OPERATING INSTRUCTIONS 

MATCOR Rectifier

+1 800 523 6692

matcor.com

CONTACT A CORROSION EXPERT

 

     

SYMPTOM

REMEDY

No DC current and no DC voltage output.

Check AC overload protection for blown fuses or tripped 

circuit breakers. Check AC power supply.

No DC current but DC voltage is present.

Check DC ammeter. Check DC connections and external 

DC circuit for continuity.

DC current reading but no DC voltage.

Check DC voltmeter.

Maximum DC current cannot be obtained at maximum DC 

voltage.

Check load resistance of external DC circuit. Check shunt 

and ammeter.

Maximum DC voltage cannot be obtained.

Check AC line voltage. Check voltage adjustment taps for 

maximum setting. Check accuracy of DC voltmeter.

TWO-YEAR GUARANTEE

Each and every cathodic protection rectifier of MATCOR, Inc. design is guaranteed against defects in design, 
workmanship or material for a period of two full years from the date of shipment from the factory. 
The obligation of MATCOR, Inc. is limited to the adjustment, repair or replacement, at its factory, of any rectifier or part 
thereof which shall be found by MATCOR, Inc. to be defective.
This guarantee does not cover costs or loss for engineering, storage, handling, shipping, installation and removal 
associated with the damaged rectifier or part, or any other costs, loss or damage of any kind.

UNDER NO CIRCUMSTANCES SHALL MATCOR, INC. BE LIABLE FOR ANY CONSEQUENTIAL DAMAGES.

FIVE-YEAR TRANSFORMER GUARANTEE

Each and every transformer installed as original equipment in a cathodic protection rectifier of MATCOR, Inc. design is 
guaranteed against defects in design, workmanship or material for a period of five full years from the date of shipment 
from the factory. The obligation of MATCOR, Inc. is limited to the adjustment, repair or replacement, at its factory, of any 
transformer which shall be found by MATCOR, Inc. to be defective.
This guarantee does not cover costs or loss for engineering, storage, handling, shipping, installation and removal 
associated with the damaged transformer or any other costs, loss, or damage of any kind.

UNDER NO CIRCUMSTANCES SHALL MATCOR, INC. BE LIABLE FOR ANY CONSEQUENTIAL DAMAGES.

V. TROUBLE SHOOTING

Refer to the rectifier circuit diagram.