4.  OPRESENTATION.

4.1.  SYSTEM CONFIGURATION

The Modular UPS is configured by the following part: Power 

modules, Bypass & Monitoring module, and cabinet with 

manual Bypass switch. One or several battery strings should 

be installed to provide backup energy once the utility fails. The 

UPS structure is shown in Fig. 1.

.

Rectifier

AC/DC

Main

Static Bypass

Manual Bypass

Inverter

DC/AC

Charge/

Discharge

Output

Battery

Bypass

Fig. 1. 

UPS Configuration

4.2.  POWER MODULE

The power module structure is shown as Fig. 2. The power 

module contains a rectifier, an inverter, and a DC/DC converter 

for charge and discharge of the external batteries.

Rectifier

AC/DC

Inverter

DC/AC

DC/DC

Input

Battery

Output

Fig. 2. 

Power module structure

4.3.  OPERATION MODE

The Modular UPS is an on-line, double-conversion UPS that 

permits operation in the following modes:

 

Normal mode

 

Battery mode

 

Bypass mode

 

Maintenance mode (manual bypass)

 

ECO mode

 

Auto-restart mode

 

Frequency Converter mode

4.3.1.  Normal Mode

The inverter of power modules continuously supply the critical 

AC load. The rectifier/charger derives power from the AC mains 

input source and supplies DC power to the inverter while si-

multaneously FLOAT or BOOST charging its associated backup 

battery.

Rectifier

AC/DC

Main

Static Bypass

Manual Bypass

Inverter

DC/AC

Charger

DC/DC

Output

Battery

Bypass

Fig. 3. 

Normal mode operation diagram

4.3.2.  Battery Mode

Upon failure of the AC mains input power, the inverter of power 

modules, which obtain power from the battery, supply the 

critical AC load. There is no interruption in power to the crit-

ical load upon failure. After restoration of the AC mains input 

power, the” Normal mode” operation will continue automati-

cally without the necessity of user intervention.

Rectifier

AC/DC

Main

Static Bypass

Manual Bypass

Inverter

DC/AC

Discharge

DC/DC

Output

Battery

Bypass

Fig. 4. 

Battery mode operation diagram

 

Note:

With the function of Battery cold start, the UPS may start without 

utility. See more detail in section 8.1.2.

ADAPT

 UNINTERRUPTIBLE POWER SUPPLY

USER'S MANUAL        

Содержание ADAPT

Страница 1: ...ADAPT UNINTERRUPTIBLE POWER SUPPLY UPS Modules 25 300 kVA III III USER S MANUAL...

Страница 2: ...T 6 2 INSTALLINGPOWERMODULE 6 3 BATTERY 6 4 CABLEENTRY 6 5 POWERCABLES 6 5 1 Specifications 6 5 2 Powerswitch 6 5 3 ConnectingPowerCables 6 6 CONTROLANDCOMMUNICATIONCABLES 6 6 1 CommunicationInterface...

Страница 3: ...ANDARDS 10 2 ENVIRONMENTALCHARACTERISTICS 10 3 MECHANICALCHARACTERISTIC 10 4 ELECTRICALCHARACTERISTICS 10 4 1 ElectricalCharacteristics InputRectifier 10 4 2 ElectricalCharacteristics IntermediateDCLi...

Страница 4: ...onnel exclusively Although we have made every effort to guarantee a com plete and accurate information in this user s manual we are not responsible for any errors or omissions that may exist The image...

Страница 5: ...figures of section 4 additional annexes will be edited if they were deemed appropriate or nec essary Generally they will be delivered in hardcopy Finally once the equipment is installed and operative...

Страница 6: ...ervention over the equip ment by the end user the manufacturer is not responsible WARNING SLC ADAPT This is a category C3 UPS product This is a product for commercial and industrial application in the...

Страница 7: ...tart mode Frequency Converter mode 4 3 1 Normal Mode The inverter of power modules continuously supply the critical AC load The rectifier charger derives power from the AC mains input source and suppl...

Страница 8: ...Bypass Manual Bypass Inverter DC AC Charger DC DC Output Battery Bypass Fig 6 Maintenance mode operation diagram Danger During Maintenance mode dangerous voltages are present on the terminal of input...

Страница 9: ...dule 1 10 Requisite installed on site Table 1 UPS Configuration 4 3 9 UPS Outlook The UPS outlook is shown as Fig 8 to Fig 10 1 Front Door 2 Dust Filter 3 Back Door 4 Foot Print Fig 8 System outlook o...

Страница 10: ...end of charging ensure the fresh air volume of the battery installation environment must meet EN50272 2001 requirements If external batteries are to be used the battery circuit breakers or fuses must...

Страница 11: ...le the case 4 Remove the protective foam around the cabinet Fig 15 Remove the protective foam 5 Check the UPS a Visually examine if there are any damages to UPS during transportation If any contact to...

Страница 12: ...Fig 17 Open the carton 4 Remove the foam cover See Fig 18 1 Carton 2 Foam packing 3 Power module Fig 18 Remove the foam cover 5 Take out the UPS with plastic package and dismantle the packaging mater...

Страница 13: ...d and immovable 6 Positioning done Attention Auxiliary equipment is needed when the mounting floor is not solid enough to support the cabinet which helps distribute the weight over a larger area For i...

Страница 14: ...quantity of battery blocks con nected in serial being able to select it among the figures above stated Fig 21 Battery string wiring diagram Danger The battery terminal voltage is of more than 400Vdc...

Страница 15: ...ual Current Device is not suggested for the system 6 5 3 Connecting Power Cables The steps of connecting power cables are as follows 1 Verify that all the external input distribution switches of the U...

Страница 16: ...onmental temperature J3 2 TEMP_COM common terminal Table 4 Description of J2 and J3 Remote EPO Input Port J4 is the input port for remote EPO It requires shorting NC and 24V and disconnecting NO and 2...

Страница 17: ...act in terface The interface diagram is shown in Fig 29 and descrip tion is shown in Table 8 Fig 29 Bypass dry contact interface diagram Port Name Function J8 1 BYPASS_ALARM_NC Bypass relay normally c...

Страница 18: ...nction J10 1 UTILITY_FAIL_NC Mains failure warning relay normally closed will be open during warning J10 2 UTILITY_FAIL_NO Mains failure warning relay normally open will be closed during warning J10 3...

Страница 19: ...hing 1 Green for 1S Off for 2S Rectifier soft starting 2 Green short time flashing 1 Green for 1S Off for 2S Inverter soft starting 3 Green medium time flashing Green for 1S Off for 5S Power module in...

Страница 20: ...gative voltage battery negative charge discharge current and bus nega tive voltage Select triangle of highlighted Battery information is presented in the Digit Displays Area battery negative voltage b...

Страница 21: ...TE 10 11 12 1 LCD touch screen 2 EPO switch 3 Audible Alarm Buzzer 4 Status indicator 5 Bypass indicator 6 Rectifier indicator 7 Inverter indicator 8 Load indicator 9 Battery indicator 10 Bypass trans...

Страница 22: ...one Function Key Description EPO Long press cut off the load power shut down the rectifier inverter static bypass and battery BYP Long press transfer to the bypass Push the button up in the back of t...

Страница 23: ...loat Output Voltage Output Current Bypass Voltage Fig 35 Structure of menu tree 7 5 MAIN MENU The main menu includes Cabinet Module Setting Log Operate and Scope and it is described in details below 7...

Страница 24: ...normally the white indicating the absent of the module and red indicating the absence of the module or in fault Version Information The version information for LCD of the power module and monitor Subm...

Страница 25: ...isplay 5 Submenu Fig 41 Module The Cabinet comprises sectors of title information display power module information version information and submenu The sectors are described as follows Title Present th...

Страница 26: ...ted module A Output phase current of selected module Hz Output frequency of selected module PF Output power factor of selected module Load V Load voltage of selected module Load The percentage of the...

Страница 27: ...is needed and the setting must be done by com missioning engineer c For the Battery and SERVICE a Two level password is needed and it is set by the after service personal d For the RATE and CONFIGURE...

Страница 28: ...y Limited Permitted working Frequency for BypassSettable 1Hz 3Hz 5Hz Dust Filter Maintenance Period Setting Dust Filter Maintenance Period BATTERY Battery Number Setting the number of the battery 12V...

Страница 29: ...ge 5 Battery Float Set Charger is Floating Battery Voltage 6 Battery Discharge Set Battery is Discharging 7 Battery Connected Set Battery cables Connected 8 Battery Not Connected Set Battery cables Di...

Страница 30: ...tdown 73 Manual Boost Charge Set Manually Battery Boost Charge 74 Manual Float Charge Set Manually Battery Float Charge Sq LCD Display Explanation 75 UPS Locked Set Inhibit to shut down the UPS 76 Par...

Страница 31: ...nning and hours of discharging Reset Dust filter Using Time Reset the time of dust filter using by touching the icon it includes the days of using and mainte nance period TEST COMMAND Battery Test By...

Страница 32: ...uching the corresponding icon in the left side of the interface The waves can be zoomed in and zoom out Touch the icon to display the 3 phase output voltage Touch the icon to display the 3 phase outpu...

Страница 33: ...ed below in Table 22 Indicator Status Indicator Status Rectifier green Inverter green Battery red Load green Bypass off Status red Table 22 Supplying the load 7 The UPS is in Normal Mode Close the bat...

Страница 34: ...of the by pass is over track and when the system needs to transfer to Normal mode by manual 8 2 4 Switching the UPS into Maintenance Bypass Mode from Normal Mode These following procedures can transf...

Страница 35: ...Fig 54 Set the period time in the item Auto Maintenance Discharge Period and confirm 6480 Fig 53 Setting period for battery auto discharge Warning The load for the auto maintenance discharge should be...

Страница 36: ...y of total 900KVA Two UPS cabinets are connected as is shown in Fig 55 UPS1 UPS2 Load Connected Output Power Supply Power Supply Fig 55 Parallel diagram The parallel board is located at the back of th...

Страница 37: ...nected with all single devices to form a closed loop as is shown in Fig 57 Fig 57 Parallel connection For more details of parallel operation please refer to the In struction for Parallel Operation of...

Страница 38: ...ush the power module into the cabinet following the steps in section 6 2 and the power module will automatically join the system 9 3 INSTRUCTION FOR MAINTAINING BYPASS MODULE Confirm the UPS is operat...

Страница 39: ...39 1 2 1 Dust filter 2 Bracket Fig 58 Dust filter on the back side of front door ADAPT UNINTERRUPTIBLE POWER SUPPLY USER S MANUAL...

Страница 40: ...level dB 65dB 100 carga 62dB 45 carga at 1 meter dB 65dB 100 load 62dB 45 load Altitude of Operation m 1000 load derated 1 per 100m from 1000m and 2000m Relative Humidity 0 95 non condensing Operatin...

Страница 41: ...192 264 for the batteries of the 2V Float charge voltage V cell VRLA 2 25V cell selectable from 2 2V cell 2 35V cell Constant current and constant voltage charge mode Temperature compensation mV Celsi...

Страница 42: ...ritical load 10 4 4 Electrical Characteristics Bypass Mains Input TEM Unit Value Rated AC voltage Vac 380 400 415 three phase four wire and sharing neutral with the bypass Rated AC Current A 455 Overl...

Страница 43: ...PLAY AND INTERFACE Item Value Display LED LCD Color touch screen Interface Standard RS232 RS485 USB Dry Contact Option SNMP AS 400 Table 33 Display and Interface ADAPT UNINTERRUPTIBLE POWER SUPPLY USE...

Страница 44: ...rra 100 08460 Palautordera BARCELONA Tel 34 93 848 24 00 Fax 34 93 848 22 05 services salicru com SALICRU COM www linkedin com company salicru salicru_SA Product Range Uninterruptible Power Supplies U...

Отзывы: