24 | SAMLEX AMERICA INC.
SAMLEX AMERICA INC. | 25
operating
condition/
protection
threshold/
reason
Green
LeD (8,
inverter)
yeLLoW
LeD (6,
input
fault)
reD
LeD (9,
fault)
Buzzer
remedy/reset
No output due
to Over Load
Shut Down
Output power
is > Continu-
ous / Surge
Rating
ON
OFF
ON
OFF
Check starting surge rating
of load. If happens with
low power CFL or SMPS, try
adding small resistive load.
If happens when inverter
is switched ON with high
capacitance load already in
ON condition, try switching
ON the load 10 sec after
the inverter has been
switched ON.
Manual Reset. Unit will latch
in shut down condition. To
reset, switch OFF the ON/
OFF Switch, wait for 3
minutes and switch ON
again.
No output due
to Ground Fault
Shut Down
Neutral or
Line con-
nected to
Ground
ON
OFF
ON
OFF
Check if there is Neutral to
Ground bond or Ground
Fault.
Manual Reset. Unit will latch
in shut down condition. To
reset, switch OFF the ON/
OFF Switch, wait for 3
minutes and switch ON
again.
No output
No DC Input
Voltage due
to Blown DC
Input Fuse
OFF
OFF
OFF
OFF
Check fuse in the 12V
battery input line.
SECTION 6 |
Protections Monitoring
& Troubleshooting