English
Installation and starting instructions Smart Control
41
5 Product information
5.1 Type key
5.3 Scope of delivery
• Switchgear SC-Booster
• Wiring diagram
• Installation and operating instructions SC-Booster
• Installation and operating instructions frequency
converter (only for the SC-FC version)
• Test report acc. to EN 60204-1
5.4 Accessories
Accessories must be ordered separately:
Example:
SC
SC
e
Smart Controller for fixed speed pumps
Smart Controller for
electronic pumps
Booster
Pressure boosting application
4x
Number of pumps
3.0
Maximum nominal power P
2
[kW]
DOL
SD
Direct online (direct start)
Star-delta starting
FC
With frequency converter
5.2
Technical data (standard versions)
Mains supply voltage [V]:
3~400/380 V (L1, L2, L3, PE)
Frequency [Hz]:
50/60 Hz
Control voltage [V]:
24 V DC; 230 V AC
Max. current consumption [A]:
See rating plate
Protection class:
IP 54
Max. fuse protection on mains side [A]:
See wiring diagram
Ambient temperature [°C]:
0 to +40 °C
Electrical safety:
Degree of contamination II
Option
Description
BACnet MSTP
Connection to BACnet MSTP (RS485)
Modbus RTU
Connection to ModBus RTU (RS485)
LON
Connection to LON
Содержание S-CTRL-SC Series
Страница 2: ......
Страница 4: ...Fig 1a Fig 1b 1 3 4 2 4 1 5 3 2...
Страница 5: ...Fig 1c Fig 1d 5 1 3 2 6 7 4 8 5 1 3 2 6 7 4 8 1...
Страница 6: ...Fig 2 Fig 3 p bar M N O P R Q p bar Q m h p bar N O Q P p bar Q m h...
Страница 7: ...Fig 4a Fig 4b p bar M N O R p bar Q m h p bar M N O R p bar Q m h...
Страница 8: ...Fig 4c p bar M N O R p bar Q m h...