background image

SPU / SPLS 

Single Point Unit / Single Point Light & Sound 

IS SPU_SPLS 190304 (Sv_Eng) 

 

 

Operation 

GB 

 

FUNCTION 

When power supply is switched on, a green LED will flash to 
indicate 

power ”ON”. This will also start the heating process of 

the sensor. After approximately 4 minutes the green LED will 
light and indicate 

”Sensor Active”. 

 
The unit has one yellow and two red LEDs. The yellow LED 
indicates low gas concentration 

(Alarm C) 

and the red LEDs 

indicate medium gas concentration 

(Alarm B) 

and high gas 

concentration 

(Alarm A)

 
When gas is detected the LEDs 

(2)

 will light and the relay 

corresponding to the alarm level will change state. If alarm delay 
is chosen (see below) the respective LED will flash, and it will 
light (and the relay will change state) when the chosen delay 
time is exceeded.  
 

SPLS 

High-intensity LED lights up at B-alarm, buzzer is activated at A-
alarm. The time delay does not apply to sound & light lid.  
 

AUTOMATIC/MANUAL RESET  

Is managed by DIP switch 

(1)

 n

o

 

3 where “on” means automatic 

reset and “off” means manual reset by pressing the “Reset/Test/ 
Service”-button (located under the cover). 
 

ALARM TIME DELAY (T1) 

Is managed by DIP-switches 

(1)

 n

1 and n

2: 

 

n

n

Delay 

on 

on 

No alarm delay 

off 

on 

1 minute alarm delay 

on 

off 

10 minutes alarm delay 

off 

off 

30 minutes alarm delay 

 

FAIL SAFE 

Relays are in normal mode energized and will change state if 
power failure or if a fault situation occurs. 
 

SELF TEST FUNCTION  

Press the “Reset/Test/Service”-button 

(5)

 for 5 seconds and the 

test program will start and go through all LED functions and all 
relay functions in five seconds intervals. 
 

FAULT FUNCTION 

If there is a voltage drop (GV-value below 0,1V) from the sensor 
there is a fault situation. During the first four hours the green 
LED will 

go out and the other LED’s will flash. Alarm relay C will 

change state. 
 
After four hours the LED “Alarm B” will light (other LED’s will go 
off) 

and relay “Alarm B” will also change state. 

 

SERVICE FUNCTION  

Pressing the ”Reset/Test/Service” button 

(5)

 for 10 seconds will 

lock all alarm functions for 60 minutes. During this period, it is 
always possible to start a new 60-minutes period by pressing the 
button for 10 seconds again. Return to active status is automatic 
at the end of the 60-minutes period or may be done manually by 
a single press on the 

“Reset/Test/Service”-button. When the 

service function is activated all 

LED’s will flash and all relays will 

be in normal mode position. 
 

  

NOTE! 

The alarm functions in the lid of the SPLS are not 
deactivated when the service mode is active. 

 

SOUND, LIGHT & MUTE BUTTON (SPLS only) 

”MUTE” button 

(9)

 mutes the buzzer for 60 minutes. If gas 

concentration drops beneath A-level alarm buzzer 

(7)

  is  

deactivated and if gas concentration drops beneath B-level 
alarm LED 

(8)

  is deactivated. More details look on page 2 

(10)

 

MANUAL ACTIVATION OF ALL ALARM LEVELS 

Closed contact/loop gives full sensor signal resulting in all alarm 
levels getting activated 

(11)

 

INSTALLATION 

The detector is connected to the screw terminals on the main 
PCB-board 

(6)

. See the wiring diagram

 

 

 

NOTE! 

SETTING ALARM LEVELS (THRESHOLDS) 
The monitoring unit is delivered as standard with basic set 
alarm levels (see page 3). 
 
Alarm levels must be set for chosen gas/detector type 
during commissioning.  
Settings depend on detector type and are made using the 
DT300 service instrument. DT300 is to be plugged in the test 
terminal. (3) 
 
(Option) The unit can be delivered with pre-set alarm levels 
for specific detector/gas. 
Contact us for more information. 

 

MAINTENANCE, ANNUAL CHECK 

The monitoring unit should be checked at least twice a year. 
A basic function test can be performed using the DT300 service 
instrument. 
Extended control and calibration require also test gas with a 
specific concentration. 
Contact us for more information.

 

 

TECHNICAL DATA 

Housing:  

Polycarbonate, PC 

Power supply: 

 

  SPU230 / SPLS230: 

85..230V AC, 50/60Hz 

  SPU24 / SPLS24:

 

12..24V AC/DC

 

Power consumption: 

Max 3W 

Indications:  

Power/Active and alarm indication on 
three levels. 

Outputs relay:  

Potential free contacts (230V, max 5A) 

Ambient temp: 

-40..50

0

C  

Humidity: 

0..95% RH (non-condensing) 

Glands: 

5 x M16 membrane glands 

Screw terminals: 

< 1,5 mm

2

, fuse < 10A 

Dimensions (LxHxD) 

160 x 80 x 60 mm 

 

  

NOTE! 

High voltage under the lid! 
The unit must only be opened by authorized personnel! 

 

 

NOTE! 

Detectors with semi conductive (SC) sensor head are not 
gas specific. Care should be taken when installing the 
equipment to minimize any cross contamination from other 
gases or vapors.  
For further guidance on specific applications contact us. 

 

 

 

Содержание SPU

Страница 1: ...e Point Light Sound IS SPU_SPLS 190304 Sv_Eng 1 SE GB Instruktioner Instructions PPM C C B B A A L N S SPU T T1 4 min T1 T1 C alarm B alarm B alarm A alarm C alarm A alarm 1 2 3 4 2 1 2 3 4 5 6 7 8 9 10 11 12 5 Gas ppm 6 SPLS 7 8 9 11 ...

Страница 2: ... Sv_Eng 2 Kopplingsschema Wiring diagram MPS MP Series GEX SPU SPLS SPU SPLS 230 SPU SPLS 24 SPU SPLS 3 wire 4 20 mA 6 TR EC Series TR EC Series R 250Ω 24VDC 0 VDC R 250Ω max 24VDC 0 VDC SPU SPLS TR SC TR IR Series R 250Ω 0 VDC 24VDC I OUT JP1 R 250Ω 24 VDC 0 VDC 0 10 VDC ...

Страница 3: ...SPU SPLS Single Point Unit Single Point Light Sound IS SPU_SPLS 190304 Sv_Eng 3 SPLS logikmatris SPLS logical matrix Kontroller Controls ...

Страница 4: ...SPU SPLS Single Point Unit Single Point Light Sound IS SPU_SPLS 190304 Sv_Eng 4 Relä lägen Relay states ...

Страница 5: ... GB NOTE The SPU are normally supplied with default set alarm thresholds These must be verified or reset during commissioning Alarm levels must always be set on each channel for proper gas and detector type Default factory settings Offset Alarm C 1 0V Alarm B 2 0V Alarm A 3 0V Factory gas specific pre calibration can be delivered upon request It must be specified when ordering See the catalogue SE...

Страница 6: ... Återgång sker automatiskt då tiden är ute alternativt manuellt genom ett kort tryck på knappen När servicefunktionen är aktiverad blinkar samtliga lysdioder och samtliga reläer är i normalläge OBS Larmfunktionerna i locket på SPLS avaktiveras ej när serviceläget är aktivt LJUD LJUS MUTE KNAPP Endast SPLS MUTE knapp 9 tystar summer under 60 minuter Om gaskoncentrationen återgår under A larmnivå av...

Страница 7: ... seconds again Return to active status is automatic at the end of the 60 minutes period or may be done manually by a single press on the Reset Test Service button When the service function is activated all LED s will flash and all relays will be in normal mode position NOTE The alarm functions in the lid of the SPLS are not deactivated when the service mode is active SOUND LIGHT MUTE BUTTON SPLS o...

Страница 8: ...SPU SPLS Single Point Unit Single Point Light Sound IS SPU_SPLS 190304 Sv_Eng 8 SE GB Måttritningar Dimensional drawings mm Reservation för tekniska ändringar Specifications subject to change ...

Отзывы: