background image

 

 

1.

 

General safety advice 

 

Please read the entire manual before you start using the cabinet. Incorrect use and failure to 
heed warnings and follow instructions may lead to serious injury. 

 

This cabinet is intended for storing and charging lithium-ion and other batteries. 

 

Only use original manufactur

ers’ batteries and heed all warnings, instructions, illustrations 

and information supplied with the battery. 

 

Never change the cabinet settings yourself, always contact the Nauta Service Team. 

 

Only allow qualified and skilled personnel to repair the electrical system and only allow 
those repairs to be undertaken with original parts. 

 

The service hatch must only be opened for safety and security inspections and only by the 
Nauta Service Team and qualified, skilled personnel. 

 

Always keep the cabinet doors closed so that any fire is limited to inside the cabinet. 

 

Never open the cabinet doors yourself if the alarm sounds. Telephone the emergency 
services and leave it to the fire brigade to open the cabinet. 

 

Never impede the smoke duct and the ventilation grill by placing anything on top of the 
cabinet. 

 

Place the cabinet in a well-ventilated room. In the event of a fire, poisonous gases may be 
discharged. 

 

Ensure that no unauthorised person who has not been instructed in the cabinet’s use gains 

access to it. 

 

A CEE-form plug is attached to the lithium-ion battery cabinet. Ensure that the voltage of the 
electricity source corresponds with that of the plug. 

 

Never exceed the maximum amperage indicated. 

 

Only use original, undamaged cables and plugs for charging batteries. 

 

Plug the charger directly into the charging point in the cabinet and never into a multiple 
socket and/or extension cable. 

 

Make sure that the fuse switch in the cabinet is up (position 1). The fuse switch is inside the 
cabinet on the outside of the lowest technical compartment. 

 

2.

 

Guarantee 

 

The manufacturer Nauta provides a warranty period of 24 months from the date of delivery 
on the cabinets specified in the manual. 

 

Salvus lithium-ion cabinets with a fire-suppression system must be inspected and serviced 
every five years. The due date of the next service is given on the maintenance sticker on the 
inside of the cabinet door. For more information, see chapter 11, Maintenance, service and 
faults. 

 

3.

 

Transport 

 

Move the cabinet in an upright position with a pallet truck. We recommend that you have 
the cabinet placed in its intended location by a specialist company. 

 

Improper transport may lead to hidden damage to cabinets and to their fire proofing and 
fire protection. 

Содержание L2

Страница 1: ...Salvus L2 L3 lithium ion cabinets manual Version 3 2022 ...

Страница 2: ...et after a fire 8 Safety information for BerkiCold Premix extinguisher agent 8 10 Signal explanation models with warning lights 9 Maintenance and service 10 Faults 10 Appendix 1 cabinet fittings 11 Models with automatic fire suppression system and 16 charging points 11 Models with automatic fire suppression system and 20 charging points 12 Appendix 2 wiring diagram s 16 Two level 12V wiring diagra...

Страница 3: ...his additional information for reference For optimal performance and long term functionality and to ensure the safety and security of the cabinet we recommend regular maintenance For more information see chapter 11 If you have any questions about your Salvus lithium ion cabinet or in the unlikely event of a malfunction please get in touch with the Nauta Service Team Yours faithfully The Nauta Serv...

Страница 4: ...poisonous gases may be discharged Ensure that no unauthorised person who has not been instructed in the cabinet s use gains access to it A CEE form plug is attached to the lithium ion battery cabinet Ensure that the voltage of the electricity source corresponds with that of the plug Never exceed the maximum amperage indicated Only use original undamaged cables and plugs for charging batteries Plug...

Страница 5: ...4 Model overview The model number is on the inside of the cabinet ...

Страница 6: ...ach shelf are charged every two hours Model 1301000175 ensure that the door closers are on and that the cabinet is connected to the electricity network Ensure that the maximum power of the cabinet is never exceeded 230V cabinet 3600W 400V cabinet 10 800W Ensure that the maximum load bearing capacity of the shelves of approx 75 kg is never exceeded Always keep the cabinet doors closed so that any f...

Страница 7: ...ors is entirely mechanical and requires very little force from the locking mechanism There is therefore very little risk involved and there is little danger of injury 6 Storing and charging batteries The Salvus lithium ion cabinet has an automatic charging system to provide 230V or 400V of electricity for the batteries in the cabinet The charging system means that batteries on each shelf are charg...

Страница 8: ...t and the cabinet can continue to be used For advice as to the disposal of the damaged batteries contact the manufacturer Safety information for BerkiCold Premix extinguisher agent only for models with an automatic fire suppression system The extinguisher agent BerkiCold Premix is used to suppress any battery fire Preventative measures for the safe use of BerkiCold Premix o Avoid inhalation and co...

Страница 9: ...operation check whether the cabinet is connected to the power supply Green light flashes Cabinet doors are open close doors Loud alarm door open Cabinet doors are open for more than 2 minutes Close the doors Loud alarm emergency Red light flashes Call the emergency services Do not open the cabinet Calamity resolved Call Nauta Service Team 31 342 455 055 ...

Страница 10: ...place for some reason or if it is no longer necessary get in touch with us as soon as possible on 31 0 342 455000 to cancel it We can then make a new appointment in consultation with you if necessary You will be charged the cost of the visit if you are not present at the agreed time or if the appointment is cancelled less than 24 hours in advance Netherlands Belgium Service staff member rate per h...

Страница 11: ...l compartment 2 Technical compartment 3 Shelf with extinguisher tubing 4 Extinguisher tubing 5 Recessed fuse switch 6 Charging point 7 CEE form plug 8 Alarm 9 Smoke alarm 10 Automatic charging system 11 Green warning lamp 12 Red warning lamp 13 Ventilation 14 Lamp 15 Fire suppression system 16 Pressure gauge ...

Страница 12: ...2 Technical compartment 3 Shelf with extinguisher tubing 4 Extinguisher tubing 5 Automatic charging system 6 Pressure gauge 7 Recessed fuse switch 8 Charging point 9 CEE form plug 10 Alarm 11 Smoke alarm 12 Green warning lamp 13 Red warning lamp 14 Ventilation 15 Lamp 16 Fire suppression system ...

Страница 13: ...16 Appendix 2 wiring diagram s Two level 12V wiring diagram See the model overview in chapter 4 ...

Страница 14: ...17 Four level 12V wiring diagram See the model overview in chapter 4 ...

Страница 15: ...17 Four level 24V wiring diagram See the model overview in chapter 4 ...

Страница 16: ...18 Four level 400V wiring diagram See the model overview in chapter 4 ...

Страница 17: ...19 Appendix 3 Declaration of compliance ...

Отзывы: