Installation and operating instructions Salmson-IF-Modules Siriux
29
English
6.2 Function
Ext. Off:
Input for potential-free NC contact.
• Contact closed: pump operates under auto control.
• Contact open: pump off.
Ext. Min:
Input for potential-free NC contact.
• Contact closed: pump operates under auto control.
• Contact open: pump operates at a fixed minimum speed.
Function/ Siriux IF-Module
Ext. Off
Ext. Min
SBM
Ext. Off/
SBM
DP-
B
U
S
Collective run signal output (SBM) as
a potential-free NO contact
-
-
-
Input for potential-free NC contact with the
function Ext. Min
-
-
-
-
Input for potential-free NC contact with the
function Ext. Off
-
-
-
Control input 0-10 V
Remote setpoint adjustment
Remote speed adjustment
-
-
DP interface for dual pump management