Doc.-ID: 210222-PT10BA-ES-RoughCam IPQ1615_en_rev.00.docx, Page 18 of 28
Attention!
Introduce the foiling up to about 15 mm close to the terminals, in order
to prevent alien crosstalk. Make sure that the foiling cannot cause any
short circuit of the data pairs!
Attention!
Bring the twisted pair composite up to about 10 mm close to the ter-
minals, in order to ensure interference immunity.
Attention!
Use only terminals approved by SAMCON.
Attention!
Finally, check your network installation with a Class-D Link Test.
5.2.1
Fusing
PoE power supply requires no fuses. The power supply fusing depends on the cable
cross-section and length.
Attention!
Recommendation for fusing relates to 40W@24VDC at 100 meters and
1.5 mm
2
Attention!
When the heating switches on, high current peaks occur! Use slow-
blow fuses.
Attention!
Please pay attention to the national and international regulations re-
garding selectivity and line protection.
Potential/
Wire no.
Colour
(IEC60757)
Conductor
Voltage
Maximum
power
consump-
tion/fusing:
L+ / 1
BK
1.5mm
2
,
stranded wire
+24 V DC
40 W of continuous power
Fine-wire fuse
(L+) 4000 mA -T- slow-blow
(high inrush load!)
L- / 2
BU
1.5mm
2
,
stranded wire
0 V DC / GND
PE
YE/GN
1.5mm
2
,
stranded wire
PE
Table 5-6 Recommendation for fusing