VM600
- 13 -
Chapter 4 Parameter function
“○”
: the parameter can be modified in both standby and operating state
;
“●”
: the parameter can’t be modified in operating state
;
“
◎
”
:the parameter is the actual detected and recorded value which can’t be modified
;
Note: the communication address is hexadecimal.
4.1 Functional parameter
Parameter
Name
Setting Range
Default
Property
Address
F0.00
Reserved
Reserved
0
●
0000
F0.01
Command source selection
0
:
Operation panel control
(
LED off
)
1
:
Terminal control
(
LED on
)
2
:
Communication LED (LED
blinking
)
0
●
0001
F0.02
Setting
main
frequency
source X
0
:
Digital setting (non-retentive at power
failure)
1
:
Digital setting (retentive at power
failure)
2
:
Keypad Knob
3
:
AI
4
:
Multi-stage speed
5
:
Simple PLC
6
:
Communication
2
●
0002
F0.03
Keypad setting frequency
0.00Hz
~
F0.05
50.0Hz
○
0003
F0.04
Running direction selection
0
:
Forward
1
:
Reverse
0
○
0004
F0.05
Maximum Output
Frequency
50.00Hz
~
400.00Hz
50.0Hz
●
0005
F0.06
Upper Limit of Frequency
F0.07
~
F0.05
50.0Hz
○
0006
F0.07
Lower Limit of Frequency
0.00Hz
~
F0.06
0.0Hz
○
0007
F0.08
The option of frequency
lower limit
0
:
Running at frequency lower limit
1
:
Stop
2
:
Standby
0
○
0008
F0.09
Carrier Frequency
1kHz
~
6.0kHz
6.0kHz
●
0009
F0.10
Acceleration Time 1
0.0s
~
100.0s
10.0s
○
000A
F0.11
Deceleration Time 1
0.0s
~
100.0s
10.0s
○
000B
F0.12
Stop Mode
0
:
Decelerate to stop
1
:
Free stop
0
○
000C