PRESSIONE MINIMA
0.5 bar
PRESS. SETPOINT 4
3.0 bar
PRESS. SETPOINT 3
3.0 bar
5.2 Applicazione 4-20mA bar
5. PROGRAMMAZIONE
TRASDUTTORE
10 bar
TRASDUTTORE
10 bar
TRASDUTTORE
16 bar
SERVE AD IMPOSTARE
IL FONDO SCALA
DEL TRASDUTTORE
UTILIZZATO
TRASDUTTORE
25 bar
PRESSIONE START
2.5 bar
PRESS. COSTANTE
3.0 bar
PRESSIONE START
2.5 bar
PRESS. COSTANTE
3.0 bar
SERVE AD IMPOSTARE LA
PRESSIONE NECESSARIA
PER AVVIARE IL MOTORE
SERVE AD IMPOSTARE LA
PRESSIONE DI LAVORO
TRASDUTTORE 25bar: 0.3 ÷ 22.7bar
TRASDUTTORE 16bar: 0.3 ÷ 13.7bar
TRASDUTTORE 10bar: 0.3 ÷ 7.7bar
TRASDUTTORE 25bar: 0.6 ÷ 23.0bar
TRASDUTTORE 16bar: 0.6 ÷ 14.0bar
TRASDUTTORE 10bar: 0.6 ÷ 8.0bar
TRASDUTTORE 25bar: 0.6 ÷ 23.0bar
TRASDUTTORE 16bar: 0.6 ÷ 14.0bar
TRASDUTTORE 10bar: 0.6 ÷ 8.0bar
ABILITA SETPOINT
OFF
ABILITA SETPOINT
OFF
PRESS. SETPOINT 1
3.0 bar
PRESS. SETPOINT 1
3.0 bar
ABILITA SETPOINT
ON
DELTA PRESSIONE
0.5 bar
DELTA PRESSIONE
0.5 bar
OFF
DISABILITA
I SETPOINT
ON
ABILITA
I SETPOINT
SERVE AD IMPOSTARE
LA PRESSIONE CHE SOTTRATTA
A QUELLA DEL SETPOINT
AVVIA IL MOTORE
SERVE AD IMPOSTARE
LA PRESSIONE DI LAVORO
RELATIVA ALL’INGRESSO
ABILITATO
TRASDUTTORE 25bar: 0.1 ÷ 22.7bar
TRASDUTTORE 16bar: 0.1 ÷ 13.7bar
TRASDUTTORE 10bar: 0.1 ÷ 7.7bar
PRESS. SETPOINT 2
3.0 bar
PRESSIONE MINIMA
OFF
PRESSIONE MINIMA
OFF
SERVE AD IMPOSTARE LA
PRESSIONE SOTTO LA QUALE
IL MOTORE VA IN BLOCCO.
AL PRIMO AVVIAMENTO
DEL MOTORE IN AUTOMATICO,
QUESTO PARAMETRO VIENE
ESCLUSO PER 10s.
OFF
ESCLUDE LA
PRESSIONE MINIMA
0 ÷ 7.5bar
RANGE:
5.1