EB 2517 EN
45
Malfunctions
Table 9:
Troubleshooting
Malfunction
Possible reasons
Recommended action
Upstream pressure
exceeds the adjusted
set point.
Insufficient pressure pulses on the
operating diaphragm.
Î
Connect the control line on site for regulators
with external control line.
Î
Clean the control line and screw fittings.
Pressure tapped at the wrong place
(regulator with external control line).
Î
Reconnect the control line at another point.
Î
Do not connect the control line at pipe bends or
necks.
Regulator installed against the flow.
Î
Install the regulator so that the direction of flow
matches the direction indicated by the arrow on
the body.
Regulator or K
VS
/C
V
coefficient too
small
Î
Check the sizing.
Î
Change K
VS
/C
V
coefficient, if necessary or in
-
stall a different sized regulator.
Î
Contact SAMSON's After-sales Service depart-
ment.
Foreign particles blocking the plug
Î
Remove foreign particles.
Î
Replace damaged parts.
Î
Contact SAMSON's After-sales Service depart-
ment.
Compensation chamber in the wrong
position or too small (with steam).
Î
Reconnect compensation chamber at a different
place or replace it (see section 7.7).
Defective operating diaphragm
Î
Replace damaged diaphragm.
Pressure drops below
the adjusted set point.
Foreign particles blocking the plug
Î
Remove foreign particles.
Î
Replace damaged parts.
Î
Contact SAMSON's After-sales Service depart-
ment.
Seat and plug are worn or leak.
Î
Replace the damaged seat and plug.
Î
Contact SAMSON's After-sales Service depart-
ment.
Pressure tapped at the wrong place
(regulator with external control line).
Î
Reconnect the control line at another point.
Î
Do not connect the control line at pipe bends or
necks.
Regulator or K
VS
/C
V
coefficient too
large
Î
Check the sizing.
Î
Change K
VS
/C
V
coefficient, if necessary or
install a different sized regulator.
Î
Contact SAMSON's After-sales Service depart-
ment.
Control line blocked
Î
Clean the control line and screw fittings.
Strainer blocked.
Î
Clean strainer.
Содержание 2417 Series