background image

Installation and operating instructions Salmson SCX-DCX / SXM-DXM / SXS / NSB-S

39

English

7.1.3 Insulation of the pump in refrigeration/air-conditioning systems

• The series SCX-DCX / SXM-DXM are suitable for use in refrigeration and air-

conditioning systems with temperatures of the fluid down to -20 °C. 

• For applications in refrigeration and air-conditioning systems, Salmson-Clima-

Form diffusion-proof thermal insulation shells or other commercially-available 
diffusion-proof thermal insulation materials must be used.

CAUTION! Risk of damage!
If the diffusion-proof insulation is applied by the customer, the pump hous-
ing may be insulated only up to the motor separation joint, so that the con-
densate drain openings remain open and allow the condensate accumulating 
in the motor to flow out without obstruction (Fig. 8). Otherwise condensate 
can accumulate in the motor, eventually causing an electrical defect.

7.2

Electrical connection

DANGER! Danger of death!
Improper electrical connections pose a risk of fatal injury due to electric 
shock.

• Only allow the electrical connection to be made by an electrician approved 

by the local electricity supplier and in accordance with the local regulations 
in force.

• Before working on the pump, all poles of the power supply must be discon-

nected. Because voltages hazardous to persons persist for some time 
(in capacitors), no work may be commenced on the module until 5 minutes 
have elapsed (applies only to 1~ systems). Check to ensure all connections 
(including potential-free contacts) are voltage-free.

CAUTION! Risk of damage!
If the wrong voltage is applied, the motor can be damaged!

• The current type and voltage of the mains connection must correspond to the 

specifications on the name plate.

• The electrical connection must be established via a fixed connection line 

equipped with a connector device or an all-pole switch with a contact opening 
width of at least 3 mm. 

• Mains-side fuse protection: 10 A, slow.

• Twin-head pumps: provide a separate mains connection cable and a separate 

fuse on the mains side for both motors of the twin-head pump.

• The pumps can also be used without restriction in existing installations with and 

without FI-protection switches. When dimensioning the FI-protection switch, 
consider the number of pumps connected and their motor currents.

• When pumps are used in systems with water temperatures above 90°C, a suit-

able heat-resistant supply cable must be used.

• The supply cable is to be placed in such a way that under no circumstances can 

it come into contact with the pipe and/or the pump and motor housing.

Содержание SCX Series

Страница 1: ...ISE EN SERVICE INSTALLATION AND STARTING INSTRUCTIONS FRAN AIS ENGLISH INSTALLAZIONE E MESSA IN SERVIZIO ITALIANO INSTALACION Y PUESTA EN SERVICIO ESPA OL N M S STOCK N 2 115 936 Ed 02 02 12 SCX DCX S...

Страница 2: ...2...

Страница 3: ...3...

Страница 4: ...Fig 1 Fig 2 Fig 3 Fig 4 Fig 4a Fig 4b 1 2 3 1 230 V 3 400 V...

Страница 5: ...Fig 4c Fig 4d Fig 5 Fig 6 Fig 7 Fig 8 L1 L2 L3 1015 230V 400V 3 230V 3 400V A1 L1 L2 L3 N A2 A1 L N A2 L N C1 C2C31015 1 230V 1 230V 1 2 3 H m Q m3 h...

Страница 6: ...fait partie int grante de la pr sente notice de montage et de mise en service Si les gammes mentionn es dans la pr sente notice sont modifi s sans notre approbation cette d claration perdra sa validit...

Страница 7: ...r le domaine de responsabilit la comp tence et la surveillance du personnel Si le personnel ne dispose pas des connaissances requises il doit alors tre form et instruit en cons quence Cette formation...

Страница 8: ...de mon tage soient effectu s par du personnel agr et qualifi suffisamment inform suite l tude minutieuse de la notice de montage et de mise en service Les travaux r alis s sur le produit ou l install...

Страница 9: ...re le gel et les dommages m caniques Des emballages ramollis perdent leur stabilit et peuvent conduire des dommages corporels de par la chute du produit La pompe peut tre uniquement port e au niveau d...

Страница 10: ...on le type de pompe voir catalogue Hauteur manom trique max Selon le type de pompe voir catalogue Vitesse de rotation Selon le type de pompe voir catalogue Tension d alimentation 1 230 V selon DIN CEI...

Страница 11: ...isation d autres fluides l accord pr alable du fabricant de la pompe est n cessaire Des ex cutions sp ciales avec des mat riaux r sistants aux fluides p ex ex cutionpourl huile sontpossiblessurdemande...

Страница 12: ...s M12 pour les raccordements de brides M12 avec ex cution combin e de brides DN 32 DN 65 8 rondelles M16 pour les raccordements de brides M16 avec ex cution combin e de brides DN 32 DN 65 Notice de mo...

Страница 13: ...pitre 6 2 DCX DXM Dans le cas d une pompe double les deux blocs moteurs sont construits de fa on identique et log s dans un corps de pompe commun SXS NSB S Les pompes de cette gamme sont gr ce la s le...

Страница 14: ...t tre ex cut s uniquement par des techniciens qualifi s et conform ment aux prescriptions en vigueur Observer les consignes de pr vention des accidents Observer les consignes des fournisseurs d nergie...

Страница 15: ...ature ambiante admissible n est pas atteinte ou si elle est d pas s e pr voir un chauffage une ventilation suffisant e Proc der tous les travaux de soudage et de brasage avant l installation de la pom...

Страница 16: ...essure de dommages mat riels d au fluide chaud sortant Ne jamais raccorder deux brides combin es l une avec l autre L utilisation d l ments de s curit p ex rondelle Grower peut conduire des fuites dan...

Страница 17: ...x de 20 C Pourl utilisationdansdesinstallationsder frig rationetdansdescircuitsdeclima tisation utiliser la coquille d isolation froid tanche la diffusion Salmson Clima Form ou d autres mat riaux isol...

Страница 18: ...ard e Pompes doubles Equiper les deux moteurs de la pompe double d une ligne de raccordement au r seau s par e pouvant tre mise hors tension et d une pro tection par fusible s par e c t r seau Les pom...

Страница 19: ...d une surcharge thermique Les bornes 10 et 15 contact sec ouverture 250 V 1 A max peuvent tre connect es un organe de coupure externe Le r glage de la protection thermique ventuellement disponible doi...

Страница 20: ...e car du fluide sortant peut causer des dommages 8 1 Remplissage et purge Remplir et purger l installation de mani re correcte Une purge de la chambre du rotor de la pompe s effectue automatiquement a...

Страница 21: ...tation est incorrect Enclencher bri vement la pompe pour contr ler le sens de rotation Si le sens de rotation est incorrect proc der de la mani re suivante Mettre la pompe hors tension Inverser 2 phas...

Страница 22: ...ionn es desdeux pompes doivent tre identiques 8 3 Mise hors service La pompe doit tre mise hors service pour les travaux d entretien de r paration ou le d montage DANGER Danger de mort Lors de travaux...

Страница 23: ...tage de la t te du moteur Ne pas maintenir la t te du moteur avec la roue orient e vers le bas Si seule la bo te bornes doit tre plac e dans une autre position il n est alors pas n cessaire de compl t...

Страница 24: ...De l air se trouve dans la pompe Purger la pompe l installation Les vannes d arr t de l ins tallation ne sont pas com pl tement ouvertes Ouvrir compl tement les vannes d arr t La puissance de la pomp...

Страница 25: ...her le disjoncteur diff rentiel En cas de nouveau d clenchement du disjoncteur diff rentiel V rifier que la pompe ne pr sente aucun d faut lectrique Contr lerlec ble lectriquedela pompe et le raccorde...

Страница 26: ...la pompe et contr ler la bonne marche du rotor de la pompe en tournant l extr mit fendue de l arbre l aide d un tournevis ou le d bloquer Alternative D montage de la t te du moteur et contr le proc de...

Страница 27: ...ignal tique lors de chaque commande 12 Elimination L limination conforme de ce produit permet d viter les dommages caus s l environnement et les risques pour la sant 1 Pour liminer le produit ainsi qu...

Страница 28: ...ration of conformity is a component of these operating instructions If a technical modification is made on the designs named there without our agreement this declaration loses its validity 2 Safety Th...

Страница 29: ...erator If the personnel are not in possession of the necessary knowledge they are to be trained and instructed This can be accomplished if necessary by the manufacturer of the product at the request o...

Страница 30: ...horised and qualified personnel who are sufficiently informed from their own detailed study of the operating instructions Work on the product unit must only be carried out when at a standstill It is m...

Страница 31: ...t and interim storage Packaging that has become weakened loses its strength and call allow the product to fall out causing injury to personnel When the pump must be transported it may be carried only...

Страница 32: ...le phase motor stainless steel pumphousing 30 Nominal flow 3 m3 h 25 Threaded connection 20 Rp 25 Rp 1 5 2 Technical data Max flow rate Depends on the pump type see catalogue Max delivery head Depends...

Страница 33: ...approval must be obtained for use of other fluids Special versions with fluids resistant materials e g ver sions for use with oil available on request SXS NSB S Drinking water and water for foodstuff...

Страница 34: ...nge bolts for DN 32 DN 65 combination flanged version Eight M16 washers for M16 flange bolts for DN 32 DN 65 combination flanged version Installation and operating instructions 5 4 Accessories Accesso...

Страница 35: ...apter 6 2 DCX DXM For a twin head pump the two motor impeller units are fitted identically and accommodated in a common pump housing SXS NSB S The selected materials and designs of the pumps of this s...

Страница 36: ...applicable regulations Accident prevention regulations must be observed Comply with the regulations of the local power supply company Pumps with pre assembled cable Never pull on the pump cable Do no...

Страница 37: ...ut off valves upstream and downstream of the pump Attach pipework to the floor ceiling or wall using appropriate fittings so that the pump does not bear the weight of the pipework Install the pump at...

Страница 38: ...can occur at the edges of the long holes This causes the screws to lose their preload and the flange connection can become leaky Use screws of sufficient length The screw thread must protrude at least...

Страница 39: ...ulations in force Before working on the pump all poles of the power supply must be discon nected Because voltages hazardous to persons persist for some time in capacitors no work may be commenced on t...

Страница 40: ...g 4c and 4d a collective fault signal SSM for connection to the building automation system is available as a poten tial free NC relay max contact loading 250 VAC 1A 7 2 2 Motor protection CAUTION Risk...

Страница 41: ...e direction of rota tion indicator light at the pump may go out 8 Commissioning WARNING Risk of injury and material damage Commissioning the pump without the sealing screw including the gasket in not...

Страница 42: ...ation is incorrect the light remains dark To check the direction of rotation briefly switch the pump on If the direction of rotation is incorrect proceed as follows Electrically isolate the pump Inter...

Страница 43: ...the individual pumps arein operation at the same time the selected speeds must be identical for both pumps 8 3 Decommissioning The pump must be decommissioned before performance of maintenance or rep...

Страница 44: ...nit can fall out and injure personnel Do not hold the motor head with the impeller facing downward The motor does not have to be completely removed from the pump housing if only the terminal box is to...

Страница 45: ...e motor impeller unit remove the foreign body Air within the pump Bleed the pump system The check valves in the system are not fully open Fully open the check valves The pump power is too low Foreign...

Страница 46: ...ction switch If the FI protection switch trips again Check the pump for electrical defects Check the mains cable to the pump and check the electrical connections Undervoltage Check the voltage at the...

Страница 47: ...e performance curve b If necessary remove the vent screw visible from outside from the pump and check the free running of the pumprotorbyturning the slotted shaft end using a screwdriver unblock if ne...

Страница 48: ...ed for each order 12 Disposal Disposing of this product properly prevents damage to the environment and risks to personnel health 1 Draw on public or private waste management companies for the disposa...

Страница 49: ...za presenti al momento della stampa Dichiarazione CE di conformit Una copia della dichiarazione CE di conformit parte integrante delle presenti istruzioni di montaggio uso e manutenzione In caso di mo...

Страница 50: ...ze necessarie il personale dovr essere addestrato e istruito di conseguenza Ci pu rientrare se necessario nelle competenze del costruttore del prodotto dietro incarico dell utente 2 3 Pericoli consegu...

Страница 51: ...ano eseguite da personale autorizzato e qualificato che abbia letto attentamente le presenti istruzioni Tutti i lavori che interessano il prodotto o l impianto devono essere eseguiti esclusivamente in...

Страница 52: ...o rigidit e possono provocare lesioni alle persone in caso di caduta del prodotto La pompa pu essere sostenuta durante il trasporto solo avvalendosi del motore corpo pompa Non sorreggerla mai per il m...

Страница 53: ...acciaio inossidabile 30 Portata nominale 3 m3 h 25 Attacco filettato 20 Rp 25 Rp 1 5 2 Dati tecnici Portata max In funzione del tipo di pompa vedi catalogo Prevalenza max In funzione del tipo di pompa...

Страница 54: ...richiesta sono possibili versioni speciali con materiali resistenti ai fluidi ad es versione per olio SXS NSB S Acqua potabile e acqua per uso alimentare secondo la diret tiva europea sull acqua potab...

Страница 55: ...attacco flangiato 8 pz rondelle M12 per viti flangiate M12 con versione a flangia combinata DN 32 DN 65 8 pz rondelle M16 per viti flangiate M16 con versione a flangia combinata DN 32 DN 65 Istruzion...

Страница 56: ...i set di innesto sono costruiti in modo identico e alloggiati in un corpo pompa comune SXS NSB S Le pompe di questa serie soddisfano per scelta dei materiali e costruzione le direttive di rilevo Trin...

Страница 57: ...ca Affidare l installazione e i collegamenti elettrici solo a personale specializ zato e in conformit alle normative in vigore Osservare le norme per la prevenzione degli infortuni Osservare le norme...

Страница 58: ...seguire tutti i lavori di salda tura e brasatura ATTENZIONE Pericolo di danni materiali Impurit nella tubatura possono distruggere la pompa in funzionamento Prima di installare la pompa procedere al l...

Страница 59: ...gia Per tale ragione non sono consentiti Utiliz zare pertanto tra la testa della vite del dado e la flangia combinata le ron delle fornite a corredo Fig 3 pos 1 Anche in caso di impiego di viti di res...

Страница 60: ...l condensato accumulatosi nel motore Fig 8 Un aumento del condensato nel motore pu altrimenti provocare un guasto elettrico 7 2 Collegamenti elettrici PERICOLO Pericolo di morte In caso di collegament...

Страница 61: ...ressacavo PG 13 5 provvedere ad un cavo di allacciamento di diametro esterno pari a 10 12 mm e montarlo come riportato in Fig 4 Pie gare inoltre il cavo in prossimit del pressacavo in modo da formare...

Страница 62: ...cizio con convertitore di frequenza I motori trifase della serie SCX DCX SXS possono essere collegati ad un convertitore di frequenza Durante il funzionamento con convertitori di fre quenza devono ess...

Страница 63: ...ttature La fuoriuscita di fluido pu provocare lesioni e danni materiali All apertura della vite di spurgo il fluido bollente pu fuoriuscire allo stato liquido o sotto forma di vapore o erompere a pres...

Страница 64: ...folgorazione da contatto con morsetti sotto tensione Privare l impianto dell alimentazione elettrica e bloccarlo per evitare che venga riacceso da persone non autorizzate Durante il funzionamento non...

Страница 65: ...izio durante gli interventi di manuten zione riparazione o in caso di smontaggio PERICOLO Pericolo di morte L esecuzione di lavori su apparecchi elettrici pu provocare lesioni fatali per folgorazione...

Страница 66: ...dere durante il montaggio smontaggio della testa del motore e provocare lesioni alle persone Non rivolgere la testa del motore con la girante in basso Se si intende portare la morsettiera in un altra...

Страница 67: ...estranei dopo aver smontato il set di innesto Presenza di aria nella pompa Sfiatare la pompa l impianto Le valvole d intercetta zione dell impianto non sono completamente aperte Aprire completamente l...

Страница 68: ...utomatico diffe renziale interviene nuovamente Verificare che la pompa non pre senti difetti elettrici Verificare il cavo di alimenta zione della pompa e i collega menti elettrici Sottotensione Contro...

Страница 69: ...l esterno della pompa e verificare la scorrevolezza del rotore della pompa ruotando l estremit scanalata dell albero con un cacciavite altrimenti sbloccarlo Alternativa smontaggio e con trollo della t...

Страница 70: ...cessario indicare tutti i dati della targhetta 12 Smaltimento Con lo smaltimento corretto di questo prodotto si evitano danni ambientali e rischi per la salute personale 1 Smaltire il prodotto o le su...

Страница 71: ...Declaraci n de conformidad CE es un componente esencial de las presentes instrucciones de funcionamiento Dicha declaraci n perder su validez en caso de modificaci n t cnica de los tipos citados en la...

Страница 72: ...ersonal Si el personal no cuenta con los conocimientos necesarios deber ser formado e instruido En caso necesario el operador puede encargar dicha ins trucci n al fabricante del producto 2 3 Riesgos e...

Страница 73: ...las tareas de instalaci n y manteni miento son efectuadas por personal autorizado y cualificado y de que dicho personal ha consultado detenidamente el manual para obtener la suficiente informaci n ne...

Страница 74: ...y contra posibles da os mec nicos provocados por golpes Los embalajes ablandados pierden firmeza pudiendo provocar lesiones al caerse el producto La bomba debe transportarse nicamente en motor carcasa...

Страница 75: ...cada 20 Rp 25 Rp 1 5 2 Datos t cnicos Caudal volum trico m x Dependiendo del tipo de bomba v ase el cat logo Altura de impulsi n m x Dependiendo del tipo de bomba v ase el cat logo Velocidad Dependien...

Страница 76: ...de la bomba Es posible solicitar ejecuciones especiales con materiales resistentes a los fluidos p ej para aceite SXS NSB S Agua sanitaria y agua para la industria alimentaria seg n la Directiva comun...

Страница 77: ...s si las conexiones son bridas 8 arandelas M16 para tornillos de brida M16 con bridas combinadas DN 32 DN 65 8 arandelas M16 para tornillos de brida M16 con bridas combinadas DN 32 DN 65 Instrucciones...

Страница 78: ...tulo 6 2 DCX DXM En el caso de una bomba doble los dos motores son id nticos y est n montados en una misma carcasa de bomba SXS NSB S Las bombas de esta serie est n especialmente adaptadas a las cond...

Страница 79: ...er realizadas exclusivamente por personal cualificado y de acuerdo con la normativa vigente Es imprescindible respetar en todo momento la normativa de prevenci n de accidentes Deber n respetarse las i...

Страница 80: ...NCI N Peligro de que se produzcan da os materiales Las impurezas del sistema de tuber as pueden destruir la bomba en funciona miento Limpie el sistema de tuber as antes de instalar la bomba Instale v...

Страница 81: ...las suministradas entre la cabeza de tornillo cabeza de tuerca y la brida combinada Fig 3 pos 1 No deben superarse los pares de apriete indicados en la tabla siguiente v ase m s abajo aunque se utilic...

Страница 82: ...el motor a fin de que los orificios para la evacuaci n de condensado queden despejados y el condensado que se forma en el motor pueda fluirsin impedimentos Fig 8 De lo contrario el condensado que asci...

Страница 83: ...Para garantizar la protecci n de la instalaci n contra el agua de goteo y la des carga de la tracci n del prensaestopas PG 13 5 deben usarse cables con un di metro exterior de 10 12 mm y proceder al m...

Страница 84: ...amiento con convertidor de frecuencia Los motores trif sicos de las versiones SCX DCX SXS pueden conectarse a un convertidor de frecuencia En caso de funcionamiento con convertidores de fre cuencia de...

Страница 85: ...y materiales En caso de que el tornillo de purga se encuentre completamente abierto podr a producirse una fuga de l quido caliente o de vapor con la posibilidad de que estos mismos elementos salgan di...

Страница 86: ...izaci n de tareas con la caja de bornes abierta existe peligro de electrocuci n por contacto con los bornes de alimentaci n el ctrica Desconecte la instalaci n y aseg rela de posibles conexiones invol...

Страница 87: ...e Durante la realizaci n de tareas en los equipos el ctricos existe peligro de muerte por electrocuci n Antes de iniciar las tareas de mantenimiento y reparaci n desconecte la bomba para que quede exe...

Страница 88: ...aje desmontaje del cabezal motor y provocar lesiones No sujete el cabezal motor con el rodete mirando hacia abajo Si se va a colocar solamente la caja de bornes en otra posici n no es necesario sacar...

Страница 89: ...limine los cuerpos extra os tras desmontar el bloque motor Presencia de aire en la bomba Purgue la bomba la instalaci n Las v lvulas de cierre de la instalaci n no est n com pletamente abiertas Abra c...

Страница 90: ...n caso de que el interruptor dife rencial vuelva a dispararse Compruebe que la bomba no tenga ning n defecto el ctrico Verifique el cable de alimenta ci n conectado a la bomba as como la conexi n el c...

Страница 91: ...cia un punto de tra bajo de la curva carac ter stica b Si procede retire el tornillo de purga visible fuera de la bomba compruebe el funcionamiento del rotor y desbloqu elo girando el extremo hendido...

Страница 92: ...cter sticas 12 Eliminaci n Eliminando este producto correctamente se evitan da os medioambientales y peligros para la salud 1 Para eliminar el producto o partes del mismo s rvase de empresas de elimi...

Страница 93: ...ETTO D USO DEVE ESSERE RIMESSO ALL UTILIZZATORE FINALE E RIMANERE SEMPRE DISPONIBILE SUL POSTO Questo prodotto stato fabbricato in un sito certificato ISO 14 001 rispettoso dell ambiente Questo prodot...

Отзывы: