Salus TRV10RFM Скачать руководство пользователя страница 2

0 TRVs on this thermostat

Note:

 The following example shows the pairing process with the VS10/20..RF thermostat. 

For HTRS-RF(30) and HTRP-RF(50) thermostats, the pairing process shall be done in the 

same way.

Note: 

To exit the manual mode and go back to auto mode - press once the pairing 

button (antenna). The red LED diode will flash once, indicating return to auto mode.

Choose the type of coordinator for ZigBee network

Choose one type of ZigBee network coordinator and prepare it for work with 

iT600 series devices:

LED diode on TRV head flashes in 

orange

. Now TRV head need to be 

paired with thermostat.

NOTE:

 TRV head and thermostat 

must be in the same heating zone!

• Online - system is connected to the Internet via an Internet 

gateway 

UGE600

   or

• Offline - with an option of connecting system to the Internet 

using a gateway 

UGE600

   or

• Offline - by using 

CO10RF

 coordinator  - no possible to connect 

system to the Internet

Thermostat pairing with the TRV head in Online mode

Thermostat pairing with the TRV head in Offline mode

Manual mode

LED diode indications

1

1

5

6

7

8

9

10

WARNING!

 Do not use the CO10RF coordinator together with UGE600.

Thermostat will go to the main screen.

Device is paired with 

the coordinator, diode 

on TRV head will start 

blinking in 

orange

.

Diode on the TRV head 

lights up once 

green

then stops flashing.

TRV head has been 

added.

 5 sec.

 5 sec.

 5 sec.

OR

OR

Press and hold          the pairing         

button for 10 seconds, the diode on the 

TRV head should start flashing in 

red

Press and hold the pairing            button 

for 10 seconds, the diode on the TRV 

head should start flashing in 

red.

10 sec.

10 sec.

Choose the device type - TRV head

Install the TRV head

on the valve according to the 

instructions on the previous page.

Install the TRV head

on the valve according to the 

instructions on the previous page.

2

3

4

Open the ZigBee network

Close the ZigBee network

 5 sec.

WARNING! 

You can connect up to 6 TRV heads to one regulator.

WARNING! 

You can connect up to 6 TRV heads to one regulator.

When...

TRV Status

LED diode...

Valve

...power supplied 

TRV head indicates 

the software version

...alternately flashes red / green

indicating the software version.

A more detailed description is in „TRV head 

setup” section on the previous page. 

...TRV head adapts 

to the valve

... flashes in green, then red and it switches 

off when the adaptation process has been 

done. When the LED will continue to flash red 

it means that adaptation process failed.

...TRV head has 

been added to the 

network.

... flashes in orange (has been added to the 

network). TRV head should be paired now 

with thermostat.

closed

..TRV head is 

added to the 

network, but it is 

not paired with 

thermostat

Auto mode

...flashes in orange

closed

TRV head is open in 

manual mode

...flashes twice in green when pressed the 

opening or closing button.

100% 

open

TRV head is closed in 

manual mode

...flashes once in green after a short press of 

the opening or closing button.

closed

 ...TRV head is in 

normal operating 

mode

Auto mode

...flashes once in green after a short press of 

the opening or closing button.

open in 

range from 

1%

up to 100%

Auto mode

...flashes once in red after short press of the 

opening or closing button.

closed

TRV head is open in 

manual mode

....flashes twice in green after short press of 

the opening or closing button.

100%

open

TRV head is closed in 

manual mode

...flashes twice in red after short press of the 

opening or closing button.

closed

The Window Open 

function is active

...flashes in green and red 2 times every 

10 seconds.

100%

open

...TRV head is 

paired with 

thermostat.

Auto mode

...does not light up.

...TRV head is 

removed from the 

network.

...flashes once in orange (TRV head is 

removed from the coordinator’s memory) 

and then flashes in red.

...identification 

of the TRV

head is turned on

...flashes in green for a maximum of 10 

minutes.

... wireless 

communication 

with the TRV head 

is lost

Auto mode

...flashing alternately in green and red after a 

short press of the opening or closing button.

TRV head is open in 

manual mode

...flashes twice in green after a short press of 

the opening or closing button.

100%

open

TRV head is closed in 

manual mode

...flashes twice in red after a short press of 

the opening or closing button..

closed

...when battery 

power is too low

...flashes three times in red every 10 seconds 

(or less often if the batteries in the TRV head 

are very weak).

25%

open

...an error occurred 

during TRV head 

assembly

... flashes alternately in red and green.

Additional functions:

Frost protection mode

When valve is manually closed, the TRV head automatically activates frost 

protection mode. Setpoint temperature of the frost protection mode is set on 

the thermostat. This function is activated when the room temperature drops 

below the frost protection setpoint teperature set on the thermostat. TRV 

head automatically maintains setpoint temperature if there is communication 

between TRV head and thermostat.

Open window function

TRV head checks the speed of temperature drop in the room. If the temperature 

drop is fast, it is assumed that in the room has been opened window. The 

function is active when the TRV head communicates with thermostat, is in 

automatic mode and the batteries are not discharged. 

Protection against scale deposits

Do not leave the valve open for a long time because it can cause scale deposits 

on it. TRV head has a protection function against scale deposits. It starts to 

opening automatically once every 14 days if no valve movement is detected. 

Protection will also work no matter if TRV head is in auto mode or manual mode

Technical Information

Warranty

SALUS Controls warrants that this product will be free from any defect 

in materials or workmanship, and shall perform in accordance with its 

specification, for a period of two years from the date of installation. SALUS 

Controls sole liability for breach of this warranty will be (at its option) to repair or 

replace the defective product.

To open or close the TRV head in manual mode, follow the procedure described 

below. If the steps described below do not bring any results it means that 

probably the TRV head buttons are locked and they should be unlocked first.

To open the valve manually, press and 

hold the opening button. The 

green 

LED diode flashes once and the TRV 

head will start to open the valve.

To close the valve manually, press and 

hold the closing button. The 

red 

LED 

diode flashes once and the TRV head 

will start closing the valve.

Model

TRV10RFM / TRV28RFM / TRV10RAM

Type

Wireless, thermostatic TRV head

 M30 x 1.5 / M28 x 1.5

LED signaling

Tri-color LED (red/green/orange)

Adaptation with a valve

Automatic

Power supply

2 x AA batteries

Control method

Modulation

Communication

Wireless, ZigBee 2.4 GHz

Operating temperature

0 to 45°C

Storage temperature

-20 to 60°C

Ambient humidity

5 to 95% RH

IP protection level

IP30

Dimensions [mm]

H=88.6, 

Ø

=51

5 sec.

5 sec.

Customer Name: ..................................................................................
Customer Address: ..............................................................................
..........................................................................................................................
 ............................................................................... Post Code:.........................
Tel No: ............................................................................................................. 
Email: ..............................................................................................................

Engineers Company: ........................................................................................
Tel No: .............................................................................................................
Email: ..............................................................................................................
Instalation Date: ..............................................................................................
Engineers Name: ................................................................................. 
Engineers Signature: ........................................................................................

3

4

5

6

7

Scan for equipment

SALUS 

Smart Home

8

10

11

12

9

Name this equipment

TRV in the living room

Connect equipment

Finish

3

14

13

Save

Select TRV(s) for living room

Name this equipment

15

1 TRVs on this thermostat

3

2

Отзывы: