48
| EN
AMBERAIR COMPACT S-CX v2023.3
EX2 module:
WIRING TERMINALS TYPE
FUNCTION
X32: 1
230VAC digital output (max 100mA)
Fire damper actuator 1 open
X32: 4
230VAC digital output (max 100mA)
Fire damper actuator 2 open
X32: 2,5
Neutral
Neutral contact for digital output ref.
X32: 3,6
Earth
Earth contact for the damper actuators
X33: 1
230VAC digital output
Combined heating/cooling coil circulation pump start
X33: 2
Neutral
Neutral contact for digital output ref.
X33: 3
Earth
Earth contact for the circulation pump
X34: 1,2,3
230VAC digital outputs and ref.
X35: 3,5
230VAC digital output
Outdoor/exhaust air dampers open
X35: 4,6
230VAC digital output
Outdoor/exhaust air dampers close
X35: 1,8
Earth
Earth contact for the damper actuators
X35: 2,7
Neutral
Neutral contact for digital output ref.
X36: 1,2,3,4
230VAC digital outputs and ref.
X37: 1,2
Capacitor
X38: 1,2,3
Power
230VAC power supply for X32-X36, X39
X39: 3
230VAC digital output (max 100mA)
Electrical heater starts/water heater circulation pump starts
X39: 1
Earth
Earth contact for the circulation pump
X39: 2
Neutral
Neutral contact for digital output ref.
X40: 1,2
Digital output
DX cooler reverse