60 | SAMLEX AMERICA INC.
SYMPTOMS
POSSIBLE CAUSE
REMEDY
• There is no AC output from
the GFCI outlet
(5, Fig 6.1)
• Green LED marked "POWER
ON"
(2, Fig 6.1)
is lighted
• No buzzer alarm
• Status LED on the GFCI
outlet
(5C, Fig 6.1)
is OFF
• Reset Button on the GFCI
outlet
(5A, Fig 6.1)
has
popped out
GFCI has tripped due to
leakage or due to Neutral
to Ground bond on the
load side.
Check load side circuits for leakage or Neutral
to Ground bond and remove this ground fault
condition. Switch ON the inverter if in OFF
condition. Check that the Green LED marked
"POWER ON"
(2, Fig 6.1)
is lighted. Press Reset
Button
(5A, Fig 6.1)
on the GFCI to reset the
GFCI. On resetting, the Status LED on the GFCI
(5C, Fig 6.1)
will be lighted Green.
• There is no AC output from
the GFCI outlet
(5, Fig 6.1)
• Green LED marked "POWER
ON"
(2, Fig 6.1)
is lighted
• No buzzer alarm
• Status LED on the GFCI
outlet
(5C, Fig 6.1)
is lighted
Red
Self monitoring circuit of
GFCI is defective.
Call Technical Support. GFCI will be required to
be replaced.
SECTION 11 |
Troubleshooting Guide