plate span and tight closing function 15 Force switch 8 3 Actuator springs 10 i p converter 16 Rod nut 8 4 Rolling diaphragm 1...

Страница 3: ...41 7 33 60 54 2 61 Fig 7 Type 3372 Electropneumatic Actuator with 350 cm actuator area for the direct attachment of a Type 3725 Positioner Legend for Fig 6 and Fig 7 1 2 Diaphragm case 20 Hexagon bol...

Страница 4: ...Switching accuracy 0 14 mA Air consumption in steady state When w 100 6 bar 200 ln h 4 bar 160 ln h 100 ln h with a supply pressure up to 6 bar and a signal pressure of 0 6 bar Air output capacity To...

Страница 5: ...on Stem retracts Stem retracts Stem extends Stem extends Stem retracts Stem retracts Stem extends Stem extends Stem retracts Stem extends Stem retracts Stem extends Bench range 0 4 to 1 4 1 4 to 2 3 2...

Страница 6: ...t required for mounting the actuator Table 2 Mounting types see Fig 8 and Fig 9 Version Integrated i p converter Type 3725 Positioner direct attachment Actuator area 120 cm 120 cm 350 cm Travel 15 mm...

Страница 7: ...bar of 2 3 4 5 6 120 15 1800 0 4 to 1 4 4 0 5 1 7 0 7 1 9 3 1 1800 1 4 to 2 3 8 1 7 2 8 0 8 2 3 2 4 4 1800 2 1 to 3 3 12 2 5 4 0 350 5250 1 5 to 2 1 8 3 15 6 65 6 65 6 65 5250 2 1 to 2 7 6 7 35 9 5 30...

Страница 8: ...22 English Order specifications Electropneumatic actuator Type 3372 Version With integrated i p converter With Type 3725 Positioner direct attachment Attachment to the valve Type Mounting type Accord...

Отзывы: