5.  DESCRIPTION.

 

The manual bypass is an option which allows feeding the 

load or loads either from an equipment - UPS or stabilizer-, 

or from commercial mains directly without breaking the 

power supply during its switching manoeuvring, because it 

is make before break type, unless it is used in a wrong way 

without respecting the stated procedure in section 7.

 

In correlation with Fig. 1 and 2, Fig 3 and 4 illustrations 

show the single line diagrams of both structures.

The structure is identical in both figures, although there 

are some differences between models. The most important 

one is the auxiliary contact from the manual bypass switch, 

which comes from a microswitch located in the back side of 

the protection cover and connected to a signal connector in-

ternally. By means of the electrical connection with the sup-

plied cable between this connector and the one available in 

several equipments like the UPS from TWIN PRO2 and/or 

RT2 series, when the protecting cover from manual bypass 

is removed, the UPS shifts from «Inverter output mode» to 

«Static bypass mode», considering that the system was 

on normal mode operating previously. Therefore, it makes 

easier the operating and avoids possible wrong manoeu-

vring that it could cause serious damages to the installation 

set, loads included.

UPS / STABILIZER

RACK MANUAL BYPASS 16 A

3 IEC 

AC input mains to 

manual bypass

3 IEC

1 IEC

Equipment IEC 

input power supply 

connector

Equipment 

IEC output

Output to 

loads

To 

equipment 

input

From equipment output

Fig. 3. 

Wiring between the UPS and the 3 kVA bypass.

UPS / STABILIZER

RACK MANUAL BYPASS         

40 / 63 A

Output 

terminals to 

loads

AC input power 

supply

EMBS connector 

To 

equipment 

input

From  equipment output

Equipment input 

terminals

Output 

terminals 

to loads

Fig. 4. 

Wiring between UPS and 6 and 10 kVA bypass.

Содержание BM-R 63 A

Страница 1: ...USER S MANUAL RACK MOUNTING MANUAL BYPASS BM R 3 6 and 10 kVA...

Страница 2: ...2 SALICRU...

Страница 3: ...and contents 6 2 LOCATION AND CONSIDERATIONS 6 2 1 1 Location 6 3 WIRING 7 OPERATING 7 1 START UP 7 2 TRANSFERENCE FROM NORMAL OR UPS MODE TO BYPASS 7 2 1 3 kVA manual bypass models from NORMAL to BYP...

Страница 4: ...ed personnel Although no effort has been spared to ensure that the information in this user manual is complete and accurate we are not responsible for any errors or omissions that may exist The images...

Страница 5: ...rms are used interchangeably in the document to refer to Manual bypass Bypass equipment or unit Rack mounting manual bypass T S S Technical Service and Support Client installer operator or user These...

Страница 6: ...ercialized in accordance with the standard EN ISO 9001 of Quality Management Systems and certified by SGS body The marking shows the conformity to the EEC Directive by means of the application of the...

Страница 7: ...y IEC connector or input terminals 2 To be connected to the UPS or stabilizer input 3 To be connected to the UPS or stabilizer output 4 IEC connectors or output terminals to loads 5 Main protective ea...

Страница 8: ...onnection with the sup plied cable between this connector and the one available in several equipments like the UPS from TWIN PRO2 and or RT2 series when the protecting cover from manual bypass is remo...

Страница 9: ...TION AND CONSIDERATIONS 6 2 1 1 Location Remove the angles and screws from the plastic bag and assemble them on the rack mounting bypass These devices are designed to be integrated into rack cabinets...

Страница 10: ...ing on its power rate Respect the stated input and output strictly other wise the UPS or stabiliser manual bypass and loads can be damaged As this is an equipment with protection against electrical sh...

Страница 11: ...ction cover 13 is removed the equipment will shift to this operating mode automati cally provided that the bypass signal 10 of the own rack mounting bypass is connected with the UPS or stabiliser 3 Tu...

Страница 12: ...fix an hypothetical failure the procedure formality will be smoother 8 2 2 Out of scope of supply In case it is detected that the product is not damaged or the fault was caused by a wrong manoeuvring...

Страница 13: ...ximum permissible current of the manual bypass switch 16 A 40A 63A Selective output breakers IEC connectors 2 Maximumpermissiblevoltageoftheoutputbreakers 250 V Output breaker size 10 A Number of outp...

Страница 14: ...14 SALICRU...

Страница 15: ...15 BM R Rack mounting manual bypass USER S MANUAL...

Страница 16: ...Product Range Uninterruptible Power Supplies UPS Lighting Flow Dimmer Stabilisers DC Power Systems Static Inverters Photovoltaic Inverters Voltage stabilisers Variable frequency drives The Technical S...

Отзывы: