Earthing concept / Installation / Switch-on

Commissioning 

3-2

3

3.2 

Earthing concept

To ensure that electrical faults are dealt with safely, the following points should be 

observed:
● 

Connect device and switching cabinet by the shortest route to a central    

 

earthing point.

● 

Ensure lowest impedance possible in connection between device and switching  

 

cabinet.

● 

All data cables connected to the device should use shielded lines.

● 

The shields should be earthed at both ends. There must be a low-resistance  

 

connection between the linked systems. High equalising currents across the  

 

shield resulting from potential differences must be avoided.

● 

Earth connection to use green/yellow cable with min. 4 mm² cross-section.

3.3 

Installation

The device should be installed in an RF shielded housing or a metal switching 

cabinet.
Adequate ventilation must be provided. To ensure that the heat generated in the 

device can be dissipated, a 100 mm space must be kept clear around the unit.
The unit must be disconnected from the power supply for installation and de-

installation.
Only the assembly components supplied should be used to mount the unit in the 

housing. The type and number of assembly components is dependent on the device 

(see Technical Details).
The dimensions specified for the holes in the front plate must be adhered to, to 

maintain IP 65 (front) protection (see Technical Data). 
Failure to observe the above instructions could cause damage to the device.

3.4 

Switch-on

Start-up: The PCD7.D61xx units boot up and load the operating system 

independently.

Содержание PCD7.D6120TV010

Страница 1: ...Hardware Manual Document 26 844 Version E1 30 04 2006 The PCD7 D61xx series Controls Division...

Страница 2: ...on 3 Commissioning 3 1 Power supply 3 1 3 2 Earthing concept 3 2 3 3 Installation 3 2 3 4 Switch on 3 2 4 Technical data 4 1 Physical dimensions 4 1 4 2 Electrical data 4 5 4 3 Environmental condition...

Страница 3: ...nitial version 0 2 Trademarks Saia is a registered trademark of Saia Burgess Electronics AG Microsoft Windows 2000 Windows XP Windows CE and the Windows logo are either registered trademarks or tradem...

Страница 4: ...nstructions Wherever hazardous faults could occur in the automation system i e a fault could cause major damage to materials or people additional external precautions must be taken or devices installe...

Страница 5: ...product described in this documentation EMC Directive DC power supply Devices with DC power supply meet the requirements of EC Directive 89 336 EEC on electromagnetic compatibility and are suitable fo...

Страница 6: ...cription 2 1 2 2 Product description The series comprises the PCD7 D6120TV010 and PCD7 D6150TV010 models User side Colour TFT display with resistive touch PCD7 D6120TV010 and PCD7 D6150TV010 Slot side...

Страница 7: ...transformer must comply with EN60742 The supply voltage must be checked against the type plate When wiring the power supply and the connector the details on the type plate must be observed Before comm...

Страница 8: ...voided Earth connection to use green yellow cable with min 4 mm cross section 3 3 Installation The device should be installed in an RF shielded housing or a metal switching cabinet Adequate ventilatio...

Страница 9: ...Technical data 4 1 4 4 Technical data 4 1 Physical dimensions PCD7 D6120TV010 exterior ush mounting dimensions Front plate Width 364 0 mm Height 296 0 mm Aperture size Width 345 0 mm Height 277 0 mm...

Страница 10: ...Burgess Controls Ltd Physical dimensions Technical data 4 2 4 PCD7 D6120TV010 dimensions Blick auf die Ger teoberseite Seitenansicht Blick auf die Ger ter ckseite Seitenansicht Blick auf die Ger teunt...

Страница 11: ...ysical dimensions Technical data 4 3 4 PCD7 D6150TV010 exterior ush mounting dimensions Front plate Width 452 0 mm Height 357 0 mm Aperture size Width 429 0 mm Height 334 0 mm Depth 124 5 mm Weight ap...

Страница 12: ...ess Controls Ltd Physical dimensions Technical data 4 4 4 PCD7 D6150TV010 dimensions Seitenansicht Blick auf die Ger teoberseite Blick auf die Ger ter ckseite Blick auf die Ger teunterseite Seitenansi...

Страница 13: ...range 0 45 C Memory Working memory 256 MByte Processor type 1 GHz VIA C3 Chipset VIA 133T integrated graphics Memory card external 128 256 512 MB 1 GB 2 GB Slots PC 104 Interfaces Serial 2x RS232 for...

Страница 14: ...he EPC units are tted with a CFA standard type 1 compact ash slot as standard Position of compact ash slot Ejection lever Only compact ash cards from SANDISK may be used in conjuction with the EPC The...

Страница 15: ...net 1 2 RJ45 USB 1 2 PS2 mouse keyboard PS 2 mouse and keyboard may only be plugged or removed with the unit switched off Otherwise these input devices will not be recognised by the operating system A...

Страница 16: ...ositive pole of the battery must point upwards be visible When the battery is changed the real time clock data will be lost Do not short circuit the battery contacts Risk of explosion Battery should o...

Страница 17: ...f the risk to components from electrostatic discharges caused by touch Recommendation at least touch the Minus of the system cabinet of PGU connector before coming in contact with the electronic parts...

Страница 18: ...a Burgess Controls Ltd Address Appendix 6 2 6 Address of Saia Burgess Saia Burgess Controls AG Bahnhofstrasse 18 CH 3280 Murten Switzerland Tel 41 26 672 71 11 Fax 41 26 672 74 99 E mail pcd saia burg...

Отзывы: