12
SALICRU
7.
Connection diagram:
3.3. JUNCTION BOX
The junction box must incorporate all of the additional protective elements (both AC and DC) that are required in order to protect the
inverter once it has been installed.
The protective DC elements that must be incorporated into the junction box are as follows:
Model
Isolator switch
Fuses
Overvoltage protector
If there is no lightning
conductor
If there is a lightning conductor or a
high probability of lightning strike
EQX 5000-2T
Built into the device
Fuses: 1000 VDC 15 A / string
Type II, 40 kA 1000 VDC
Type I+II, 5 kA 1000 VDC
EQX 8000-2T
Built into the device
Fuses: 1000 VDC 15 A / string
Type II, 40 kA 1000 VDC
Type I+II, 5 kA 1000 VDC
EQX 10000-2T
Built into the device
Fuses: 1000 VDC 15 A / string
Type II, 40 kA 1000 VDC
Type I+II, 5 kA 1000 VDC
The AC elements required are as follows (and must also be physically separated):
Model
Circuit breaker
Residual-current device
Overvoltage protector
Pre-fuses. Maximum value (x 3)
EQX 5000-2T
3P 10 A Curve C
4P 25 A 30 mA Class A
Type II, 40 kA 400 V TNC
125 A gL
EQX 8000-2T
3P 16 A Curve C
4P 25 A 30 mA Class A
Type II, 40 kA 400 V TNC
125 A gL
EQX 10000-2T
3P 16 A Curve C
4P 25 A 30 mA Class A
Type II, 40 kA 400 V TNC
125 A gL