8
SALICRU
3.
Insert the metal terminals into the MC4 connectors, until you hear a click. Once this is done, pull gently on the cable to make sure
it is correctly attached.
4.
Screw the cap onto the body of each connector, making sure all of the elements fit together perfectly and that the rubber seals seal
the cable with the connector:
Use the special spanners for
MC4 connectors in order to
ensure optimum tightening
without damaging the
connectors.
5.
Check the polarity and voltage of the photovoltaic panels before connecting them to the inverter, in line with the
values shown in the following table:
Specifications
Inverter model
EQX 5000-2T
EQX 8000-2T
EQX 10000-2T
Maximum DC input power (W)
5500
8800
11000
Maximum DC input voltage (VDC)
900
1000
Operating range (VDC)
200-800
MPPT range (VDC)
260-800
350-800
400-800
MPPT trackers / inputs per MPPT
2/1
Max. input current per MPPT x no. of MPPTs
10 A x 2
12 A x 2
12,5 A x 2
Max. short-circuit current per MPPT (Isc PV) x no. of MPPTs
11 A x 2
13 A x 2
14 A x 2
Содержание EQUINOX EQX 5000-2T
Страница 1: ...EQX 5000 2T EQX 8000 2T EQX 10000 2T SOLAR INVERTERS QUICK GUIDE...
Страница 2: ...2 SALICRU...
Страница 6: ...6 SALICRU Mounting process Material required Steps to follow...