5.  INSTALLATION.

Installation of the equipment must be carried out only by 

authorized and qualified persons.

Before carrying out any maintenance, repair or manipulation 

of any of the equipment connections, the device must be 

disconnected from any power source, both the equipment power 

supply and the measurement.

The equipment must be installed downstream of the 

general protections of the installation.

The equipment is installed in a distribution panel on a DIN rail 

46277.
The following cables have to be used to connect the equipment 

(the units make reference to the cable area):

 

Voltage measurements and PS --> 1.5mm2 (0.45/0.75kV 

minimum rated voltage)

 

ˆ

Current transformers 

 1 mm

2

 

÷

 1.5 mm

2

 

ˆ

Dry contacts 

  

 1.5 mm

2

 

ˆ

RS-485 COM 

 

 1.5 mm

2

 (Braided Shielded Cable).

 

ˆ

Dig Input 

→ 

 1.5 mm

2

The cables used for the connections must be crimped with 

terminals.

5.1.  CURRENT TRANSFORMERS. 

It's strongly recommended to use the current transformers 

delivered by SALICRU.
If another current transformers are going to be used, SALICRU has 

to be informed. Anyway, SALICRU will not be held responsible of 

any malfunction when not offical current transformers are used.

5.1.1.  Current transformer setting switch.

CURRENT PROBE SETTING SWITCH

SW1

SW2

SW3

SW4

SW5

CT

0

0

0

0

0

30 A / 100 mA

0

0

0

0

1

80 A / 100 mA

0

0

0

1

0

90 A / 100 mA

0

0

0

1

1

100 A / 100 mA

0

0

1

0

0

120 A / 100 mA

0

0

1

1

1

200 A / 100 mA

0

0

1

1

0

300 A / 100 mA

Table 2.  Position of the microswitches according to the 

power of the CT transformer. See Detail A (Fig. 2).

SLC ENERGY MANAGER

   ENERGY METER

USER'S MANUAL        

Содержание Equinox SLC

Страница 1: ...SLC ENERGY MANAGER ES EN MANUAL DE USUARIO ENERGY MANAGER...

Страница 2: ...2 SALICRU...

Страница 3: ...EQUIPO 4 3 TABLA DE REFERENCIA 5 INSTALACI N 5 1 TRANSFORMADORES DE CORRIENTE 5 1 1 Ajuste de los micro interruptores del transformador de corriente 5 2 DIAGRAMAS DE CONEXI N 5 2 1 Diagrama de conexi...

Страница 4: ...hacemos responsables de los errores u omisiones que pudieran existir Las im genes incluidas en este documento son a modo ilus trativo y pueden no representar exactamente las partes del equipo mostrada...

Страница 5: ...alizarlainstalaci n puesta en marcha y operaci n de una forma sencilla y ordenada Finalmente una vez que el equipo ha sido instalado y est ope rando es recomendable guardar la documentaci n descargada...

Страница 6: ...lectromagn tica CEM 2011 65 EU Restricci n de sustancias peligrosas en apa ratos el ctricos y electr nicos RoHS Seg n las especificaciones de las normas armonizadas Normas de referencia UNE EN IEC 610...

Страница 7: ...izaci n y con trol de energ a destinado a gestionar la energ a de la instalaci n Existen tres modelos SLC EM SLC ENERGY MANAGER SLC EM T SLC ENERGY MANAGER T SLC EM Lite SLC ENERGY MANAGER Lite 4 2 VI...

Страница 8: ...S L3 Iin T L3 Iin T Medidas de tensi n N Neutre L1 Fase 1 L2 Fase 2 L3 Fase 3 Rel s de salida R1 RL1COM RL1NC RL1NO R2 RL2COM RL2NC RL2NO RS 485 Comm A DO RI B DO RI GND GND Entradas digitales Ethern...

Страница 9: ...os 1 5 mm2 RS 485 COM 1 5 mm2 Cable trenzado blindado Entrada digital 1 5 mm2 Los terminales de los cables empleados para el conexio nado deben crimparse 5 1 TRANSFORMADORES DE CORRIENTE Se recomienda...

Страница 10: ...10 SALICRU 5 2 DIAGRAMAS DE CONEXI N 5 2 1 Diagrama de conexi n monof sico Fig 3 Diagrama de conexi n monof sico 5 2 2 Diagrama de conexi n trif sico Fig 4 Diagrama de conexi n trif sico...

Страница 11: ...elbusenbuscadeinversores reci n conectados Este proceso tambi n se puede activar a trav s de la interfaz de usuario El EM tambi n puede enviar comandos a los diferentes inversores para cambiar algunos...

Страница 12: ...tr mites normativos para la intervenci n del S S T en caso de aver a 7 2 2 Exclusiones SALICRU no quedar obligada por la garant a si advierte que el defecto en el producto no existe o fue causado por...

Страница 13: ...az de usuario Web embebida INVERSOR Capa f sica RS 485 Protocolo Modbus Velocidad 9600 Bits de datos 8 Bit de stop 1 Paridad No REL S Cantidad 2 Tensi n nominal 250 Vac Corriente nominal 6 A ENTRADA D...

Страница 14: ...14 SALICRU...

Страница 15: ...15 ES SLC ENERGY MANAGER ENERGY METER USER S MANUAL...

Страница 16: ...os Sistemas de Alimentaci n Ininterrumpida SAI UPS Estabilizadores Reductores de Flujo Luminoso Fuentes de Alimentaci n Onduladores Est ticos Inversores Fotovoltaicos Estabilizadores de Tensi n La red...

Страница 17: ...SLC ENERGY MANAGER EN USER S MANUAL ENERGY MANAGER...

Страница 18: ...18 SALICRU...

Страница 19: ...EWS OF THE DEVICE 4 3 REFERENCE TABLE 5 INSTALLATION 5 1 CURRENT TRANSFORMERS 5 1 1 Current transformer setting switch 5 2 CONNEXION DIAGRAMS 5 2 1 Single phase conexi n diagram 5 2 2 Three phase conn...

Страница 20: ...r by qualified personnel Althoughnoefforthasbeensparedtoensurethattheinforma tion in this user manual is complete and accurate we are not responsible for any errors or omissions that may exist The ima...

Страница 21: ...s whatsoever Finally once the equipment is installed and operating it is recom mended to save the documentation downloaded from the website CD ROM or Pen Drive in a safe and easy to access place for a...

Страница 22: ...ion of the use of hazardous substances in electrical and electronic equipment RoHS According to the specifications of the harmonized standards Ref erence standards UNE EN IEC 61010 1 2011 A1 2020 Safe...

Страница 23: ...oring and controllerdeviceintendedtomanagetheenergyontheinstallation There are three models SLC EM SLC ENERGY MANAGER SLC EM T SLC ENERGY MANAGER T SLC EM Lite SLC ENERGY MANAGER Lite 4 2 VIEWS OF THE...

Страница 24: ...S L2 Iin S L3 Iin T L3 Iin T Voltage measurements N Neutral L1 Phase 1 L2 Phase 2 L3 Phase 3 Output Relays R1 RL1COM RL1NC RL1NO R2 RL2COM RL2NC RL2NO RS 485 Comm A DO RI B DO RI GND GND Digital input...

Страница 25: ...ers 1 mm2 1 5 mm2 Dry contacts 1 5 mm2 RS 485 COM 1 5 mm2 Braided Shielded Cable Dig Input 1 5 mm2 The cables used for the connections must be crimped with terminals 5 1 CURRENT TRANSFORMERS It s stro...

Страница 26: ...26 SALICRU 5 2 CONNEXION DIAGRAMS 5 2 1 Single phase connexion diagram Fig 3 Single phase connexion diagram 5 2 2 Three phase connexion diagram Fig 4 Three phase connexion diagram...

Страница 27: ...ch of them and from time to time scanning the bus for newly connected inverters This process can be triggered through the user interface too The EM can also send commands to the different inverters to...

Страница 28: ...treamline any regulatory procedures for the intervention of T S S in the event of a fault 7 2 2 Exclusions Our company will not be bound by the warranty if it notices that the defect in the product do...

Страница 29: ...rface Embedded web INVERTER Physical layer RS 485 Protocol Modbus Speed 9600 Data bits 8 Stop bit 1 Parity No RELAYS Quantity 2 Rated Voltage 250 Vac Rated Current 6 A DIGITAL INPUT Quantity 1 Type 5...

Страница 30: ...30 SALICRU...

Страница 31: ...EN 31 SLC ENERGY MANAGER ENERGY METER USER S MANUAL...

Страница 32: ...Product Range Uninterruptible Power Supplies UPS Lighting Flow Dimmer Stabilisers DC Power Systems Static Inverters Photovoltaic Inverters Voltage stabilisers Variable frequency drives The Technical...

Отзывы: