EB 2090 EN

3

Safety instructions

General safety instructions

4

The regulator may only be mounted, started up or operated by trained and
experienced personnel familiar with the product.
According to these mounting and operating instructions, trained personnel refers
to individuals who are able to judge the work they are assigned to and recognize
possible dangers due to their specialized training, their knowledge and
experience as well as their knowledge of the relevant standards.
All safety instructions and warnings in these mounting and operating instructions,
particularly those concerning assembly, start-up and maintenance, must be
observed.

4

For appropriate operation, make sure that the regulator is only used in
applications where the operating pressure and temperatures do not exceed the
operating values based on the sizing data submitted in the order.

4

Note that the manufacturer does not assume any responsibility for damage
caused by external forces or any other external factors.
Any hazards which could be caused in the regulator by the process medium or
operating pressure are to be prevented by means of appropriate measures.

4

The Type 2040 Safety Temperature Monitors do not have their own potential
ignition source according to the ignition risk assessment stipulated in
EN 13463-1: 2001, section 5.2, even in the rare incident of an operating fault.
Therefore, they

do not

fall within the scope of Directive 94/9/EC.

4

The regulator complies with the requirements of the European Pressure Equipment
Directive 97/23/EC. The declaration of conformity issued for a valve bearing the
CE marking includes information on the applied conformity assessment procedure.
The declaration of conformity can be provided on request.

TÜV typetesting/EC type examination

The Type 2040 Safety Temperature Monitors are typetested by TÜV (German technical surveil-
lance association). The test mark is available on request.
An EC type examination according to Pressure Equipment Directive 97/23/EC, Module B has
been performed on the Type 2040 Safety Temperature Monitor.

Содержание 2040

Страница 1: ...Self operated Temperature Regulators Type 2040 Safety Temperature Monitor STM Mounting and Operating Instructions EB 2090 EN Edition October 2014 Fig 1 Type 2040 Safety Temperature Monitor ...

Страница 2: ...et point indication 7 4 Maintenance 8 5 Service 8 6 Dimensions 9 7 Technical data 10 8 Nameplate 11 2 EB 2090 EN Contents CAUTION Indicates a hazardous situation which if not avoided could result in minor or moderate in jury Note Indicates supplementary explanations information and tips Definitions of the signal words used in these instructions ...

Страница 3: ... damage caused by external forces or any other external factors Any hazards which could be caused in the regulator by the process medium or operating pressure are to be prevented by means of appropriate measures 4 The Type 2040 Safety Temperature Monitors do not have their own potential ignition source according to the ignition risk assessment stipulated in EN 13463 1 2001 section 5 2 even in the ...

Страница 4: ...rature drops the plug moves in the closing direction restricting the medium flow If the medium temperature drops fur ther the valve is closed completely when the temperature reaches the adjusted set point The set point temperature and the throttling range in front of it can be adjusted within the set point range The valve first opens again when the medium temperature has exceeded the adjusted set ...

Страница 5: ...aling 3 Set point adjuster 3 1 Cap 3 2 Lock nut 4 Positioning spring 5 Tubular plug 6 Temperature sensor 7 Connection nut with spherical liner accessories 8 Connection nut with flat gasket accessories 8 Connection nut with flat gasket Connection with soldering nipples brass or welding ends stain less steel Connection nut with soldering nipples brass or welding ends stainless steel ...

Страница 6: ... regulator can be installed in any de sired position 4 The direction of flow must match the ar row on the valve body 3 Set point adjustment See Figs 3 and 4 The safety temperature monitor has been ad justed by the manufacturer to a set point tem perature limit of Tset point 10 C set point range from 30 to 10 C or 37 C set point range from 45 to 10 C After removing the cap 3 1 and undoing the lock ...

Страница 7: ...er clockwise until the flow noise inside the regulator ceases i e the valve is closed 4 Calculate the temperature difference be tween the momentary ambient temperature and the required set point temperature Tset point to be adjusted 4 Divide the calculated temperature differ ence by 13 The result shows how may turns of the set point adjuster Fig 4 are required 4 Turn the set point adjuster clockwi...

Страница 8: ...suitability of these regulators for oxygen service If the point at which the regulator closes devi ates strongly from the adjusted set point shut off may be impaired because the seat and plug are clogged up with dirt or due to natu ral wear In this case remove the regulator from the pipeline and clean it If necessary replace the plug seal with a new one 5 Service If malfunctions or defects occur c...

Страница 9: ... For pipe 16 For pipe 28 Soldering nipple brass Dimensions in mm DN 15 DN 25 L1 155 L2 165 d 16 1 28 5 D 21 3 33 7 Welding ends stainless steel Height H1 Without set point indication H1 108 1 mm With set point indication H1 116 1 mm Weight 1 8 kg without connecting parts Connecting parts with spherical liner Connecting parts with flat gasket ...

Страница 10: ...ting pressure 40 bar Max perm differential pressure p 25 bar Leakage rate 0 05 of KVS at 10 C 0 1 of KVS at 45 C Hysteresis 2 K Accuracy 1 C Permissible temperature range 60 C to 60 C Temperature differential between open closed 17 K 1 On request Table 2 Materials Material number according to DIN EN Type 2040 Safety Temperature Monitor Body CC491K G CuSn5ZnPb Bellows CW453K CuSn8F40 Spring 1 4310 ...

Страница 11: ...ate Fig 6 Nameplate specifications Flow of direction Production number 3 Model number with modification index Valve coefficient KVS 5 Set point temperature with unit Test mark 1 Keep regulator free of oil and grease 1 Omitted at a set point temperature between 31 C and 45 C ...

Страница 12: ...SAMSON AG MESS UND REGELTECHNIK Weismüllerstraße 3 60314 Frankfurt am Main Germany Phone 49 69 4009 0 Fax 49 69 4009 1507 Internet http www samson de EB 2090 EN S Z 2016 12 ...

Отзывы: