11

7.  OPERATING.

 

UPS or stabilizer operating manual, which the manual by-

pass is linked has to be available.

 

Make sure that all connections have been done properly 

and the instructions and labelling on each device as regards 

to installation have been respected.

 

It is needed and mandatory to proceed in the established 

order.

 

Consider the available protections:

 

ˆ

In 3 KVA models, two circuit breakers, one for each 

output terminal strip with IEC connectors.

 

ˆ

In 6 and 10 KVA models, one input circuit breaker of 40 

or 63 A respectively.

7.1.  START UP.

 

Supply voltage to the manual bypass input.

 

In the 6 and 10 kVA models, turn the input circuit breaker  

from manual bypass to «On».

 

Start the UPS or stabilizer up, by respecting the steps 

stated in their documentation (user's manual).

7.2.  TRANSFERENCE FROM 

«

NORMAL

»

 OR 

«

UPS

»

 MODE 

TO 

«

BYPASS

»

.

7.2.1.  3 kVA manual bypass models, from 

«

NORMAL

»

 to 

«

BYPASS

» 

mode.

1. 

Transfer the own UPS or stabilizer to «Bypass mode» (shutdown 

the inverter or the stabiliser, depending on the case, in 

order to feed the load through their internal static bypass 

switch). Confirm the output voltage availability through the 

LCD panel or indicator.

Any transfer manoeuvring will be done with 

the UPS or stabilizer on «Bypass mode».

2. 

Turn the manual bypass switch 

a from «UPS» to «BYPASS». 

The load will be supplied from the AC grid directly.

3. 

Those UPS or stabilizers models with input circuit breaker, turn 

it «Off». The UPS or stabilizer will be out of service com-

pletely.

4. 

In case, a preventive maintenance, reparation or replacement 

of the equipment were  needed, disconnect both cables 

with the IEC connector, which go from the UPS or stabilizer 

to the rack mounting manual bypass.

7.2.2.  6 and 10 kVA manual bypass models, from 

«

UPS

»

 to 

«

BYPASS

» 

mode.

1. 

Transfer the own UPS or stabilizer to «Bypass mode» (shutdown 

the inverter or the stabiliser, depending on the case, in 

order to feed the load through their internal static bypass 

switch). Confirm the output voltage availability through the 

LCD panel or indicator.

Any transfer manoeuvring will be done with 

the UPS or stabilizer on «Bypass mode».

2. 

Remove the protection cover 

13

 from the manual bypass 

switch.

In case the UPS or stabilizer have not been transferred to 

«Bypass mode», when the protection cover 

13

 is removed, 

the equipment will shift to this operating mode automati-

cally, provided that the bypass signal 

10

 of the own rack 

mounting bypass is connected with the UPS or stabiliser.

3. 

Turn the manual bypass switch 

from «UPS» to «BYPASS». The 

load will be supplied from the AC grid directly.

4. 

Those UPS or stabilizers models with input circuit breaker, turn 

it «Off». The UPS or stabilizer will be out of service com-

pletely.

5. 

In case, a preventive maintenance, reparation or replacement 

of the equipment were  needed, disconnect the cables 

between the UPS or stabilizer and the rack mounting manual 

bypass.

It is recommended to disconnect both ends of the 

cable, UPS or stabilizer and rack mounting bypass, 

in order to avoid any incident of wrong manoeuvring.

7.3.  TRANSFERENCE FROM 

«

BYPASS

»

 TO 

«

NORMAL

»

 OR 

«

UPS

» 

MODE.

7.3.1.  3 kVA manual bypass models, from 

«

BYPASS

»

 to 

«

NORMAL

» 

mode.

1. 

Check that the complete set is connected according to section 

6.3, as regards to the power of each model.

2. 

UPS or stabiliser models with input circuit breaker, turn it  «On», 

and the «Bypass mode» will be restored (the UPS inverter or 

stabiliser has to be turned «Off»).

3. 

Turn the manual bypass switch 

8

 from «BYPASS» to «NORMAL». 

The load will be supplied through the AC grid through the 

UPS or stabiliser static bypass.

 Any transfer manoeuvring will be done with 

the UPS or stabilizer on «Bypass mode».

4. 

Turn the UPS inverter or stabilizer «On», by respecting the steps 

stated in their documentation (user's manual).

7.3.2.  6 and 10 kVA manual bypass models, from 

«

BYPASS

»

 

to 

«

UPS

» 

mode.

1. 

Check that the complete set is connected according to sec-

tion 6.3, as regards to the power of each model.

2. 

UPS or stabiliser models with input circuit breaker, turn it  «On», 

and the «Bypass mode» will be restored (the UPS inverter or 

stabiliser has to be turned «Off»).

3. 

Turn the manual bypass switch 

8

 from «BYPASS» to «UPS». The 

load will be supplied through the AC grid through the in-

ternal UPS or stabiliser static bypass.

Any transfer manoeuvring will be done with 

the UPS or stabilizer on «Bypass mode».

4. 

Put the protection cover 

13

 of the manual bypass switch back, 

otherwise the UPS inverter or stabiliser will not start up.

5. 

Turn the UPS inverter or stabiliser «On», by respecting the steps 

stated in their documentation (user's manual).

BM-R 

Rack mounting manual bypass

 

 

USER'S MANUAL        

Содержание BM-R 3

Страница 1: ...USER S MANUAL RACK MOUNTING MANUAL BYPASS BM R 3 6 and 10 kVA...

Страница 2: ...2 SALICRU...

Страница 3: ...and contents 6 2 LOCATION AND CONSIDERATIONS 6 2 1 1 Location 6 3 WIRING 7 OPERATING 7 1 START UP 7 2 TRANSFERENCE FROM NORMAL OR UPS MODE TO BYPASS 7 2 1 3 kVA manual bypass models from NORMAL to BYP...

Страница 4: ...ed personnel Although no effort has been spared to ensure that the information in this user manual is complete and accurate we are not responsible for any errors or omissions that may exist The images...

Страница 5: ...rms are used interchangeably in the document to refer to Manual bypass Bypass equipment or unit Rack mounting manual bypass T S S Technical Service and Support Client installer operator or user These...

Страница 6: ...ercialized in accordance with the standard EN ISO 9001 of Quality Management Systems and certified by SGS body The marking shows the conformity to the EEC Directive by means of the application of the...

Страница 7: ...y IEC connector or input terminals 2 To be connected to the UPS or stabilizer input 3 To be connected to the UPS or stabilizer output 4 IEC connectors or output terminals to loads 5 Main protective ea...

Страница 8: ...onnection with the sup plied cable between this connector and the one available in several equipments like the UPS from TWIN PRO2 and or RT2 series when the protecting cover from manual bypass is remo...

Страница 9: ...TION AND CONSIDERATIONS 6 2 1 1 Location Remove the angles and screws from the plastic bag and assemble them on the rack mounting bypass These devices are designed to be integrated into rack cabinets...

Страница 10: ...ing on its power rate Respect the stated input and output strictly other wise the UPS or stabiliser manual bypass and loads can be damaged As this is an equipment with protection against electrical sh...

Страница 11: ...the UPS or stabilizer have not been transferred to Bypass mode when the protection cover 13 is removed the equipment will shift to this operating mode automati cally provided that the bypass signal 10...

Страница 12: ...fix an hypothetical failure the procedure formality will be smoother 8 2 2 Out of scope of supply In case it is detected that the product is not damaged or the fault was caused by a wrong manoeuvring...

Страница 13: ...ximum permissible current of the manual bypass switch 16 A 40A 63A Selective output breakers IEC connectors 2 Maximumpermissiblevoltageoftheoutputbreakers 250 V Output breaker size 10 A Number of outp...

Страница 14: ...14 SALICRU...

Страница 15: ...15 BM R Rack mounting manual bypass USER S MANUAL...

Страница 16: ...alicru_SA Product Range Uninterruptible Power Supplies UPS Lighting Flow Dimmer Stabilisers DC Power Systems Static Inverters Photovoltaic Inverters Voltage stabilisers Variable frequency drives The T...

Отзывы: