24
SALICRU
O1
3 sec
Output voltage
selection
120
(*)
127
100
110
115
•
The values indicated with
(*)
are factory default settings.
•
The settings can only be made in ‘byPA’ or ‘STby’ mode.
•
To carry out any modification of the configuration, follow the indicated
sequence with the inverter necessarily Off.
•
To exit the main menu from any position, press buttons + together.
O2
O3
O4
O6
O9
1O
11
12
15
17
OO
Selection of device
as UPS or CF
Selection of device
as CF
ECO mode
selection
Static bypass
selection
Non-critical load
output sockets
Backup time for
non-critical load
output sockets
Backup time for all
output sockets
Battery pack Ah
capacity
EPO contact
configuration
Time shown
configuration
DIS
(*)
ENA
BAT50
(*)
BAT60
DIS
(*)
ENA
ENA
(*)
DIS
DIS
(*)
ENA
0.. 999
DIS
(*)
0.. 999
7.. 999
AO
(*)
AC
EAT
(*)
RAT
ESC
DIS
Frequency converter disabled. Device functions as a UPS.
ENA
Frequency converter enabled. In this operating mode, the
static bypass is disabled by default.
BAT 50 UPS with output frequency of 50 Hz.
BAT 60 UPS with output frequency of 60 Hz.
CF 50
(1)
CF with output frequency of 50 Hz.
CF 60
(1)
CF with output frequency of 60 Hz.
(1)
With parameter ‘02’ = ‘ENA,’ the ‘CF 50’ or ‘CF 60’ variables
are displayed instead of ‘BAT 50’ or ‘BAT 60.’
DIS
ECO mode disabled.
ENA
ECO mode enabled.
ENA
Bypass enabled, with the inverter of the UPS ‘Off’.
DIS
Bypass disabled, with the inverter of the UPS ‘Off’.
DIS
Programming of output sockets for non-critical loads disabled.
ENA
Programming of output sockets for non-critical loads enabled.
Backup time setting for non-critical load output sockets when
operating in Battery mode.
Default setting is 999.
Backup time setting for all output sockets when operating in Battery
mode.
Default setting is ‘DIS’, deactivated. Take into consideration that the
available backup will depend on battery charge level
Note: When it is at ‘0’, the backup time will be 10 seconds.
Battery pack Ah. Do not change for standard models and adjust in
extended backup models (see section ).
Although the device will still work without adjusting this value on
the display, the time shown in minutes will be incorrect and the bat-
tery charging current will not automatically adjust to them.
EPO button contact type setting.
AO
EPO activated when circuit opened.
AC
EPO activated when circuit closed.
EAT
Shows available backup time.
RAT
Shows elapsed backup time.
Fig. 11.
Settings menu.