SSR-202 Wiegand proximity card reader 

Setup instructions 

 

 
Copyright© 2009 

– Saflec Systems (Pty) Ltd 

www.safsys.co.za 

Setup instructions 
 

Connections - Reader to controller 

 
 
 
 
 
 
 
 
 
 
 

 
 
 
 
 
 
 
 
Figure 5 

Wiegand wiring diagram 

 
Step 1: Set the reader to 26 bit or 34 bit Wiegand mode 

(See Fig 6)

 

The SSR-202 can be set into 26 bit, 34 bit or any bitlength Wiegand 

– this will affect the number 

that is read from the proximity cards, so the correct setting must be applied and must be 
standardised throughout the system to avoid problems. 
 

To set 26 bit Wiegand format (24 bit data length) set the rotary dipswitch on the 
back of t

he reader to ‘A’. 

 

To set 34 bit Wiegand format (32 bit data length) set the rotary dipswitch on the 
back of the reader to ‘B’. 

 

Figure 6 

Bit length settings 

 
Note

: The settings 0..9 are used for RS-485 mode and the C to F are reserved for other purposes 

and should not be set in Wiegand mode. 

Содержание SSR-202

Страница 1: ...ard frequency of 125 kHz including Hitag 1 Hitag 2 and HT4102 It includes a tri color LED for indication of the scanner status and a Piezo buzzer to indicate a successful card read This unit comes with a splash proof back cover and can be mounted in any orientation using the mounting screw holes This reader has been designed to be used with the following devices SDC 510 Single door controller SDC ...

Страница 2: ...s will affect the number that is read from the proximity cards so the correct setting must be applied and must be standardised throughout the system to avoid problems To set 26 bit Wiegand format 24 bit data length set the rotary dipswitch on the back of the reader to A To set 34 bit Wiegand format 32 bit data length set the rotary dipswitch on the back of the reader to B Figure 6 Bit length setti...

Страница 3: ...ta 0 Data 1 and Present The Present data line is not always required and can normally be ignored The indication lines Red LED Green LED and Buzzer Connect these lines ensuring that the correct cables are used Step 3 Connect the power See Fig 5 Connect the power lines to the reader making sure that correct polarity is observed Note The power supply must be a 12 Volt DC power supply capable of suppl...

Страница 4: ...0 C to 70 C Storage Temperature 10 C to 80 C Enclosure Rating IP54 Digital Outputs Wiegand Specification Open collector transistor output with 4k7 Pullup Resistor to 5V DC Max Voltage on terminal 2 to 20V referenced to ground Max Load 100ma Digital Inputs Wiegand Specification TLL input with 4k7 Pullup Resistor to 5V DC Max Voltage on terminal 10 to 20V referenced to ground V Input Low 1V V Input ...

Отзывы: