background image

41

8.2.1.  Troubleshooting guide for devices up to 3 kva.

Symptom

Possible cause

Solution

no alarms or indications on the LCd display and mains 

voltage normal. 

The power cable is not connected correctly.

Check that the power cables are firmly connected to 

the mains. 

The power cable is connected to an IeC output connector 

on the UpS.

Correctly connect the power cable to the respective 

IeC connector.

Icon 

 and warning code 

 flash on the LCd 

display and the audible alarm modulated every second 

is active.

The epo function is activated.

Close the epo signal circuit to deactivate it. 

Icon 

 and warning code 

 flash on the LCd 

display and the audible alarm modulated every two 

seconds is active.

neutral earth fault detection. Inverted phase and neutral 

input cables.

disconnect the input plug from the AC power socket 

and invert the connection of the phase and the supply 

neutral (rotate the plug 180º).

Icon 

 and warning code 

 flash on the LCd 

display and the audible alarm modulated every two 

seconds is active.

The internal or external batteries are badly connected

Check that all batteries are properly connected.

Fault code 27 and the 

BATT fAULT

 message 

are shown on the LCd display. The alarm sounds 

continuously.

The voltage of the batteries is too high or the charger is 

faulty.

Contact the distributor or seller or, failing that, our 

T.S.S.

Fault code 28 and the 

BATT fAULT

 message are 

shown on the LCd display. The audible alarm sounds 

continuously.

The voltage of the batteries is too low or the charger is 

faulty.

Contact the distributor or seller or, failing that, our 

T.S.S.

Icon 

 and warning code 

 flash 

on the LCd display and the audible alarm modulated 

every second is active.

The UpS is overloaded.

disconnect the excess loads from the output sockets.

The UpS is overloaded. The connected loads are powered 

directly from the mains through the bypass.

disconnect the excess loads from the output sockets.

After repeated overloads, the UpS is locked in bypass 

mode. The connected loads are powered directly from the 

mains.

disconnect the excess loads from the output sockets, 

shut down the device and restart it.

Fault code 49 is shown on the LCd display. The 

audible alarm sounds continuously.

UpS input overcurrent.

disconnect the excess loads from the output sockets.

Fault code 43 is shown on the LCd display. The 

audible alarm sounds continuously.

The UpS shuts down automatically as a result of an 

overload in the output of the device.

disconnect the excess loads from the output sockets 

and restart it.

Fault code 14 is shown on the LCd display. The 

audible alarm sounds continuously.

The UpS shuts down automatically as a result of a short 

circuit in the output.

Check the output wiring and that the connected loads 

are not short-circuited

Fault codes 01, 02, 03, 11, 12, 13 and 41 are shown 

on the LCd display. The audible alarm sounds 

continuously.

An internal fault has occurred in the UpS. This is due to one 

of two possibilities:

1. The load is still powered, but directly from the mains 

through the bypass.

2. The load is no longer powered.

Contact the distributor or seller or, failing that, our 

T.S.S.

The backup time is shorter than expected.

The batteries do not charge completely.

Charge the batteries for at least 5 h and then check 

their charge state. If the problem persists, contact the 

distributor or seller or, failing that, our T.S.S.

Faulty batteries.

Contact the distributor or seller or, failing that, our 

T.S.S. for battery replacement.

Fault code 2A is shown on the LCd display. The 

audible alarm sounds continuously.

Charger short-circuited at its output.

Check whether the connection of the external battery 

pack connected to the UpS is short-circuited.

Fault code 45 is shown on the LCd display. At the 

same time, the audible alarm sounds continuously.

The charger does not provide output and the battery voltage 

is less than 10 v per element.

Contact the distributor or seller or, failing that, our 

T.S.S.

Tab. 23. 

Troubleshooting guide.

SLC TWIN RT2

 UnInTeRRUpTIbLe poweR SUppLy SySTemS (UpS)

USER MANUAL        

Содержание 698CC000002

Страница 1: ...SLC TWIN RT2 0 7 10 kVA UNINTERRUPTIBLE POWER SUPPLY SYSTEMS UPS USER MANUAL...

Страница 2: ...on battery module 5 1 5 6 Vertical tower type mounting with PDU 5 1 5 7 Rack mounting in 19 cabinet with PDU 5 1 5 8 Preliminary considerations before connection 5 1 5 9 Preliminary considerations bef...

Страница 3: ...7 2 4 2 Operating mode Description of state 7 2 4 3 Warning or alert codes 7 2 4 4 Error or fault codes 7 2 4 5 Warning or alert indicators 7 3 Control panel for 4 kVA to 10 kVA models 7 3 1 Audible...

Страница 4: ...ed personnel Although no effort has been spared to ensure that the information in this user manual is complete and accurate we are not responsible for any errors or omissions that may exist The images...

Страница 5: ...ssioning to be performed in a simple and orderly manner without having any doubts whatsoever Finally once the equipment is installed and operating it is recommended to save the documentation downloade...

Страница 6: ...duct may cause radio interference in which case the user must take additional measures SLC TWIN RT2 4 10 kVA This is a category C3 UPS This is a product for commercial and industrial application in th...

Страница 7: ...self will always prevail The nameplate of the device shows all of the values relating to its main properties and characteristics Act accordingly for its installation 0 7 to 3 kVA models 4 to 10 kVA mo...

Страница 8: ...grammable at disconnection for non critical loads Connector for connection to external battery module Standard and B1 3 kVA models COM port USB RS232 COM port AC power IEC connector Smart slot protect...

Страница 9: ...ery module connector Fig 3 Rear view of battery modules for extended backups PDU for 4 to 6 kVA devices Output circuit breaker Output IEC connectors Output circuit breaker Output IEC connectors PDU fo...

Страница 10: ...without batteries but with a space reserved for installation in the same box for models whose standard version specifies this For other models the battery pack will be installed in the manner conside...

Страница 11: ...ains contact T S S With the inverter shut down the output supplies mains power directly through the static bypass of the device provided that it has AC input power Frequency converter CF mode Operatin...

Страница 12: ...hout interruptions to the power supply of the protected system while preventing unnecessary hazards for the technical personnel 4 5 3 Communication card The UPS features a slot at the rear for inserti...

Страница 13: ...UPS 1 battery module Information for warranty registration 2 metal pieces for use as handles and screws for installing the unit in a rack cabinet 2 plastic pieces to extend the base of the UPS and ena...

Страница 14: ...distance is considerable it is recommended to transport the device in its packaging to the installation site and then unpack it 5 1 5 Siting immobilising and considerations All TWIN RT2 series UPSs ar...

Страница 15: ...t the guides at the required height ensuring correct tightening of the fixing screws and appropriate fitting in the machining according to each case Place the device onto the guides and insert it all...

Страница 16: ...he upper or lower part of the cabinet it is recommended that two people carry out the installation operations Fix the UPS and the battery module to the cabinet frame by means of the screws supplied wi...

Страница 17: ...n of the cables must always be considered in relation to the size of the terminals of the switches so that they are correctly fastened across their entire cross section for optimum contact between the...

Страница 18: ...g systems in parallel only in models 3 kVA To access the signal block it is necessary to remove its protective cover Slot for the integration of one of the optional electronic communication units Remo...

Страница 19: ...ig 2 as critical loads will be reserved Take into account that they are set by default as critical loads The 3 kVA models also have a 16A IEC connector that enables the connection of a load of the tot...

Страница 20: ...through the mesh available in the cable bundle of them being compulsory to fix the con nectors of both ends to the connectors fitted in the battery case by means of the supplied screws and duly tight...

Страница 21: ...of each UPS In the event of acquiring a manual bypass board through another conduit check that it has this auxiliary contact and connect it to the terminal block of the UPS or each device in parallel...

Страница 22: ...ngth between the input and output cables of the device must be less than 20 When the distance between the UPSs in parallel and the circuit breaker board is more than 20 metres the difference in length...

Страница 23: ...from each other Fig 20 View of ViewPower s main screen Installation procedure Go to the web page http support salicru com Select the required operating system and follow the instructions described on...

Страница 24: ...ns depending on the model will start to function Then the main start screen will be displayed after a test of the device On the 4 to 10 kVA models it is necessary to press the ON button for a second t...

Страница 25: ...nd The devices that make up the current parallel system will switch to Bypass mode Switch the devices to manual bypass 1 Remove the mechanical lock on the distribution board s manual bypass switch or...

Страница 26: ...a faulty UPS in an operational parallel system The steps to follow to replace a UPS in a system consisting of two or three units are the same as those for incorporating a device except for the differ...

Страница 27: ...cted to the output as a by displaying four equivalent segments respectively in the following proportion 0 25 26 50 51 75 and 76 100 Information about programmable outputs P1 Indicates that the program...

Страница 28: ...ESC ESC Escape HLS HLS Upper voltage limit for transfer to battery mode LLS LLS Lower voltage limit for transfer to battery mode AO AO EPO normally open AC AC EPO normally closed EAT EAt Estimated bac...

Страница 29: ...ble with each press OFF ENTER UPS shutdown Press this button for at least 2 seconds Confirmation of selection Press this button to confirmselection in the device ssettings mode Tab 6 Functionality of...

Страница 30: ...ctly related to the capacity of the battery pack The charger will adapt the charging factor automatically according to the value of the total capacity entered up to the maximum of the current that is...

Страница 31: ...ameter 02 ENA the CF 50 or CF 60 variables are displayed instead of BAT 50 or BAT 60 DIS ECO mode disabled ENA ECO mode enabled ENA Bypass enabled with the inverter of the UPS Off DIS Bypass disabled...

Страница 32: ...the output voltage from the bypass in ECO mode energy saving LCD display CF mode Description When the input frequency is between 46 and 64 Hz the UPS can be set to a constant output frequency of 50 o...

Страница 33: ...too low 2A Battery charger short circuited at its output 41 Overtemperature 43 Output overload 45 Charger fault 49 Input overcurrent Tab 13 Error or fault code 7 2 4 5 Warning or alert indicators Code...

Страница 34: ...in relation to the point where it is located ON Starting up the UPS Press the button for at least 2 seconds Confirmation of selection Press this button to confirmselection in the device ssettings mod...

Страница 35: ...codes list Description and settings Code 01 Output voltage Fig 27 Parameter 3 setting Output voltage It is possible to choose one of the following values for the output voltage between phase and neutr...

Страница 36: ...Bypass enabled When selected bypass mode is enabled DIS Bypass disabled If selected automatic bypass is permitted but not manual switch to bypass At this point manual switch to bypass is understood as...

Страница 37: ...external battery pack of 45 Ah belonging to it 45 Ah 7 Ah 6 4 When rounding down value 6 must be entered in parameter 3 The basic reason for adjusting the setting is as follows without it affecting t...

Страница 38: ...n the regulation ranges and ECO mode is activated the UPS supplies the output voltage from the bypass in ECO mode energy saving LCD display ECO CF mode Description When the output frequency is selecte...

Страница 39: ...switch cover open 3D Bypass not available 3E Start up fault Tab 20 Warning or alert code 7 3 4 4 Error or fault codes Code Error or fault description 01 DC bus start up fault 02 DC bus overvoltage 03...

Страница 40: ...nal which is in turn connected to earth any metal part of the device Repair and or maintenance work must be carried out by our T S S except for the replacement of batteries which can be performed by q...

Страница 41: ...After repeated overloads the UPS is locked in Bypass mode The connected loads are powered directly from the mains Disconnect the excess loads from the output sockets shut down the device and restart i...

Страница 42: ...of the following fault codes 01 02 03 04 11 12 13 14 1A 21 24 35 36 41 42 or 43 are displayed on the LCD display and the audible alarm sounds continuously An internal fault has occurred in the UPS Thi...

Страница 43: ...ged 89 90 91 93 Performance at full load in ECO mode 95 96 97 99 Overload in line mode 110 130 5 min 100 110 10 min 130 140 30 sec 110 130 1 min 140 150 1 5 sec 130 1 sec 150 100 ms Overload in batter...

Страница 44: ...rallel devices 5 As a frequency converter the power supplied will be 78 of the rated 6 As a frequency converter the power supplied will be 60 of the rated Tab 25 General technical specifications 9 2 G...

Страница 45: ...g through the visible light spectrum to infrared the latter called IRED infra red emitting diode Circuit breaker A circuit breaker is a device capable of interrupting the electrical current of a circu...

Страница 46: ...46 SALICRU...

Страница 47: ...47 SLC TWIN RT2 UNINTERRUPTIBLE POWER SUPPLY SYSTEMS UPS USER MANUAL...

Страница 48: ...any salicru salicru_SA Product Range Uninterruptible Power Supplies UPS Lighting Flow Dimmer Stabilisers DC Power Systems Static Inverters Photovoltaic Inverters Voltage stabilisers The Technical Serv...

Отзывы: