Samlexpower SEC-1223 Скачать руководство пользователя страница 18

18  |  SAMLEX AMERICA INC.    

 

SECTION 7  

|  Troubleshooting Guide

7.1  TROUBLESHOOTING GUIDE IS GIVEN AT TABLE 7.1 BELOW

NOTE:  This guide is based on operation as a power supply (only DC load is connected - 

no external battery or battery backup).

TABLE 7.1  TROUBLESHOOTING GUIDE

Symptom

Possible Cause

Remedy

ON / OFF Switch is ON

•  Switch is NOT lighted

•  No DC output

No AC power from the  

AC outlet

Internal AC side fuse  

is blown

Check AC power is available at the AC 

outlet. Breaker feeding the AC outlet may 

have tripped.

Open the top cover and check the AC side 

fuse. Replace if blown.

If the fuse blows again, the input section is 

damaged. Please call Tech Support.

ON / OFF Switch is ON

•  Switch is lighted

•  No DC output

Unit has shut down due to over 

temperature – Temperature of 

output transformer windings is: 

≥ 105°C ± 5°C / 221°F ± 9°F

(For SEC-1223 only)

Check that the fan is running. If not, the 

fan / fan control circuit may have been 

damaged. Call Tech Support.

Check that the fan suction vents on the 

sides of the unit and the discharge vents on 

the bottom of the unit are not blocked.

The unit will reset automatically when the 

transformer windings cool down to  

≤ 75°C ± 5°C / 167°F ± 9°F

ON / OFF Switch is ON

•  Switch is lighted

•  DC Output voltage 

drops

If the voltage loses regulation 

and drops to < 13.5V, the unit 

is overloaded and is in current 

limit. The load is trying to draw ≥ 

the current limit value

If the voltage drop is consider-

able with voltage < 2V, the load 

side is seeing a short circuit and 

short circuit current limited to 

the current limit value is being 

driven into the short circuit

Reduce the current drawn by the load to 

less than the continuous rating.

Switch OFF the load. Remove the short 

circuit on the load side.

GFCI outlet / GFCI break-

er supplying AC power 

to the unit trips when the 

unit is switched ON

Additional RF noise currents from 

the unit that are filtered to Earth 

Ground increase the net Leakage 

Current on the GFCI outlet / 

GFCI breaker to >  4 to 6mA

Switch OFF other SMPS devices operating 

from the same GFCI outlet / GFCI breaker 

to reduce the net leakage current to < 4mA

Move the unit to another GFCI outlet / 

GFCI breaker that has lesser number of  

SMPS load(s) or no SMPS load

Power the unit from normal, non GFCI 

outlet or from an outlet not protected by 

GFCI breaker

Содержание SEC-1223

Страница 1: ...Switch Mode DC Power Supplies SEC 1212 SEC 1223 Please read this manual BEFORE installing your Power Supply Owner s Manual...

Страница 2: ...FORMATION PROVIDED IN ITS MANUALS OR OTHER DOCUMENTATION 2 ASSUMES NO RESPONSIBILITY OR LIABILITY FOR LOSSES DAMAGES COSTS OR EXPENSES WHETHER SPECIAL DIRECT INDIRECT CONSEQUENTIAL OR INCIDENTAL WHICH...

Страница 3: ...INFO Indicates useful supplemental information 1 3 GENERAL Please read before using your power supply 1 It Is recommended that you return your power supply to a qualified Samlex dealer for any servic...

Страница 4: ...re alimentation doit tre mis la terre pour r duire le risque de choc lectrique L alimentation est quip d un conducteur de mise la terre et de mise la terre Le cordon doit tre branch dans une prise de...

Страница 5: ...4 for detachable power cord with IEC 60320 C13 connector on one end and NEMA5 15P plug on the other end 3 Black Negative DC Load Terminal 4 Red Positive DC Load Terminal 5 Ventilation slots Additional...

Страница 6: ...detachable power cord with IEC 60320 C13 connector on one end and NEMA5 15P plug on the other end 3 Black Negative DC Load Terminal 4 Red Positive DC Load Terminal 5 Air inlet slots for cooling fan co...

Страница 7: ...d less heat dissipation Protected against short circuit over current and over voltage through PWM controller SEC 1212 is convection cooled SEC 1223 has forced air cooling and over temperature shut dow...

Страница 8: ...et non pas les chargeurs de batterie Ne pas connecter ces appareils directement une batterie These units should NOT BE DIRECTLY CONNECTED TO A BATTERY for charging or for battery back up Battery charg...

Страница 9: ...EC 1223 4 3 LOCATION OF INSTALLATION Please ensure that the following requirements are met Working Environment Indoor use Cool Heat is the worst enemy of electronic equipment Hence please ensure that...

Страница 10: ...1223 has air intake openings on the sides and exhaust openings at the bottom for the cooling fan The units should be mounted in such a manner so that small objects should not be able to fall easily i...

Страница 11: ...3 female connector Insert this end into the AC Power Inlet on the unit 2 Figs 2 1 2 2 15A Plug for connecting to 120 VAC outlet NEMA5 15P 4 5 2 Connection for nominal AC input voltage of 230VAC range...

Страница 12: ...rminal of the jumper wire at point C by pulling it upwards Insulate this end with insulation tape and use a cable tie to tie it securely to the nearby wire bundle Changing internal Fuse a For the fact...

Страница 13: ...e of Terminal Lugs that have been provided with the unit see Fig 4 1 After crimping the Terminal Lugs use insulating heat shrink tubing or tape to insulate the bare cylindrical portion of the lugs Fig...

Страница 14: ...d that is required to be powered from the power supply d Ensure that the ends of the Positive and Negative wires of the DC load to be connected to the power supply have been properly terminated with P...

Страница 15: ...des interf rences nuisibles aux communications radio Cependant cela ne garantit pas qu aucune interf rence ne se produira dans une installation particuli re Si cet quipement provoque des interf rence...

Страница 16: ...ith the transmitter related noise pick up a loose coaxial connector or a broken or a missing ground may aggravate this problem Normally this noise will be below the background or band noise Increase t...

Страница 17: ...resistance is lower i e if the skin is wet or wounded This leakage current does not return to the power source but is dissipated in Earth Ground A leakage current of 4 to 6mA could produce lethal elec...

Страница 18: ...the unit are not blocked The unit will reset automatically when the transformer windings cool down to 75 C 5 C 167 F 9 F ON OFF Switch is ON Switch is lighted DC Output voltage drops If the voltage l...

Страница 19: ...Mode Power Supply SMPS with Fixed Frequency Pulse Width Modulation PWM Output Side Switching Frequency 20 KHz 25 KHz PROTECTIONS Short Circuit Overload Constant Current Limiting at 14A Auto Reset Cons...

Страница 20: ...ONNECTIONS AC Input Connection IEC 60320 C14 Inlet Connector on the unit Detachable Power Cord with IEC 60320 C13 Connector on one end NEMA5 15P Plug on the other end DC Output Connectors Terminal wit...

Страница 21: ...ving a reasonable number of opportunities to do so Warranty service shall be performed only by the Warrantor Any attempt to remedy the defect by anyone other than the Warrantor shall render this warra...

Страница 22: ...22 SAMLEX AMERICA INC Notes...

Страница 23: ...SAMLEX AMERICA INC 23 Notes...

Страница 24: ...Numbers Ph 1 800 561 5885 Fax 1 888 814 5210 Local Numbers Ph 604 525 3836 Fax 604 525 5221 Website www samlexamerica com USA Shipping Warehouses Kent WA Plymouth MI Canadian Shipping Warehouse Delta...

Отзывы: