Содержание PCD7.D412DTPF

Страница 1: ...Document 27 620 Release ENG07 2019 06 20 Manual I O modules for PCD1 PCD2 series and for PCD3 series PCD7 D412DTPF standard SVGA MB Panel and PCD7 D4xxxT5F programmable pWeb Panel ...

Страница 2: ...2 1 Technical data of the SVGA MicroBrowser panel 2 1 2 2 Technical data for the pWeb panels 2 2 2 2 1 Overview 2 2 2 2 2 Product related presentation 2 2 2 2 2 Battery of the pWeb panel 2 3 3 Logic controller of the programmable pWeb panel 3 1 Communications interfaces 3 4 3 1 1 On board RS 485 3 4 3 1 2 Additional communications ports using slot A Port no 1 3 5 3 1 2 1 PCD7 F110S Serial Interfac...

Страница 3: ...y DNS Server 5 2 5 2 Logic Controller pWeb panels only 5 3 5 2 1 Program Name 5 3 5 2 2 Status RUN or HALT 5 3 5 2 3 S BUS 5 3 5 3 Web Connection 5 5 5 3 1 Connection 5 5 5 3 2 Type no selection for pWeb 5 5 5 3 3 Start page 5 5 5 3 4 Remote Host IP 5 5 5 3 5 Remote Port 5 5 5 3 6 Connection List 5 5 5 4 System 5 6 5 4 1 Production data 5 6 5 4 2 Info 5 6 5 4 3 Settings 5 7 5 4 4 Special Settings ...

Страница 4: ... 15 7 6 3 Additional uBTerminal container for Save logs to File function 7 15 7 7 List of message box messages 7 16 8 Handling precautionary measures 8 1 Glass touchscreen 8 1 8 2 Information on the LCDs of the MB panel display 8 1 8 3 Care 8 1 9 General recommendations for the Web Editor 9 1 In the Project configurations 9 1 9 2 In the Web Editor project general information 9 1 9 3 Definition of ...

Страница 5: ...iables removed EN04 2013 05 31 HaMa Chapter 3 1 2 Description oft the communica tion modules PCD7 F1xxS for Slot A EN05 2014 01 20 HaMa New logo and new company name ENG06 2016 01 27 HaMa New fixation set ENG07 2019 06 20 HaMa Added the crossed bin logo for Waste of Electrical and Electronic Equipment WEEE disposal copied from Word to InDesign 0 3 Brands and trademarks Saia PCD and Saia PG5 are re...

Страница 6: ...lation of components of the PCD7 D4xxxT5F The following are discussed Definition of the connectors Power supply and consumption Dimensions Possible communications modes In other chapters more details can be found about Hardware Software Setup menu step by step and configuration Usage firmware update etc Maintenance Complementary manuals PG5 2 0 User guide 26 732 File System and FTP Server 26 855 E...

Страница 7: ... RTS232 4 CTS232 5 GND GND 6 DTR232 7 DSR232 8 COM232 9 DCD232 Power supply Earth 24V Connector 2 pole Communications 2 Ethernet switch 2 RJ 45 with LED indicator USB Standard USB slave Reset button Pushbutton 1 3 Voltage supply of the panel Pin Signal 1 24V 2 Earth Current supply 24 VDC 30 20 or 19 VAC 15 current supply with full wave rectifier Current consumption Power output without back light ...

Страница 8: ...imensions and cut out in mm 1 4 Dimensions and cut out in mm 1 4 1 12 1 panel 62 6 Front panel W H 319 264 Display W H 245 185 Cut out W H 300 244 1 4 2 10 4 panel 62 6 Front panel W H 281 221 Display W H 211 150 Cut out W H 262 202 1 4 3 5 7 panel 50 6 Front panel W H 202 156 Display 5 7 W H 117 88 Cut out W H 189 142 ...

Страница 9: ... sides Refer to the photos below Mounting parts of 12 1 panels Mounting parts of 10 4 panels Mounting parts of 5 7 panels Note It is helpful to have somebody hold the unit from the front side of the panel while the brackets are being installed The bolts require a 2 5 mm Allen key Screw the bolts into the brackets up to the point when you can still clip them onto the MicroBrowser without being obst...

Страница 10: ...d on a wall This is why we provide wall mounting kits for solid and cavity wall mounting In wall On wall In wall cavity walls On wall solid walls Mounting kit for the 5 7 MB panel PCD7 D457 IWS2 PCD7 D457 OWS2 Mounting kit for the 10 4 MB panel PCD7 D410 IWS PCD7 D410 OWS Mounting kit for the 12 1 MB panel PCD7 D412 IWS PCD7 D412 OWS 1 6 Operation and handling of the touchscreen To operate the tou...

Страница 11: ... are obvious ly also capable of displaying websites from controllers located within the network The procedure for this is the same as with the standard 12 SVGA panel Connecting to external devices If an ethernet connection to an Automation Server exists the HTTP connection can be established between our PCD7 D4xx and any SBC controller In the case of the programmable panels the panel is generally ...

Страница 12: ... generally used as a Service port It is used mainly to download new firmware programs onto the device The USB port meets the USB 1 1 specification Maximum speed 12 MBit s 1 7 3 Getting started with the Web Editor on the MicroBrowser panel PCD7 D4xx Detailed documentation can be downloaded from our website See manual 26 838 Manual Web Editor To get started with programming the MB panel some particu...

Страница 13: ...tions 2 1 Technical data of the SVGA MicroBrowser panel Display Display size 12 1 TFT Resolution SVGA 800 600 Backlight LED Colours 65 536 Contrast adjustment Yes On Board File System 128 MByte Operating system Saia PCD COSinuS with SBC MicroBrowser expansion Internet services Automation Server SBC MicroBrowser Interfaces Ethernet 10 100 M 2 RJ45 switch Current consumption Max 600 mA Voltage suppl...

Страница 14: ...icroBrowser Automation Server Interfaces Ethernet 10 100 M 2 RJ45 switch USB 1 1 2 0 1 client Serial interfaces RS 485 socket for PCD7 F1xxS communications module Temperature range Operation 0 50 C Storage 25 70 C Relative humidity Operation 10 80 Storage 10 98 non condensing Processor Coldfire CF5373L 240 MHz Real Time Clock RTC Yes with battery back up Battery Lithium Renata CR 2032 lifetime 1 3...

Страница 15: ... 1 3 years1 1 Depending on the ambient temperature The higher the temperature the shorter the buffer time New controllers include batteries in the scope of delivery and these must be inserted during commissioning Pay attention to the polarity of the batteries CPUs with lithium batteries are not maintenance free The battery voltage is moni tored by the CPU The status LED lights up 12 pWeb panel onl...

Страница 16: ...485 Network The pin no s of the connected PCD are explained in the respective manual Make sure that the terminators are properly terminated In the example below you can see a possible connection between the terminals and PCDs In order to avoid reflection on the communications channel the net work should be terminated with termination resistors The PCD7 D4xx has a switch for this 5 V PCD1 M2_ Port ...

Страница 17: ...guration can either be performed directly via the Setup menu on the pWeb panel or indirectly via the Hardware configuration on the PG5 Overwrite the current configuration the same as when making a change 3 1 2 Additional communications ports using slot A Port no 1 Slot A on the pWeb panels allows you to plug in optional modules for communica tions interfaces Only modules of the PCD7 F1xxS series a...

Страница 18: ...ly Connector pins Signal RS 232 Signal RS 485 0 GND GND 1 TXD D 2 RXD D 3 RTS 4 CTS 5 GND GND 6 DTR 7 DSR 8 COM 9 DCD Connector pins Signal 1 GND 2 NC 3 D 4 D Connector pins Signal 1 24 V 2 GND Installation PCD7 D410VT5F Earth 2 Ethernet switch USB Reset Switch PCD7 F1xxS RS 485 Power Supply Installation PCD7 D457VT5F Earth 2 Ethernet switch USB Reset Switch PCD7 F1xxS RS 485 Power Supply ...

Страница 19: ...2 connection Port x 1 10 pin spring loaded terminal block RS 422 PGND 10 TX 11 TX 12 RX 13 RX 14 PGND 15 RTS 16 RTS 17 CTS 18 CTS 19 PGND TX TX RX RX SGND RTS RTS CTS CTS Pin RS 422 Peripherie device Terminal 0 PGND Tx 1 2 Tx Rx 3 4 Rx PGND 5 6 RTS RTS 7 8 CTS CTS 9 RS485 connection Electrically connected RS 485 interface Port x 1 10 pin spring loaded terminal block RS 485 PGND PGND RX TX RX TX x0...

Страница 20: ...RS 232 connection Port x 1 RS 485 10 pin spring loaded terminal block 0 PGND TxD 1 2 RxD RTS 3 4 CTS PGND 5 6 DTR DSR 7 8 COM DCD 9 RS 232 connection to DTE RS 232 connection to DCE 6 DTR 0 PGND 1 TXD 2 RXD 3 RTS 4 CTS 5 PGND 7 DSR 9 DCD PGND TX RX RTS CTS SGND DTR DSR DCD cable Peripherie device DTE 8 Reserve PGND TX RX RTS CTS SGND DTR DSR DCD 0 PGND 1 TXD 2 RXD 3 RTS 4 CTS 5 PGND 6 DTR 7 DSR 9 ...

Страница 21: ... module and can be activated using the silde switch on the module PCD7 F150S RS 485 terminator Slider 1 2 ON C O Closed terminated Slider 1 2 ON C O Open not terminated factory setting RS485 connection 10 pin spring loaded terminal block Port x 1 RS 485 PGND PGND RX TX RX TX x0 x1 x2 RX TX RX TX GND RS 485 RS 485 RS 485 Peripherie device PCD Modul Terminal 0 PGND Rx Tx 1 2 Rx Tx 3 4 PGND 5 6 7 8 S...

Страница 22: ...Belimo MP Bus 10 pin spring loaded terminal block 0 PGND MP 1 2 MFT IN 3 4 PGND 5 6 7 8 SGD 9 MP Bus cabling 0 PGND Earth connection MP line 1 MP Multi point The MP Bus is the Belimo master slave bus Up to 8 slaves can be connected to a master device These are MFT 2 flap drives MFT 2 valve drives MFT fire damper drives VAV NMV D2M compact controller 2 MFT MFT programming unit internal MP Bus 3 IN ...

Страница 23: ...to generate the project However it can also be configured directly on the panel using the Setup menu described in Chapter 5 2 3 2 1 General information The following description assumes that the user is familiar with the PG5 software If this is not the case we recommend reading the manual 26 733 PG5 software requirements PG5 V 2 0 The device configurator defines direct access to pro gramming instr...

Страница 24: ... Running the device configurator The device configurator is used for hardware configuration setting up logs and I O handling Double click on the project tree icon to start the device configurator Use a right click to select the Device and use Change Device Type to set the panel to be configured The Download button can be used to download the configuration onto the pWeb Panel ...

Страница 25: ...owing procedure Open www sbc support com and download the latest firmware version Establish a connection between PG5 and the CPU the same way as when downloading an application in accordance with the available devices serial with PGU cable modem1 USB Ethernet In the Tools menu select Update Firmware and use the Browse function to select the path for the file with the new firmware version Make sure...

Страница 26: ...ion of the internal file sys tem The user is not able to see this partition 4 Options after download Execute program RUN Sets the PLC to RUN once the download is successfully completed Remain STOPPED After the download PLC remains STOPPED It is not possible to download only those blocks which have been modified The user program is downloaded into the on board memory in a file and after a restart o...

Страница 27: ...er program is already stored in the on board flash memory only the RAM DB text for the on board flash memory are stored to the folder PLC_SYS not visible to the user Note Registers flags timers and counters are not stored During a restore the DB text are copied back into the SRAM memory Backup to INTFLASH file system The values RAM DB text are stored in the internal PCD_Backup folder This allows t...

Страница 28: ...with error The same as Run but with an error mes sage green Run conditional with error The same as Run conditional but with an error message green green green Stop The status Stop occurs in the following cases Downloading with the option Remain in Stop status PGU stopped by programming unit red Stop with error The same as Stop but with an error mes sage red Halt The status Halt occurs in the follo...

Страница 29: ...iggered and the controller restarted Instruction SYSWR K 1000 Software Watchdog instruction R K x Parameters according to following table K constant or entered value Register x 0 The Software Watchdog is deactivated x 1 The Software Watchdog is activated if the instruction is not repeated within 200 ms a cold start is performed x 2 The Software Watchdog is activated if the instruction is not repea...

Страница 30: ...icroBrowser panel and programmable pWeb panel MicroBrowser SVGA panel PCD7 D 12 1 SVGA Programmable pWeb panels firmware 1 19 34 PCD7 D412DT5F 12 1 SVGA PCD7 D410VT5F 10 4 VGA PCD7 D457VT5F 5 7 VGA 4 1 Opening the Setup menu To call up the Setup menu Î Î Touch any area on the screen except the buttons for 4 seconds at any time Î Î Touch the icon displayed during startup see section 5 TITLE Î Î The...

Страница 31: ...tem Start screen see 5 4 3 Settings on page 5 7 Available for a few seconds only pressing on this icon will take you directly to the Setup menu Animated icon for Please wait data loading User defined System Start screen 5 4 3 Settings on page 5 7 4 3 Changing the password MB panels of the PCD7 D4xxxx series are supplied without a password on the Setup menu If however access to the Setup menu is su...

Страница 32: ...ocument 27 620 Release ENG07 2019 06 20 4 3 Using the Setup menu Saving and exiting 4 4 4 Saving and exiting If you have changed one or more parameters you must confirm if you want to save the changes to save reboot or to reset the new parameters without sav ing ...

Страница 33: ...nel settings See section 5 1 2 Logic Controller Configure the internal logic controller pWeb panels only See section 5 2 3 Web Connection Configure the web connection See section 5 3 4 System Info Settings Special Settings FW download Reboot See section 5 4 5 Display Display settings See section 5 5 6 Keyboard Virtual keyboard See section 5 6 7 Password Enter a password See section 5 7 8 Language ...

Страница 34: ...G5 device configu rator If the Device Configuration is updated via PG5 the data set in Setup is overwritten If you want this data to be carried over to the PG5 the configuration requires the configuration file to be uploaded into the PG5 project 5 1 1 DCHP On If DCHP is off an IP must be set by the user Otherwise all the necessary settings are acquired by the DCHP server 5 1 2 TCP IP address IP ad...

Страница 35: ...configuration file to be uploaded into the PG5 project 5 2 1 Program Name Displays the name of the loaded PG5 project 5 2 2 Status RUN or HALT Displays the status of the logic controller 5 2 3 S BUS Configuration of the S bus of the internal logic controller Î Î S Bus Station S bus station of the logic controller Î Î Serial Settings for the serial S bus connection Active Activates the serial conne...

Страница 36: ...e Baud rate Sets the baud speed of the serial S bus Start address First S Bus station on gateway End address Last S Bus station on gateway Speed Speed of connection Î Î IP For setting the IP address Active Activates S bus via IP PGU If PGU is activated the panel can be programmed via this interface Port Port of the IP connection Î Î IP Master Gateway Active For setting the master gateway Timeout T...

Страница 37: ...nnection with any PCD Connection is made with the local IP address 127 0 0 1 HTTP Direct Direct connection Ethernet only 5 3 3 Start page Name of the start page for this connection 5 3 4 Remote Host IP IP address of the connected PCD 5 3 5 Remote Port Remote port default 80 5 3 6 Connection List We advise you to establish one or more connections up to x16 from the List of Connections Edit the conn...

Страница 38: ... Î Î Production Date Month in which the device was produced Î Î Display Type Type of display internal designation Î Î HW LCD Rotation Rotation of the display 5 4 2 Info System info such as Firmware Version Booter Version etc Î Î Firmware Version Firmware version currently installed on the panel Î Î Booter Version Booter version currently installed on the panel Î Î M1 Expansion Info Indicates if an...

Страница 39: ...hed for first in INTFLASH Webpages Remote before local Remote before local means file teq gif etc are searched for on the re mote server before the local server on the MB panel is searched Î Î Start Delay s Start delay for restart min 1 sec max 15 sec Î Î Start screen Enter the greeting modify the welcome screen Startup text Freely definable greeting max 64 characters X position of the text Value ...

Страница 40: ...m from scratch After the Formatting OK message the device returns to the System menu Î Î Time Real Time Clock RTC Time Real Time Clock RTC enter time container uBT_RtcTime Date RTC enter date container uBT_RtcDate Time Server Active Activates deactivates the time server Î Î Memory Only in problem cases Outside of the permissible memory range Heap 1 2 3 and LR Î Î Show Runtime Info Extended command...

Страница 41: ...sted in a range between 0 and 5000 5 5 3 Rotation Landscape Portrait 5 5 4 Calibrate Touchscreen Carefully using the stylus 5 6 Keyboard 5 6 1 SIP Virtual Keyboard Activates deactivates SIP Soft Input Panel Virtual Keyboard 5 6 2 Name of the first keyboard You can choose from Alphapad teq alphanumeric or keypad teq numeric as the first keyboard to open 5 6 3 Width of the Focus in Pixels You can se...

Страница 42: ...m the password after entering it When you enter a new password you have to confirm it If the characters entered in the confirmation field do not match the new password the old password is re tained If you would like to disable password protection press the Enter key and confirm without inputting any characters Forgot your password Delete the file inflash config passwd dat FTP connection This will ...

Страница 43: ...n creased Forgot your password Delete this file TSPOINTS DAT For internal use INTFLASH WEBPAGES Directory for all project files which you want to save LOCALLY teq gif files etc INFLASH FONT FONT directory must be created by the user It contains all the special or additional bft files containing typefaces INFLASH TRENDLOGS TRENDLOGS directory is created automatically when logs are stored The CSV fi...

Страница 44: ...tion from No local file search to Local file search before remote 2 Copy all associated files teq gif to the corresponding subdirectories of INTFLASH WEB PAGES Each associated station has its own subdirectory The names of the subdirectories cor respond to the communication method HTTP direct communication IP address of the station with an underscore instead of a dot e g IP address 192 168 12 90 be...

Страница 45: ...errupted during the download process no notification appears on screen This is because the FW flash memory is erased at the start of the process 7 1 2 Safe Firmware Download via USB The safe method for downloading firmware is always via USB a Switch off the MB panel b At the top of the back cover os a hole of 3 mm in diameter It contains a button Take a narrow tipped pen or a small screwdriver any...

Страница 46: ...zer is activated with increasing frequency 4 Once the pitch or the frequency of the buzzer has stabilised after approx 10 sec release the Reset button and wait 5 You may have to wait to 1 to 2 minutes During this time the FW is reconstruct ing the whole organisation of the memory and recreating all the files which are required for the default settings Finally the MB panel reboots automatically and...

Страница 47: ...al symbol in pixels X dimension Width of a character Text length Length of a single line piece of text Text field Length of the painter General recommendations for text fields you can find info in the online help for the first version of Web Editor We recommend using text fields exceeding the size displayed in the Editor by up to 20 To determine the text field length you can also consult the follo...

Страница 48: ...idth 5 Font size ySize min x Size max x Size Arial 36 41 7 36 Arial 24 28 7 24 Arial 20 23 6 20 Arial 16 19 3 16 Arial 12 15 3 12 Arial 10 12 3 10 Arial Bold 36 41 9 35 Arial Bold 24 28 7 23 Arial Bold 20 23 6 20 Arial Bold 14 16 4 15 CourierNew 20 23 12 12 CourierNew 16 19 10 10 CourierNew 12 14 7 7 CourierNew 10 12 6 6 CourierNew Bold 20 23 12 12 CourierNew Bold 14 17 8 8 Tahoma 24 29 5 24 Tahom...

Страница 49: ...ion for Sales Companies restricted Area Files containing typefaces for specific languages or fonts formats sizes not appearing in the list can also be installed on an MB panel If you want to do so please contact SBC Support To ensure that all characters are supported we recommended using the Arial typeface This is particularly the case for languages with a large number of characters such as Chines...

Страница 50: ... different files can be registered When a character is required the front file is opened and the data for the characters is called up The data is intended for subsequent use Î Î Name of the font files max 24 ASCII characters without spaces including file extension Î Î To install font files copy the files to the FTP server of the MB panel via an FTP connection Î Î Chinese fonts 12 is the smallest l...

Страница 51: ...na Chinese etc we recommend sticking with the default settings for the text position not centred or justified In some typefaces it is not possible to represent all Unicode characters We recommend using the Arial Unicode MS or MS Sans Serif typefaces as they are well suited to use with Unicode characters Do not edit the CSV file in the S Web Editor directly because the text window of the S Web Edit...

Страница 52: ...e a button with the following action parameters Actions Set Vari ables The type is the Container the name is LANGUAGE and then the Unicode csv file We recommend copying the csv files into the local server of the MicroBrowser panel under INTFLASH Webpages Î Î For information on the topic of multilingual displays see also Multilingual HMIs in the online help of the Web Editor ...

Страница 53: ... typeface 5 Arial same format reduce size to next possible size 6 Arial simple reduce size to next possible size If there is no smaller typeset for Arial 7 Arial same format or simple use the smallest available font size If you replace a typeset then this is logged in the log file 7 5 4 Web Editor Unicode character sets are available using the source type HTML TAG in the Web Editor and with a CSV ...

Страница 54: ...an be started by setting an interval time 0 30 000 mSec for the pulsed signal A 50 pulse pause ratio is used i e the pulse time is equal to the pause time Changes made while the alarm is already sounding are ignored At a setting of 0 however the alarm is immediately deactivated The alarm is stopped immediately by touching the screen R W uBT_AlarmVolume Decimal value string 10 0 20 100 Volume of th...

Страница 55: ...y uBT_BooterVersion ANSI text string Current version string 0 8 Firmware booter version String read only R W uBT_BuzzFreq ANSI text string 1000 125 8000 Frequency settings of the acoustic signal from touching 125 250 500 100 0 2000 4000 8000 If using the touch function to define the pitch of the acoustic signal when touching the screen R W uBT_BuzzOnOff Boolean value string 1 On 0 1 Acoustic signa...

Страница 56: ...he cache memory The cache memory is wiped upon startup and URL jumps Image files are decompressed and cached in a separate always acti vated video cache This video cache is wiped upon startup URL jumps and whenever too much data has been loaded When this occurs all necessary files are reloaded and decompressed R W uBT_EnableSIP Boolean value string 1 acti vated 0 1 Read write SIP à Select the Soft...

Страница 57: ... string 350 0 639 Position of the startup text horizontal position from the left R W uBT_IntroTextYPos Decimal value string 300 0 479 Position of the startup text vertical position from the top down R W uBT_TCPIPAddr String IP address 0xC0 A8 0C 5A 192 168 12 90 Read write the TCP IP address of the terminal own address within the subnet being used If the setting is changed a restart is required Th...

Страница 58: ...Setup Text Enter show pay attention to upper lowercase A pop up window opens on the terminal containing the Setup menu R W uBT_SubNetMask String IP address 0xFF FF FF 00 Read write subnet mask of the subnet used by the terminal If a change is made a restart will be necessary This will mean FTP connections are lost Read only uBT_Version ANSI text string Current version string 0 32 Firmware version ...

Страница 59: ...T_TrendLoad File currently loaded Read Write uBT_TrendSelect Last file in the directory File currently selected When saving a trend the value is set with the saved file name Read Write uBT_TrendOldest Change to the uBT_TrendSelect container Used for button actions Select oldest file Write only uBT_TrendNewest Select newest file Write only uBT_TrendPrev Select previous file Write only uBT_TrendNext...

Страница 60: ...rends Out of memory in heap 3 Î Î Usually displayed due to there being too many data points Offline trend alarm events HD log and online trend are stored in heap 3 Total amount of memory used by offline trend data and HD log is 1280 kbytes see section 13 Before using trends you must first calculate the amount of memory required Online trends If update period of process points Web Editor para meter...

Страница 61: ...uid in the LCD display contains an irritant Should this fluid come into contact with your skin rinse the area affected under running water for at least 15 minutes Should fluid from the LCD display get into your eyes rinse out your eyes under running water for at least 15 minutes and seek medical attention Features of the LCD display The colours and brightness of the individual MB panel displays ar...

Страница 62: ...er name must not contain any underscores or signs i e not PDP ADDRESS COFF_containername PDP FOR MAT Consider that the suffix for container offset is d for a decimal and k for the for mat HH MM Use Online trends macros with the right timestamp The time server must be activated in the Setup menu For information on calculating the amount of memory required see 9 5 3 De compression of Gif files analy...

Страница 63: ...t tool for a hardware reset Do not use a paperclip or pin but rather push the microswitch carefully with a Ø 3 mm drill bit 9 5 Some rules regarding gif images The three timestamps on the MB panel s graphical display are Repaint video cache Decompression in the video cache in case of URL jump and after startup almost linear with the number of pixels See 9 5 3 Decompression of Gif files analysis ca...

Страница 64: ... project with no gif list and you do not have to wait until all gif files in the gif list have been decompressed Decom pression continues in the background until the video memory is full if there are multiple gif files in the gif list See 9 5 3 Decompression of Gif files analy sis calculation on page 9 4 Operation of Open MicrosoftP PNotepad Editor Write the following header text for the file PATH...

Страница 65: ... jump to the correct first page of the project 9 5 3 Decompression of Gif files analysis calculation Available for the solutions from sections 9 5 1 and 9 5 2 How do you analyse the number of gifs in the video cache based on the number of pixels in the gif images The video cache has a total size permanent and flush able of 16 MByte Of this 4 to 6 Mbyte are used for the permanent cache The remainin...

Страница 66: ... 3 1280 kbytes 2048 kbytes 4096 kbytes out of memory for language resource or LR out of memory 512 kbytes 768 kbytes 1024 kbytes 9 7 Extended alarm macros 9 8 Trend macros for MB panels with save logs to files The Web Editor macro library does not contain any special trend macros with S2F save to files for MicroBrowser panels These macros must for the moment be downloaded on the Support screen and...

Страница 67: ...rendMacro MB_ HDlog macros with S2F Î Î MacroLib SBCTrendMacro MB_ trend macros with S2F The applies to Online Trends Offline Trends DBs and Offline Saved Trends which allow you to play back all of the stored files Î Î MacroLib SBCHDLogTrendMacro MB_ HDlog macros with S2F This applies to Remote Offline Saved Trends HDlog macros Section 7 6 3 Additional uBTerminal container for Save logs to File fu...

Страница 68: ...igate through the list of saved files using the buttons and select one of them 7 Navigate through the list of files with the same prefix 8 Prefix name Free characters which are available as a prefix max 5 characters Do not modify the prefix name between the login processes Such carelessness can cause problems The name is used to identify a group of CSV files 9 Loaded Trend Not in the online trend ...

Страница 69: ...anual PCD7 D412DTPF PCD7 D4xxxT5F Document 27 620 Release ENG07 2019 06 20 9 8 General recommendations for the Web Editor 9 FTP access By selecting FTP access you can display and read the list of CSV files In INTFLASH TRENDLOGS ...

Страница 70: ...he reader of the risk to components from electrostatic discharges caused by touch Recommendation Before coming into contact with electrical components you should at least touch the Minus of the system cabinet of PGU connector It is better to use a grounding wrist strap with its cable permanently attached to the Minus of the system This sign accompanies instructions that must always be followed Exp...

Страница 71: ...10 Part 1 WARNING Safety Check compliance with nominal voltage before commissioning the device see type label Check that connection cables are free from damage and that when wiring up the device they are not connected to voltage NOTE In order to avoid moisture in the device due to condensate build up acclimatise the device at room temperature for about half an hour before connecting CLEANING The d...

Страница 72: ...al and Electronic Equipment directive This symbol on our product shows a crossed out wheelie bin as required by law regarding the Waste of Electrical and Electronic Equipment WEEE disposal This indicates your responsibility to contribute in protecting the environment by proper disposal of this waste i e not disposing of this product with your other wastes To know the right disposal mechanism pleas...

Страница 73: ...fstrasse 18 3280 Murten Switzerland Phone 41 265803000 Fax 41 265803499 Email support support saia pcd com Supportsite www sbc support com SBC site www saia pcd com International Represetatives SBC Sales Companies www saia pcd com contact Postal address for returns from customers of the Swiss Sales office Saia Burgess Controls AG Service Après Vente Bahnhofstrasse 18 3280 Murten Switzerland ...