Conditions of Use  

Application & Maintenance Guideline for LUNAX Door Systems 

 

©

20

19

/S

ubj

ect

 to c

ha

nge

 

 Ver

si

on

 19

-0

1  

M

KT

-R

EG

-AG

-LU

N

AX

-19

-0

3/3 

lunax.com 
vetrotech.com 

 
 

SYSTEM COMPONENTS / HARDWARE 

Intumescent  fire-  and  smoke-seals  are  critical  parts  of  fire-
rated LUNAX 
other hardware components have been removed, badly fitted 
or  are  damaged,  they  must  be  replaced  with  the  same  type 
material originally supplied. Please contact your installer or a 
VETROTECH sales office for information. 

For  necessary  or  required  checks  and  maintenance  of  LUNAX 
Door  Systems  hardware  (e.g.  door  closers,  locks,  hold-open 

instructions  and  guidelines  or  contact  the  local  VETROTECH 
sales office. 
 
 

Regular Maintenance 

The  frequency  of  door  functionality  tests  and  maintenance 
may  vary  depending  on  local  regulations,  frequency  of  use  / 
type of occupancy. The following instructions are for reference 
only. Please verify potential regulatory requirements with local 
authorities. 
 

 

Functionality Test 

As  a  proper  function  of  the  door  closer  and  other  hardware 
components  has  to  be  guaranteed  at  all  times,  scheduled 
checks must be carried out as follows: 

 

Inspect  glass  and  hardware  for  any  damages, 
excessive  wear  and  tear,  unusual  sounds  or 
friction 

 

Check  for  any  obstacles,  rubbing,  twisted 
intumescent  seals  or  smoke  seals,  etc.  possibly 
preventing  a  free  movement.  Seals  must  be 
properly positioned and fully attached 

 

Verify  accurate  gap  dimensions  as  per  images 
below and adjust if outside tolerance 

 

Open  each  door  leaf  completely  and  release  it 
until closed. The door is considered closed, when 
positioned  in  the  center  of  the  intumescent 
strip,  located  in  the  perimeter  supporting 
structure.  Repeat  for  each  direction  of  swing,  if 
applicable 

 

Open each door leaf approx. 5°-15° and release it. 
The  door  must  fully  close  (and  latch,  if 
applicable) 

 

If applicable, verify door locks or latches properly. 
For  electrical  locks  verify  the  functionality  in 
powered and non-powered operation modes 
 

 
 

 

Door closing speed from fully open (90° to 180°) 
is to be approx. 10 seconds. Ensure the door does 
not  slam.  Adjust  speed  as  necessary  (refer  to 
door closer manual) 

 

Check proper function of electro-magnetic hold-
open device. Hold-open devices are connected to 
the  fire  detection  and  alarm  system  and 
designed to release automatically in case of fire, 
by  power  being  disconnected.  Simulate  lack  of 
power to verify proper function 
 

Any  and  all  parts  defective,  dislocated,  worn,  etc.  need 
immediate adjustment, repair or replacement by a certified / 
authorized  representative  to  ensure  continued  proper 
functionality of fire-resistance and general operation of Lunax 
Door Systems. 
 
 

Gap Control 