14 

 

3.

 

  

 

Unit Operation 

1.Start up 

※ 

Start the unit and select the running mode. 

※ 

After the unit runs for 30 minutes, check the following items.   

1.  Check if Water flow rate and water pressure are in the normal range. 

2.  Measure 

the 

high/low 

pressure. 

 

The 

low 

pressure 

should 

be 

between0.3~0.6Mpa and high pressure should be between 1.35~2.1Mpa. 

3.  Check the compressor electric current. 

4.  Make  sure  all  the  temp.  sensors  are  properly  set  and  the  capillary  should  be 

fastened to avoid any damage. 

2.Long-term Unit Stoppage 

Pay attention to the following items for long time stoppage

 

1.  Check if any leakage and make sure the unit is filled with refrigerant. 

2.  Discharge the water from system to avoid freezing during wintertime. 

3.  Turn off the power of the unit and water pump. 

3.Startup after long time stoppage 

1.  Fill in the water again and open the air discharge valve at the same time.    After the 

water is filled, close the valve. 

2.  Put the power on and check water flow rate and if any leakage. 

3.  Put the power on for 24 hours to warm up the compressor before starting the unit. 

4.

 

  

 

System Protection 

  Anti-freezing during Winter 

For heat pump unit which is in the status of power save during winter time, when the water 

temp is lower than the set anti-freezing temp, the unit will automatically start the anti-freezing 

function.    Thus please put the power on during the winter time when the unit is used. 

  Anti-freezing of plate heat exchanger 

While cooling and the water leaving temp is lower than 3

℃,

the compressor will be stopped 

to protect the heat exchange.    The water pump will keep running. 

Motor Overload Protection 

Compressor over high temp or overload protection. 

Water pump motor protection 

Fan motor protection. 

  Temp Sensor Protection 

The system will alarm if anything wrong with the temp sensor. 

  Compressor startup protection 

The  compressor  has  2  minutes  delay  for  starting.    If  the

 

compressor  is  stopped  while

 

operation has the delay of 3 minutes. 

  Flow rate protection 

Install the flow switch to protect system from over low water flow rate and stop the unit while 

Содержание FVCA Series

Страница 1: ...Air Cooled Mini Chiller Installation Operation and Maintenance Manual Models FVCA 40 200 B R 50 80 C R Ref S 080 05 12 Sakura Air Conditioner User friendly Earth friendly...

Страница 2: ...ed Mini Chiller Installation Operation and Maintenance Manual Note Please read this Manual carefully before install and operate the unit and keep it probably for reference in the future Air Cooled Min...

Страница 3: ...Mini Air Cooled Chiller 2 Contents 1 Notes on Safety 3 2 Installation 4 3 Electric 6 4 Test Run 12 5 Control 14 6 Service and Maintenance 16...

Страница 4: ...ers or dealers Don t install the unit by yourself which may cause water leakage electric shock or fire Caution Please install the electric cutoff The main control must use same power supply with the u...

Страница 5: ...nstallation The base of the unit can be made of concrete The unit also can be set on the supporter which can be installed on the wall or pillar An isolator pad should be used between the unit and base...

Страница 6: ...or valve etc The flow switch must be installed The close type expansion tank is used to protect the water pipe from breaking caused over high pressure The auto water supply valve and water discharge v...

Страница 7: ...alve is recommended Auto Water Supply Valve Auto water supply valve can be either vertically or horizontally installed at the water return circuit but not upside down The water supply volume should be...

Страница 8: ...llowing chart is the minimal requirement Model Power Min Wire Current Mini Power Supply FHCA40C R 220 50 1 25 6 FHCA40B R 380 50 3 12 5 2 5 FHCA50B R 380 50 3 13 5 4 FHCA60B R 380 50 3 14 4 FVCA50C R...

Страница 9: ...Sensor Outer Coil 1 Sensor Water Leaving Temp Sensor 50 Ambient Temp Sensor Return Water Temp Sensor 2 12 MMP 2 13 8 P 9 S R T 50 White White Low Pressure Switch Power Supply Protection KM1 2 FR1 2 F...

Страница 10: ...oi l 2 Sensor O ut er Coi l 1 Sensor MMP Am bi ent Tem p Sensor Pl ease i nst al l t he f l ow sw i t ch ot her w i se t he syst em w i l l al ar m W i r e cont r ol Fl ow Sw i t ch Pow er Suppl y Pr...

Страница 11: ...W W at er Leavi ng Tem p Sensor O ut er Coi l 1 Sensor Am bi ent Tem p Sensor Ret ur n W at er Tem p Sensor P P Low Pr essur e Sw i t ch Pow er Suppl y Pr ot ect i on KM 1 2 FR1 2 FL M M P LP RVR Fl o...

Страница 12: ...er Leavi ng Tem p Sensor O ut er Coi l 1 Sensor Am bi ent Tem p Sensor Ret ur n W at er Tem p Sensor P P P Low Pr essur e Sw i t ch Pow er Suppl y Pr ot ect i on KM 1 2 FR1 2 FL M M P LP RVR Fl ow Sw...

Страница 13: ...l 2 Sensor O ut er Coi l 1 Sensor Ret ur n W at er Tem p Sensor W at er Leavi ng Tem p Sensor Am bi ent Tem p Sensor LP Low Pr essur e Sw i t ch W i r e cont r ol M M P AC Cont act or Fl ow Sw i t ch...

Страница 14: ...mage the water pump and the whole water system Recommended Water Flow Rate m3 h Unit Pipe Size Min Flow Rate Standard Flow Rate Max Flow Rate FHCA40 1 1 056 1 6 2 4 FHCA50 1 1 188 1 8 2 7 FHCA60 1 1 4...

Страница 15: ...2 Put the power on and check water flow rate and if any leakage 3 Put the power on for 24 hours to warm up the compressor before starting the unit 4 System Protection Anti freezing during Winter For...

Страница 16: ...he same set information after the electricity is cut off Colorful LCD Display Trouble Codes Display Time clock still works if no electricity 1 Mode Switching the mode by pressing the mode key 2 Temper...

Страница 17: ...The system can keep some important data such as the set temp password etc 10 Trouble Codes Code Item Condition 2 Low Temp Compressor Stop Water Pump still works 3 High Temp Compressor Stop Water Pump...

Страница 18: ...ription Remark C1 Coil Temp Display Use set key to select the corresponding system coil temp C2 Water Leaving Temp C3 Outdoor Temp 12 Pre heating on compressor oil If to pre heat the compressor oil th...

Страница 19: ...ng term stoppage Before starting the unit next time fill in the water and check the unit again Warming up the unit for 6 hours and make sure the unit is in good condition then start the unit Note Sepa...

Отзывы: