EN |
9
RIS PE 3.0 v2020.1
• It is recommended to use the accessories-holders. This will reduce vibration transmitted by the unit to the air duct system and environment.
•
Enough space must be left for opening of the maintenance door and filter covers.
• If the installed ventilation unit is attached to a wall, it may transmit noise vibrations to the premises. Though the level of noise caused by the
fans is admissible, it is recommended to mount the unit at the distance of 400 mm from the nearest wall. If it is not possible, the mounting of the
unit is recommended on the wall of the room where the level of noise is not important.
• Ducts are connected to the unit in such way that they could be easily disassembled and the heater could be removed from the unit when per-
forming service or repair works
The protective film is intended to protect the unit during transportation. It is recommended to remove the film because other
-
wise oxidation signs may occur.
Before every heating season the condensate tube shall be filled with water as indicated during the first startup!
W
α
W
α
α
5.5.1. PLACE REQUIREMENTS FOR THE EQUIPMENT AND MOUNTING POSITIONS
L
1,5xL
L
1,5xL
H
H
Figure 5.5.1.1.
Min. distance to open the door - 1,5xL; Min. distance to open control box door - H > 400 mm.
5.5.2. MOUNTING ON SEALING
0 -1
10-15mm
20
Figure 5.5.2.1.
RIS 400 PE 3.0; RIS 700 PE 3.0
Figure 5.5.2.2.
RIS 1000 PE 3.0; RIS 1500 PE 3.0
- Installing should only be performed by qualified and trained staff.
- AHU are mounted to the ceiling using mounting elements (bolts, screws and etc.). It is needed to keep 1° inclination in drainage direction (picture
below), do not mount AHU in opposite direction.
- RIS 1000PE 3.0, RIS 1500PE 3.0 Air handling unit is fixed using auxiliary profiles.
- Do not mount AHU in other positions.
- Mount the unit on safe and firm base.
- Connect unit to duct system with reference to information on AHU body.