37
6
INSTALLATION & OPERATION
Standard Battery Charging Programs
The SCC-30AB provides 8 standard battery charging algorithms (programs) that
are selected with the DIP Switches. These standard algorithms are suitable for
Lead-Acid batteries ranging from sealed (Gel, AGM, maintenance free) to flooded
to L-16 cells and Ni-Cd etc.
Table 6.1 below summarizes the major parameters of the standard charging algo-
rithms. Note that all the voltages are for 12V systems. For 24 V system, multiply
the voltages by 2.
All values are 25ºC (77ºF).
Table 6.1. Standard Battery Charging Programs
Note: All the voltages given in the Table are for 12V Battery System.
For 24V Battery Systems multiply the voltage values by 2.
DIP
Switches
(2-3-4)
A
Battery Type
B
PWM Absorption
Voltage
C
Float
Voltage
D
Equalize
Voltage
E
Equalize
Time
(hours)
F
Equalize
Interval
(days)
Off-Off-Off
1 – Sealed
14.0
13.4
None
-
-
Off-Off-On
2 – Sealed
14.1
13.4
14.2
1
28
Off-On-Off
3 - Sealed
14.3
13.4
14.4
2
28
Off-On-On
4 - Flooded
14.4
13.4
15.1
3
28
On-Off-Off
5 - Flooded
14.6
13.4
15.3
3
28
On-Off-On
6 - Flooded
14.8
13.4
15.3
3
28
On-On-Off
7 - L-16
15.0
13.4
15.3
3
14
On-On-On
8-Ni-Cd
16.0
14.5
None
-
-
A.
Battery Type
– These are generic Lead-Acid – wet cell (Lead Antimony, Lead
Calcium), sealed AGM, sealed Gel Cell and Ni-Cd battery types.
B.
Voltage
–This is the PWM Absorption Stage with constant voltage charging. The
“PWM Absorption voltage” is the maximum battery voltage that will be held
constant. As the battery becomes more charged, the charging current tapers
off until the battery is fully charged.
C.
Float Voltage
–When the battery is fully charged, the charging voltage will be
reduced to 13.4 volts for all battery types. It will be 14.5V for Ni-Cd.
D.
Equalization Voltage
–During an equalization cycle, the charging voltage will
be held constant at this voltage.
E.
Equalization Time
–The charging at the selected equalization voltage will
continue for this number of hours.
F.
Equalization Interval
–Equalizations are typically done once a month. Most of the
cycles are 28 days so the equalization will begin on the same day of the month. It
can be set by DIP Switch 2~4 for different interval days. Each new cycle will be reset
as the equalization starts so that a setting day period will be maintained.