Salicru SLC ADAPT Скачать руководство пользователя страница 9

9

5.  INSTALLATION

 

Read and follow all of the Safety Information set out 

or linked in chapter 2 of this document. Failure to 

adhere to any of the indications set out may cause a serious 

or very serious accident for those who are in direct contact 

with the unit or who are in the vicinity, as well as faults in 

the bypass panel, the unit or units, and/or in the loads con-

nected to the system.

 

Check that the information on the name plate is the right 

information for the installation.

 

A bad connection or operation can cause faults in the panel, 

the unit or units, and/or the loads connected to the system. 

Read the instructions in this manual carefully and follow 

the steps in the corresponding order.

 

Only proceed with the connection if all of the switches 

on the unit or units that make up the system are set to 

standby and there is no mains supply present (disconnect 

switch(es) of the power line(s) for the panel set to “OFF”).

 

All of the bypass panel connections described in this document 

will be implemented according to the labels on the unit, which 

in turn is based on the respective block diagrams. In structural 

terms, there are six different types of panel, regardless of their 

possible configurations (L, M, N, etc.):

 

ˆ

Generic manual bypass panel for a standard UPS (Fig. 3).

 

ˆ

Generic manual bypass panel for a UPS with a separate 

bypass line (Fig. 4).

 

ˆ

Manual bypass panel for “n” standard parallel or re-

dundant UPSs (Fig. 5). For UPS series CUBE3+, CUBE4 and 

TWIN PRO2.

 

ˆ

Manual bypass panel for “n” standard parallel or redundant 

UPSs (Fig. 6), for UPS series ADAPT, ADAPT-X, ADAPT2, 

TWIN PRO2, X-PERT and X-TRA.

 

ˆ

Manual bypass panel for “n” parallel or redundant UPSs 

with a separate bypass line (Fig. 7), for UPS series CUBE3+ 

and CUBE4.

 

ˆ

Manual bypass panel for “n” parallel or redundant UPSs 

with a separate bypass line (Fig. 8), for UPS series ADAPT, 

ADAPT-X, ADAPT2, X-PERT and X-TRA.

Beyond the structures indicated, there are slight nuances in 

terms of control connections between panels for each UPS 

range, which are clarified later in this chapter.

 

The figures in this document are by way of example, and are 

intended to show the linear and orderly layout of the operating 

mechanisms, without considering the physical format that 

may correspond to the unit’s power. Another factor to consider 

is the 

optional

 version shown in all figures, 

P

”, 

which corre-

sponds to operating mechanisms via circuit breakers.

 

Depending on the panel model, the enclosure may vary (plastic 

or metal box, or metal cabinet), so the adjacency between them 

could be affected, although the order would be maintained.

 

Depending on the power of the bypass panel and the version 

requested, the operating mechanisms may vary in number 

(parallel systems), in number of poles (according to the con-

figuration), format, size and type (disconnect switch or circuit 

breaker), but they will always be identified via the labels.

Pay attention to the steps indicated for any change in 

the operating mode, following the identification la-

bels on the operating mechanisms.

 

The manual bypass panel version with a separate static bypass 

line (-B), has additional connection and operating elements that 

are only available in this version. Disregard all references to 

them for the standard or basic version.

5.1.  TO BE CONSIDERED IN THE INSTALLATION

 

These instructions are generic for any manual bypass panel 

from this series. Disregard unavailable terminal connections.

 

All connections to the panel are made via terminals. However, 

on some models, and due to their high power or current, cables 

are connected directly to the disconnect switch or switch plates.

 

In terms of the earth and earth bonding cable connection, the 

panels usually have two points on opposite ends, generally 

threaded studs.

 

In the documentation provided on CD-ROM together 

with each UPS, the information relating to the “Recom-

mended Installation” is included for each of the input and 

output configurations. It shows the wiring diagrams, as well as 

the protection size and the minimum cross-sections of the ca-

bles connected to the unit, according to its nominal working 

voltage. All values are calculated for a 

total maximum cable 

length of 30 m

 between the distribution board, unit and loads.

 

ˆ

For longer lengths, correct the cross-sections to prevent 

voltage drops, observing the regulations or standards 

of the country.

 

ˆ

In the same documentation and for each configuration, the 

information for “N” parallel units is available, as well as the 

characteristics of the “Backfeed protection”.

All indications relating to the “Backfeed protection” 

referred to in the UPS user manual must be followed, 

considering the availability or not of the separate static 

bypass line and the corresponding actions to be taken in 

each case.

 

In parallel systems, the length and cross-section of 

the  cables that run from the protection board to 

each UPS and from these to the board will be the same for 

all of them without exception.

USER'S MANUAL        

Содержание SLC ADAPT

Страница 1: ...SLC ADAPT SLC ADAPT X SLC ADAPT 2 SLC CUBE 3 SLC CUBE 4 7 5 80 kVA SLC X PERT SLC X TRA SLC TWIN PRO2 MAKE BEFORE BREAK MANUAL BYPASS PANEL FOR UPS BM USER S MANUAL...

Страница 2: ...2 SALICRU...

Страница 3: ...Systemswith n equipmentsinparallelorredundant 5 3 7 1 Powerconnections 5 3 7 2 Connection of the auxiliary contact of the manual bypass switch of each UPS with the one in the bypass panel not availab...

Страница 4: ...onnel exclusively Although we have made every effort to guarantee a com plete and accurate information in this user s manual we are not responsible for any errors or omissions that may exist The image...

Страница 5: ...SING THIS MANUAL The generic documentation for the unit is provided in digital format on a pen drive and includes among other documents the system user manual itself and document EK266 08 relating to...

Страница 6: ...d in accordance with the EN ISO 9001 standard on Quality Assurance and is certified by SGS The mark indi cates conformity with the EEC Directives 2014 35 EU Low voltage directive 2014 30 EU Electromag...

Страница 7: ...lbypasspanelto theUPS With a separate static bypass line Fig 2 These panels have separate terminal blocks for the input and static bypass networks which allows both networks to be supplied from differ...

Страница 8: ...e from a source other than the UPS input line B Unit with separate bypass line L Single phase input single phase output configuration L Single phase input three phase output configuration N Three phas...

Страница 9: ...a circuit breakers Depending on the panel model the enclosure may vary plastic ormetalbox ormetalcabinet sotheadjacencybetweenthem could be affected although the order would be maintained Depending on...

Страница 10: ...n process is complete the panel should be repacked until it is started up in order to protect it against mechanical shock dust dirt etc 5 2 2 Storage The unit must be stored in a dry well ventilated a...

Страница 11: ...identified with the label ensuring that this is done before supplying input voltage to the bypass panel Connect the loads to the set of terminals identified as LOADS OUTPUT on the bypass panel respect...

Страница 12: ...nt Aux cont available on manual bypass panels for these UPSs SLC ADAPT SLC ADAPT X SLC ADAPT2 SLC CUBE 3 SLC CUBE 4 SLC X PERT SLC X TRA 1 YES YES YES YES YES YES YES 2 YES YES YES 1 YES YES 1 The IDI...

Страница 13: ...ese UPSs SLC CUBE 3 SLC CUBE 4 SLC TWIN PRO 2 1 YES YES 2 YES YES Fig 5 Manualbypasspanelfor n standardparallelorredundantUPSs forUPSseriesCUBE3 CUBE4andTWINPRO2 5 3 7 3 Connection between the auxilia...

Страница 14: ...t circuit breaker Fig 6 Manual bypass panel for n standard parallel or redundant UPSs for the ADAPT ADAPT X ADAPT2 TWIN PRO2 X PERT and X TRA series INPUT LINE LOADS OUTPUT MANUAL BYPASS Aux cont Manu...

Страница 15: ...programmed as an auxiliary contact for the NC output circuit breaker Fig 8 Manual bypass panel for n standard parallel or redundant UPSs with a separate bypass line for the ADAPT ADAPT X ADAPT2 TWIN...

Страница 16: ...ut Auxiliary Contact Input Battery Circuit Breaker Auxiliary Contact Input External Digital Input External Digital Input External Digital Input External Digital Input SREG_LOGIC_POS_NEG__DIG_ALMS_BOOL...

Страница 17: ...PSNSTATICBYPASS Off UPS NOUTPUT Off Fig 10 Position of the manual bypass switches Out of service with several UPS s Make sure that all the loads are shutdown start up switches turned Off Proceed in th...

Страница 18: ...er Off according to the procedure stated in the User s installation and start up manual of the UPS It is essential to shutdown the inverter of the UPS before proceeding otherwise a short circuit at it...

Страница 19: ...to the factory for its fixing This option is valid when the power of the equipments which are still installed is enough to supply the loads Evenitisunlikelybutnotimpossible anynewfaultinany of the rem...

Страница 20: ...according to the procedure stated in the User s installation and start up manual of the equipment Turn the UPS INPUT and UPS OUTPUT switches of the bypass panel to Off In case of including the separat...

Страница 21: ...21 USER S MANUAL...

Страница 22: ...any salicru salicru_SA Product Range Uninterruptible Power Supplies UPS Lighting Flow Dimmer Stabilisers DC Power Systems Static Inverters Photovoltaic Inverters Voltage stabilisers The Technical Serv...

Отзывы: