www.salda.lt
.
5
Converter MIN 0-250 x10
0
.
6
Converter MAX 1-250 x10
20
.
7
Controller Modbus master/slave address 0: Master
1 - 247: Slave
0
.
8
Modbus data transfer rate
0: 1200
1: 2400
2: 4800
3: 9600
4: 19200
5: 38400
6: 57600
7: 115200
4
.
9
Modbus parity
0: None
1: Even
2: Odd
0
.
Controlled device
(Remote controller will automatically recog-
nize the PRV and ECO plates))
0: None
1: Custom
2: ECO
3: PRV
0
.
Modbus address of controlled device 1 - 247
1
.
SET Temperature address 00:00 - FF:FF
00:00
.
3
SET Fan speed (%) address 00:00 - FF:FF
00:00
.
4
SET Fan speed fixed address 00:00 - FF:FF
00:00
.
5
SET Pressure address 00:00 - FF:FF
00:00
.
6
SET CO2 address 00:00 - FF:FF
00:00
.
7
Temperature address 00:00 - FF:FF
00:00
.
8
Alarm 1 address 00:00 - FF:FF
00:00
.
9
Alarm 2 address 00:00 - FF:FF
00:00
.
3
Alarm 3 address 00:00 - FF:FF
00:00
.
3
Alarm 4 address 00:00 - FF:FF
00:00
.
3
Alarm 5 address 00:00 - FF:FF
00:00
.
33
Alarm 6 address 00:00 - FF:FF
00:00
.
34
Alarm 7 address 00:00 - FF:FF
00:00
.
35
Alarm 8 address 00:00 - FF:FF
00:00
.
36
Alarm 9 address 00:00 - FF:FF
00:00
.
37
Alarm 10 address 00:00 - FF:FF
00:00
.
38
Restore controller factory settings 0: No
1:Yes
0
.
39
Modbus (Holding register) type parameter
reading and changing tool 0- 999
0
.
4
Modbus (Coil register) type parameter read-
ing and changing tool 0 - 999
0
.
4
Control panel version -
-
.
4
Fan’s controlled by 0..10VDC signal start
delay time in seconds 0 - 120
0
.
43
0..10VDC ON/OFF 0:OFF 1:ON
0
To restore factory settings, service password “022” should be reentered.