System Overview - Options

Option 1 - Page 09

Option 2 - Page 10

Option 3 - Page 10

The systems below although not exhaustive show the main options. The
maximum number of groups per KL10 wiring centre is two.  The group
selection communication cable must correspond to the group terminals
on the KL10 WC. Please refer to note 5 on the KL10 installation guide.

Group 1

Group 2

Group 1

Group 2

All Digital Variants can be
configured  from VS10. Groups
must have a group control
thermostat. 1 or 2 Groups can be
used per wiring centre. HW Timer
can be stand alone or part of a
group.  If using HW Timer as part
of a group it must be in group 1.

08

VS10W and VS10B Installer Manual

Option 2 - Unit is configured as a Group Control Thermostat used to control a group(s) of Dial Stat(s)

Option 3 - Unit is configured as a Group Control Thermostat used to control a group(s) of Digital Stat(s) configured as group thermostats.

Option 1 - Unit is configured as individual PRT.

iT600 VS10W - VS10B Installer - User Manual 022.qxd_Layout 1  07.07.2014  0

Содержание VS10W

Страница 1: ...4 in 1 Digital Thermostat Control Models VS10W and VS10B INSTALLER USER MANUAL iT600 VS10W VS10B Installer User Manual 022 qxd_Layout 1 07 07 2014 0...

Страница 2: ...duct Compliance System options overview Installation Parameter Settings Error Codes User Guide Installers notes Warranty Box Contents Icons used in this manual Safety Important info Your benefit For l...

Страница 3: ...onnected to the wiring centre and using the communication connections More information can be found on pages 9 and 10 Product Compliance This product is CE compliant and meets the following EC Directi...

Страница 4: ...in the installernotessection pages72 74 230V AC 04 VS10W andVS10B Installer Manual These instructions are applicable to the SALUS model statedonthefrontcoverofthismanualonly Warning This product must...

Страница 5: ...mmable Room Thermostat PRT The unit can be configured to either one of the following 1 UFH Manifold Wiring Centre Radiator Boiler HotWater Group Control Thermostat 2 Group Thermostat 3 Timer 4 SYSTEM...

Страница 6: ...ermostat Holidaywill also be applied to a timer if applicable Communication connections see page 13 are required for grouping thegroupthermostats Thermostatscan bealso globallychangedfromheatingtocool...

Страница 7: ...s Installing this Optional inexpensive CommunicationCableallowsthethermostatstocommunicate with each other This allows the thermostat to assume convenient remote control of groups of thermostats Bring...

Страница 8: ...iants can be configured from VS10 Groups must have a group control thermostat 1 or 2 Groups can be usedperwiringcentre HWTimer can be stand alone or part of a group IfusingHWTimeraspart of a group it...

Страница 9: ...6 6 Group Party 6 6 Group Heating Program 6 6 Group Permanent Override 6 6 GroupTemporary Override 6 6 Heat Cool changeover 6 4 Note Thecommunicationconnectionisonlyusedforheat coolchangeoverwhenusing...

Страница 10: ...Group Party 6 4 Group Heating Program 6 4 Group Permanent Override 6 4 GroupTemporary Override 6 4 Heat Cool changeover 6 4 Note HW timer will only use HOLIDAY function when the communication connecti...

Страница 11: ...ng the cylinder thermostat Unit configured to HotWaterTimer Cylinder thermostat options 1 Connected direct toWC Default 2 Connected direct toVS10 requires additional parameter change See page 40 VS10W...

Страница 12: ...ge see page 40 Forconveniencethereisauniquebuiltinoptionallowingthecylinder thermostat to be connected to either the HWTimer orWiring Centre Please refer to note 1 onWiring Centre guide and page 18 fo...

Страница 13: ...ermostat GroupThermostat and HWTimer PowerTerminals 230Vac Used for supplying power to the unit and switched output SensorTerminals Can be used for external AIR Floor sensor when configured as thermos...

Страница 14: ...Carefully remove the front housing Installation Thermostat Mounting 1 3 2 60mm 14 VS10W andVS10B Installer Manual iT600 VS10W VS10B Installer User Manual 022 qxd_Layout 1 07 07 2014 0...

Страница 15: ...e operation and efficient control the unit is best positioned in a draft free area and at 130cm from the floor Do not position the thermostat nearanyheatsource behindcurtains directsunlightoranareaofh...

Страница 16: ...emote control of groups of thermostats Bringing central control of features such asTime control Holiday Partyfunctionsaswellasfrostcontrol The individual group members can leave or re enter group cont...

Страница 17: ...the unit has to be configured for External Air Sensor or Floor Protection Sensor please see device parameter setting page 40 VS10W andVS10B Installer Manual 17 INSTALLATION SALUS External sensor Sold...

Страница 18: ...s 230Vac Optional Communication Connections 12VDC If hot water is part of a group then the communication connection must be connected to group 1 18 VS10W andVS10B Installer Manual iT600 VS10W VS10B In...

Страница 19: ...arameters page 40 For additional Wiring Centre information refer to note 1 onWiring Centre guide HWTimerconnectedcylinderthermostat IN OUT Link must be fitted WC connected cylinder thermostat Default...

Страница 20: ...d Ensuretheorientationarrow is pointing upwards PowerTerminals SensorTerminals if applicable Communicationconnections optionalbutrecommended You are ready to secure the rear housing to the wall box 20...

Страница 21: ...e rear housing Align the front housing at the bottom edge 2 Lightly press until you hear a positive click Ensure the pin connections are aligned VS10W andVS10B Installer Manual 21 INSTALLATION iT600 V...

Страница 22: ...re Programmable thermostat Program mode indicator Indicatesprogramisrunning AutoOnorAutoOff Forgroupthermostatthis indicatesthatitisamemberofagroup Party indicator WhenPartymodeisactive Vacation indic...

Страница 23: ...show the other information Temporary manual override indicator If the set temperature is changed when in program mode the hand will appear until the next program start time Programs number indicator I...

Страница 24: ...am mode indicator Indicates program is running HW Mode indicator Mode for 1 period of HW a day from Program 1 ON to Program 3 OFF HW Mode indicator Indicates continuously On HW Mode indicator Indicate...

Страница 25: ...w battery indicator Batteries need to be replaced Setting indicator Indicate the unit is in setting mode when program setting Indicate the manual mode Keylock indicator Shows that keys are inactive VS...

Страница 26: ...returntohomedisplaywithoutsaving 3 Shortpresstoreturntothepreviousscreenwhenitisinuser installersettingmode 1 OKkey Shortpresstoconfirmselection 2 Longpresstosaveandexit 3 Longpresstoentertheusersetti...

Страница 27: ...Installation First Power Up VS10W andVS10B Installer Manual 27 INSTALLATION iT600 VS10W VS10B Installer User Manual 022 qxd_Layout 1 07 07 2014 0...

Страница 28: ...ebelow S03 setting 1 is used for Control Group options 2 3 see pages 33 36 communication connectionmustbeused globalheat coolchangeoverisalsoincludedifapplicabletoyoursystem S03setting0isusedforoption...

Страница 29: ...GroupControlThermostatusedtocontrolagroup s ofDigitalStat s configuredasgroupthermostats Option 3 Page 35 Group 1 Group 2 Group 1 Group 2 An additional HotWaterTimer can be used with any of the above...

Страница 30: ...dVS10B Installer Manual Press once Press x amount of times Hold for five seconds Flashing xx Short press to save and long press to save and exit Short press to back up iT600 VS10W VS10B Installer User...

Страница 31: ...ttings Refer to page 33 Short press on to back up Use to change to 2 PRT with no communication Select S03 setting 0 if communication is required for global heat cool changeover Your system must suppor...

Страница 32: ...s to exit to home screen or continue to change device settings Refer to page 40 Hot water with no communication 32 VS10W andVS10B Installer Manual Use to change to 2 Use to change to 2 iT600 VS10W VS1...

Страница 33: ...S10W andVS10B Installer Manual 33 Long press to exit to home screen or continue to change device settings Refer to page 40 Communication connection required for this setting SYSTEM OPTION 2 iT600 VS10...

Страница 34: ...andVS10B Installer Manual Long press to exit to home screen or continue to change device settings Refer to page 40 Communication connection required for this setting Use to change to 2 iT600 VS10W VS1...

Страница 35: ...anual 35 SYSTEM OPTION 3 Group Control Thermostat Long press to exit to home screen or continue to change device settings Refer to page 40 Communication connection required for this setting iT600 VS10...

Страница 36: ...ller Manual Group Thermostat Long press to exit to home screen or continue to change device settings Refer to page 40 Communication connection required for this setting Use to change to 1 iT600 VS10W...

Страница 37: ...staller Manual 37 SYSTEM OPTION 3 Long press to exit to home screen or continue to change device settings Refer to page 40 Communication connection required for this setting Use to change to 2 iT600 V...

Страница 38: ...Parameters If you have made an error or need to change your system parameters please follow steps below This should only be done by your installer Press all three buttons simultaneously iT600 VS10W VS...

Страница 39: ...will follow power up sequence on page 27 You are now ready to enter or change your system parameters Refer to page 28 VS10W andVS10B Installer Manual 39 INSTALLATION iT600 VS10W VS10B Installer User M...

Страница 40: ...ers follow the steps below Please note your system parameters will be shown first but cannot be edited in this section To change the system parameters please refer to the previous two pages 40 VS10W a...

Страница 41: ...at Connected 0 connection D04 Sensor probe 0 D03 must be set to 1 then used as air sensor external sensor be used as or floor sensor Air sensor There will be no internal temp measurement 0 1 D03 must...

Страница 42: ...ng Set point 5 40 Deg C Maximum temp that can 5 Deg C Limit be set for Cooling D14 Floor sensor High Output relay will be switched off LimitTemperature 6 45 Deg C when temp is reached for 27 Deg C flo...

Страница 43: ...nsoropen 04 Floorsensorshort Floorsensorshort Ifthereismorethan1error thenonErrorpage pressUPtoshowothererrorcodes e g Err0305 3errorsErrorcode05 1stone PressUptoshowErr0308 3errorsErrorcode08 2ndone...

Страница 44: ...emporary Frost Protection 5 CAdjustable Power Source 230VAC50Hz Rating 3Amp Communication Bus 12VDC Temperature Scale 5to35 C tolerance0 5 C Heat Cool Globalchangeoverusingcommunicationbusandexternali...

Страница 45: ...User Guide Setting time and date VS10W andVS10B Installer Manual 45 USER GUIDE PRT and Group ControlThermostat iT600 VS10W VS10B Installer User Manual 022 qxd_Layout 1 07 07 2014 0...

Страница 46: ...to select 12 hour and right to select 24 hour Adjust the time using the up or down arrow key 46 VS10W andVS10B Installer Manual PRT and Group ControlThermostat Hour Minutes iT600 VS10W VS10B Installer...

Страница 47: ...d date Adjust the year month day using the up or down arrow key VS10W andVS10B Installer Manual 47 USER GUIDE PRT and Group ControlThermostat Month Year Day iT600 VS10W VS10B Installer User Manual 022...

Страница 48: ...the home Typically 19 Deg C LowerTemperature typically used for unoccupied or sleep times Typically 17 Deg C for UFH or 15 Deg C for radiators Frost Temperature typically used for Periods of long abs...

Страница 49: ...mperatureTypically 24 C VS10W andVS10B Installer Manual 49 Your thermostat comes preset for the above temperatures These can be adjusted please see page 53 Coolingisonlyavailableifyoursystemsupportsth...

Страница 50: ...9 00 17 00 23 00 Monday to Friday 21 19 17 12 00 8 00 9 00 17 00 23 00 Saturday to Sunday PRT and Group ControlThermostat If using grouping the schedule from the group control thermostat will be appl...

Страница 51: ...24 12 00 8 00 9 00 17 00 23 00 Saturday to Sunday VS10W andVS10B Installer Manual 51 USER GUIDE PRT and Group ControlThermostat If using grouping the schedule from the group control thermostat will be...

Страница 52: ...VS10B Installer Manual Press once Press x amount of times Hold for five seconds Flashing xx Short press to save and long press to save and exit Short press to back up iT600 VS10W VS10B Installer User...

Страница 53: ...e will use this as the low setting The temperature set are applicable to the individual thermostat PRT Group ControlThermostat and GroupThermostat Setting the low temperature VS10W andVS10B Installer...

Страница 54: ...hosen By setting the low temperature the programs will use this as the low setting 54 VS10W andVS10B Installer Manual The temperature set are applicable to the individual thermostat PRT Group ControlT...

Страница 55: ...elect the day of the programs VS10W andVS10B Installer Manual 55 5 2 7 Days Individual If using grouping the schedule from the group control thermostat will be applied to group members USER GUIDE iT60...

Страница 56: ...emperature Schedule Adjust the time using the up or down arrow key Use right and left to select the Hi Mid or low temp 56 VS10W andVS10B Installer Manual iT600 VS10W VS10B Installer User Manual 022 qx...

Страница 57: ...e temperatures see page 53 on how to change Repeat through to program 4 If you require a 5th or 6th program enter a time and select your temperature To remove a program out set the time to VS10W andVS...

Страница 58: ...the up or down arrow key to adjust the temperature to the setting you desire Temporary override allows you to increase the temperature or decrease it to the desired setting until it reverts back on t...

Страница 59: ...temporary override press or See below VS10W andVS10B Installer Manual 59 PRT Group ControlThermostat and GroupThermostat Confirm the temporary set temperature USER GUIDE iT600 VS10W VS10B Installer Us...

Страница 60: ...oved from the group See page 64 Move from to Use the up or down arrow key to view your set temperature See page 58 To adjust your permanent override temperature follow the steps on page 58 Repeat for...

Страница 61: ...se the up arrow to select the hr min Press tick to confirm and it will start to count down Party Mode set in a Control Group Thermostat will also affect group thermostats unless they are removed from...

Страница 62: ...to be off for Press tick to confirm and it will start the holiday count down 62 VS10W andVS10B Installer Manual Holiday set in a Control Group Thermostat will also affect group thermostats unless the...

Страница 63: ...een set to VS10W andVS10B Installer Manual 63 Frost protection set in a Control Group Thermostat will also affect group thermostats unless they are removed from the group See page 64 Frost protection...

Страница 64: ...the group thermostat will follow this mode or will be displayed The group thermostat has now left the group and is in permanent To adjust the set temperature please refer to page 58 The group thermos...

Страница 65: ...page 58 The group thermostat has now left the group and is in permanent To adjust the set temperature please refer to page 58 The group thermostat has been returned to it will follow the mode status o...

Страница 66: ...Holiday mode from the group control thermostat will be displayed When is selected the hot water timer will follow the program schedule See page 68 Hot water will be on once per day Hot water will be c...

Страница 67: ...User Guide HotWater Boost VS10W andVS10B Installer Manual 67 USER GUIDE iT600 VS10W VS10B Installer User Manual 022 qxd_Layout 1 07 07 2014 0...

Страница 68: ...F 12 00 6 00 8 00 18 00 22 00 Saturday and Sunday Monday to Friday ON ON OFF OFF OFF Your hot water timer comes preset with the times below These can be adjusted See next page 68 VS10W andVS10B Instal...

Страница 69: ...User Guide Setting HotWaterTimes VS10W andVS10B Installer Manual 69 USER GUIDE 5 2 7 Days Individual iT600 VS10W VS10B Installer User Manual 022 qxd_Layout 1 07 07 2014 0...

Страница 70: ...User Guide Setting HotWaterTimes 70 VS10W andVS10B Installer Manual Repeat these steps for programs iT600 VS10W VS10B Installer User Manual 022 qxd_Layout 1 07 07 2014 0...

Страница 71: ...User Guide Setting HotWaterTimes VS10W andVS10B Installer Manual 71 USER GUIDE Repeat these steps for programs iT600 VS10W VS10B Installer User Manual 022 qxd_Layout 1 07 07 2014 0...

Страница 72: ...Installer Notes 72 VS10W andVS10B Installer Manual iT600 VS10W VS10B Installer User Manual 022 qxd_Layout 1 07 07 2014 0...

Страница 73: ...Installer Notes VS10W andVS10B Installer Manual 73 iT600 VS10W VS10B Installer User Manual 022 qxd_Layout 1 07 07 2014 0...

Страница 74: ...Installer Notes 74 VS10W andVS10B Installer Manual iT600 VS10W VS10B Installer User Manual 022 qxd_Layout 1 07 07 2014 0...

Страница 75: ...he date of installation SALUS Controlssoleliabilityforbreachofthiswarrantywillbe atitsoption torepairorreplacethedefectiveproduct CustomerName CustomerAddress PostCode TelNo Email EngineersCompany Tel...

Страница 76: ...ech com Issue Date April 2014 For PDF Installation guide please go to www salus controls com Maintaining a policy of continuous product development SALUS Controls plc reserve the right to change speci...

Отзывы: