25
Models.
ADVANCE R
Available power ratings (VA / W).
750VA / 450W
1000VA / 600W
1500VA / 900W
marking.
Ce
Quality and environmental management.
ISo 9001 and ISo 140001 (certified by SgS)
Tab. 14.
ADVANCE R general technical specifications.
Models.
ADVANCE T
Available power ratings (VA / W).
850VA / 595W
1000VA / 700W
1500VA / 1050W
2000VA / 1400W
3000VA / 2100W
Technology.
Line-interactive with sine-wave output.
Input.
Input type.
Single-phase.
number of cables.
3 cables - Phase R (L) + neutral (n) and earth.
Rated voltage.
220 / 230 / 240 v AC
Input voltage range.
165..290 v AC
Input frequency range.
50 / 60 hz (auto-detectable).
Cold start (from batteries).
yes
Inverter.
waveform.
Pure sine wave.
Power factor.
0.7
Rated voltage.
220 / 230 / 240 v AC, selectable
output voltage accuracy (battery mode).
±10%
Total harmonic distortion (Thdv), with linear load.
< 5 % linear load
<10 % non-linear load
frequency.
50 / 60 hz.
with mains absent -backup mode- 50 / 60 ±1% hz.
Transfer time, line mode to battery mode (normal mode).
4 ms
Compatibility with APfC loads.
yes
Performance at full load, in normal mode with battery 100%
charged.
> 98 %
Performance at full load, in battery mode.
> 80 %
overload in line mode
> 110 % ±10 % Audible alarm and fault after 1 min
> 120 % ±10 % Immediate fault
overload in battery mode.
> 110 % ±10 % Audible alarm and fault after 1 min
> 120 % ±10 % Immediate fault
Batteries (AGM sealed 3 - 5 years life). Only devices other than B1
element voltage.
12 v dC
Capacity.
7 Ah
7.2 Ah
9 Ah
9 Ah
9 Ah
number of batteries in device connected in series / group
voltage.
2 / 24 v dC
2 / 24 v dC
4 / 48 v dC
number of accumulators in battery module connected in
series x no. packs in parallel / group voltage.
2 x 2/24 v dC
2 x 2/24 v dC
3 x 4/48 v dC
Low battery voltage.
23 v
23 v
45 v
blocking voltage for group end of backup.
20.5 v
20.5 v
40 v
Internal battery charger.
group floating voltage.
27.5 v
27.5 v
54.8 v
maximum charge current.
1 A (devices other than b1) / 10 A (b1 devices)
Recharge time.
4 hours to 90%
Other functions.
Cold start.
yes
emergency power off (ePo).
yes
General.
IeC input connectors.
IeC 60320 C14 10A
IeC 60320 C20
IeC output connectors.
IeC 60320 C13
IeC 60320 C3 +
Terminals
Communication ports.
(1 x RS232 -db9- and 1 x USb, functionally mutually exclusive).
Connector for external ePo installation
yes
Slot for optional cards.
SnmP
monitoring software.
Powermaster (free download).
Audible noise at 1 m in battery mode.
< 45 db
< 50 db
operating temperature.
0..+40ºC
Storage temperature with batteries.
–20..+50 ºC
Storage temperature without batteries.
–20..+70 ºC
working altitude.
2,400 masl (power degradation up to 5,000 m)
SPS ADVANCE R & T
UnInTeRRUPTIbLe PoweR SUPPLy (UPS)
USER MANUAL