5. Charging in service
■
Continuous parallel operation,
with
occasional battery discharge.
Recommended charging voltage:
❑
for two level charge:
• float level
= 1.42 V/cell for SNL
= 1.40 V/cell for SNH and SNM
• high level
= 1.47 - 1.70 V/cell for SNL
= 1.45 - 1.70 V/cell for SNH and SNM
A high voltage will increase the speed
and efficiency of the recharging;
❑
for single level charge:
1.43 -1.50 V/cell.
■
Buffer operation,
where the load
exceeds the charger rating.
Recommended charging voltage:
1.50 - 1.60 V/cell.
■
Discontinuous operation,
with short
heavy-current discharges or other
shallow discharges.
8 h with the current in the table or
15 h at 1.65 V/cell.
6. Periodic Maintenance
■
Keep the battery clean using only
water.
Do not use a wire brush or solvents of
any kind. Vent caps can be rinsed in
clean water if necessary.
■
Check the electrolyte level. Never
let the level fall below the lower mark.
Use only distilled or deionized water
to top up. Experience will tell the time
interval between topping up.
■
Check at least once yearly that all
connectors are tight.
The connectors and terminal screws
should be corrosion-protected by
coating with a thin layer of neutral
vaseline or anti-corrosion oil.
■
Check the charging voltage.
In parallel operation, it is of great
importance that the recommended
charging voltage remains unchanged.
The charger should be checked at
least once yearly.
High water consumption of the battery
is usually caused by improper voltage
setting of the charger.
7. Changing electrolyte
In most stationary battery applications,
the electrolyte will retain its effectiveness
for the life of the battery. However,
under special battery operating
conditions, if the electrolyte is found
to be carbonated, the battery
performance can be restored by
replacing the electrolyte.
The electrolyte type to be used for
replacement in these cells is: E13.
Refer to "Electrolyte Instructions".
Advanced and Industrial Battery Group
156, avenue de Metz
93230 Romainville - France
Tel.: + 33 (1) 49 15 36 00
Fax: + 33 (1) 49 15 34 00
Doc N° 06.99 - 21080.2
Published by the Communication Department
Data in this document are subject to change
without notice and become contractual
only after written confirmation.
SNH 9
1.8
0.22
0.73
15
M6
SNH 12
2.4
0.20
0.66
15
M6
SNH 17
3.4
0.18
0.60
15
M6
SNH 21
4.2
0.34
1.1
25
M6
SNH 25
5.0
0.32
1.1
25
M6
SNH 29
5.8
0.30
0.98
25
M6
SNH 34
6.8
0.28
0.92
25
M6
SNH 40
8.0
0.79
2.6
35
M8
SNH 50
10
0.74
2.4
35
M8
SNH 60
12
0.69
2.3
35
M10
SNH 70
14
0.64
2.1
35
M10
SNH 80
16
0.69
2.0
35
M10
SNH 90
18
0.96
3.1
50
M10
SNH 100
20
0.91
3.0
50
M10
SNH 110
22
0.86
2.8
50
M10
SNH 120
24
0.81
2.7
50
M10
SNH 130
26
1.05
3.4
50
M10
SNH 145
29
0.98
3.2
50
M10
SNH 155
31
0.92
3.0
50
M10
SNH 185
37
1.34
4.4
70
2 x M10
SNH 210
42
1.22
4.0
70
2 x M10
SNM 9
1.8
0.24
0.77
15
M6
SNM 14
2.8
0.22
0.72
15
M6
SNM 22
4.4
0.19
0.62
15
M6
SNM 31
6.2
0.16
0.53
15
M6
SNM 39
7.8
0.32
1.0
25
M6
SNM 47
9.4
0.29
0.94
25
M6
SNM 55
11
0.26
0.84
25
M6
SNM 70
14
0.75
2.4
35
M8
SNM 90
18
0.66
2.1
35
M8
SNM 110
22
0.62
2.0
35
M10
SNM 130
26
0.55
1.8
35
M10
SNM 145
29
0.89
2.9
50
M10
SNM 165
33
0.82
2.7
50
M10
SNM 185
37
0.75
2.5
50
M10
SNM 215
43
0.95
3.1
50
M10
SNM 240
48
0.86
2.8
50
M10
SNM 285
57
1.30
4.2
70
2 x M10
SNM 310
62
1.21
4.0
70
2 x M10
SNM 335
67
1.13
3.7
70
2 x M10
SNL 10
2.0
0.24
0.77
15
M6
SNL 15
3.0
0.22
0.72
15
M6
SNL 21
4.2
0.21
0.67
15
M6
SNL 30
6.0
0.18
0.58
15
M6
SNL 38
7.6
0.32
1.0
25
M6
SNL 45
9.0
0.32
1.0
25
M6
SNL 59
12
0.28
0.90
25
M6
SNL 70
14
0.79
2.6
35
M8
SNL 85
17
0.70
2.3
35
M10
SNL 105
21
0.70
2.3
35
M10
SNL 135
27
0.60
2.0
35
M10
SNL 170
34
0.91
3.0
50
M10
SNL 205
41
0.82
2.7
50
M10
SNL 220
44
1.05
3.4
50
M10
SNL 260
52
0.93
3.0
50
M10
SNL 310
62
1.35
4.4
70
2 x M10
SNL 355
71
1.23
4.0
70
2 x M10
* value for E22
Cell type
Charging Current
Electrolyte per cell
Quantity of oil
Cell connection
0.2C5 (A)
Solid* (kg)
liquid (l)
ml/vent
bolt per pole